Summary
PRCOM20162363
Building Permit - Commercial
Final Completion
PARTIAL COMMERCIAL
FOUNDATION AND UNDERSLAB ONLY PERMIT FOR NEW 4 STORY APARTMENT BUILDING REF: PRCOM20161761 FOR FULL BUILDING PERMIT
09/14/2016
10/10/2016
06/28/2017
Locations
Contacts
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
BLUE RIVER PLUMBING INC, Address:9125 BARTON ST, Phone:(913) 701-6410  
LYNN ELECTRIC & COMMUNICATIONS INC, Address:725 N 2ND ST STE K, Phone:(785) 843-5709  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/14/2016 10/06/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Partial Commercial $1,055.48 $1,055.48 Paid 10/10/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 12/12/2016 12/12/2016
Misc
Partial Correction
12/12/2016
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS.
Footing Inspection - Commercial Partial 12/30/2016 (8:00) 12/30/2016 12/30/2016
Misc
Partial Correction
12/12/2016
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. 12/30-OK THE ELEVATOR SLAB
Foundation Inspection - Commercial Passed 1/11/2017 01/11/2017
Underslab Plumbing Inspection - Commercial Partial 2/7/2017 2/7/2017 02/07/2017
Misc
Partial Correction
02/07/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Passed 2/8/2017 2/8/2017 02/08/2017
Misc
Resolved
02/08/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Resolved
02/08/2017
RADON COLLECTION PIPING SYSTEM FOUND INSTALLED PER REVISION /1\ ON DRAWING SHEET 2.00.
Underslab Electrical Inspection - Commercial Partial 2/8/2017 02/08/2017
Misc
Partial Correction
02/08/2017
OK TO COVER WHEN READY DEEP UNDER-SLAB ELECTRICAL CONDUIT FROM UNDER EAST FOOTING TO ELECTRICAL ROOM
Footing Inspection - Commercial Partial 2/16/2017 (1:00) 2/16/2017 02/16/2017
Misc
Partial Correction
12/30/2016
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. 12/30-OK THE ELEVATOR SLAB
Misc
Partial Correction
02/16/2017
OK TO POUR POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR.
Underslab Electrical Inspection - Commercial Passed 2/8/2017 02/21/2017
Misc
Resolved
02/21/2017
OK TO COVER WHEN READY DEEP UNDER-SLAB ELECTRICAL CONDUIT FROM UNDER EAST FOOTING TO ELECTRICAL ROOM
Foundation Inspection - Commercial Passed 2/9/2017 2/21/2017 02/21/2017
Underground Electrical Inspection - Commercial Partial 2/23/2017 3/16/2017 03/16/2017
Misc
Partial Correction
03/16/2017
NO MATERIAL OR WORKMANSHIP ISSUES FOUND ON DATACOMM CONDUITS RUN FROM FOOTING ELEVATION UP OUTSIDE OF BUILDING WEST FOUNDATION WALL -- THREE 3"; TWO 1-1/4"; ONE 3/4"
Footing Inspection - Commercial Partial 3/20/2017 (8:00) 3/20/2017 03/20/2017
Misc
Partial Correction
02/16/2017
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. 12/30-OK THE ELEVATOR SLAB
Misc
Partial Correction
02/16/2017
OK TO POUR POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR.
Misc
Partial Correction
03/20/2017
OK TO POUR WHEN READY RETAINING WALL FOOTINGS AT SW & NW
Concrete Walls and Columns Inspection Partial 3/23/2017 03/23/2017
Misc
Partial Correction
03/23/2017
OK TO POUR WHEN READY C.I.P. CONCRETE WING WALLS AT: OUTSIDE SW & NW CORNERS OF BLDG
Footing Inspection - Commercial Partial 4/12/2017 (10:30) 4/12/2017 04/12/2017
Misc
Partial Correction
03/20/2017
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. 12/30-OK THE ELEVATOR SLAB
Misc
Partial Correction
03/20/2017
OK TO POUR POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR.
Misc
Partial Correction
03/20/2017
OK TO POUR WHEN READY RETAINING WALL FOOTINGS AT SW & NW
Misc
Partial Correction
04/12/2017
OK TO POUR WHEN READY TRENCH FOOTINGS AT BOTH DETACHED GARAGES. ENSURE MIN 3" RE-BAR CLEARANCE TO BOTTOMS AND BANKS DURING POUR.
Foundation Inspection - Commercial Partial 4/17/2017 (9:00) 4/17/2017 04/17/2017
Misc
Resolved
04/17/2017
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. 12/30-OK THE ELEVATOR SLAB
Misc
Resolved
04/17/2017
OK TO POUR POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR.
Misc
Resolved
04/17/2017
OK TO POUR WHEN READY RETAINING WALL FOOTINGS AT SW & NW
Misc
Resolved
04/17/2017
OK TO POUR WHEN READY TRENCH FOOTINGS AT BOTH DETACHED GARAGES. ENSURE MIN 3" RE-BAR CLEARANCE TO BOTTOMS AND BANKS DURING POUR.
Misc
Partial Correction
04/17/2017
OK TO POUR POST-TENSIONED DETACHED GARAGE FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR.
Underground Electrical Inspection - Commercial Partial 4/21/2017 4/21/2017 04/21/2017
Misc
Partial Correction
03/16/2017
NO MATERIAL OR WORKMANSHIP ISSUES FOUND ON DATACOMM CONDUITS RUN FROM FOOTING ELEVATION UP OUTSIDE OF BUILDING WEST FOUNDATION WALL -- THREE 3"; TWO 1-1/4"; ONE 3/4"
Misc
Partial Correction
04/21/2017
OK TO COVER WHEN READY SECONDARY SERVICE CONDUITS FROM TRANSFORMER LOCATION AT NE CORNER OF BLDG #2 TO BLDG ENTRY AT SW CORNER OF BLDG #3;
Underground Electrical Inspection - Commercial Partial 4/25/2017 4/25/2017 04/25/2017
Misc
Partial Correction
04/21/2017
NO MATERIAL OR WORKMANSHIP ISSUES FOUND ON DATACOMM CONDUITS RUN FROM FOOTING ELEVATION UP OUTSIDE OF BUILDING WEST FOUNDATION WALL -- THREE 3"; TWO 1-1/4"; ONE 3/4"
Misc
Partial Correction
04/21/2017
OK TO COVER WHEN READY SECONDARY SERVICE CONDUITS FROM TRANSFORMER LOCATION AT NE CORNER OF BLDG #2 TO BLDG ENTRY AT SW CORNER OF BLDG #3; THREE 3" FROM XFRMR LOC @ S END OF #7 PARTIAL TO 20' SOUTH;
Underground Electrical Inspection - Commercial Partial 4/26/2017 4/26/2017 04/26/2017
Misc
Partial Correction
04/25/2017
NO MATERIAL OR WORKMANSHIP ISSUES FOUND ON DATACOMM CONDUITS RUN FROM FOOTING ELEVATION UP OUTSIDE OF BUILDING WEST FOUNDATION WALL -- THREE 3"; TWO 1-1/4"; ONE 3/4"
Misc
Partial Correction
04/25/2017
OK TO COVER WHEN READY SECONDARY SERVICE CONDUITS FROM TRANSFORMER LOCATION AT NE CORNER OF BLDG #2 TO BLDG ENTRY AT SW CORNER OF BLDG #3; THREE 3" FROM XFRMR LOC @ S END OF #7 SOUTH TO N END OF #3;
Footing Inspection - Commercial Partial 4/27/2017 (1:15) 4/27/2017 04/27/2017
Misc
Partial Correction
04/27/2017
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT LOWER BLDG N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT UPPER BLDG N, W, & S. UFER JUMPERS INSTALLED AT N & S ENDS. 12/30-OK THE ELEVATOR SLAB
Misc
Partial Correction
04/27/2017
OK TO POUR POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR
Misc
Partial Correction
04/27/2017
OK TO POUR WHEN READY RETAINING WALL FOOTINGS AT SW & NW
Misc
Partial Correction
04/27/2017
OK TO POUR WHEN READY TRENCH FOOTINGS AT BOTH DETACHED GARAGES. ENSURE MIN 3" RE-BAR CLEARANCE TO BOTTOMS AND BANKS DURING POUR.
Underslab Plumbing Inspection - Commercial Passed 5/10/2017 5/10/2017 05/10/2017
Footing Inspection - Commercial Partial 5/11/2017 (1:45) 5/12/2017 05/12/2017
Misc
Resolved
05/12/2017
OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT LOWER BLDG N, E, & S. NO UFER JUMPERS INSTALLED IN THESE SECTIONS. OK TO POUR WHEN READY PERIMETER FOOTING & INTEGRAL COLUMN FOOTINGS AT UPPER BLDG N, W, & S. UFER JUMPERS INSTALLED AT N & S ENDS. 12/30-OK THE ELEVATOR SLAB
Misc
Resolved
05/12/2017
OK TO POUR LOWER LEVEL POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR
Misc
Resolved
05/12/2017
OK TO POUR WHEN READY RETAINING WALL FOOTINGS AT SW & NW
Misc
Resolved
05/12/2017
OK TO POUR WHEN READY TRENCH FOOTINGS AT BOTH DETACHED GARAGES. ENSURE MIN 3" RE-BAR CLEARANCE TO BOTTOMS AND BANKS DURING POUR.
Misc
Partial Correction
05/12/2017
OK TO POUR UPPER LEVEL POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR
Foundation Inspection - Commercial Passed 5/22/2017 05/22/2017
Misc
Resolved
05/22/2017
OK TO POUR POST-TENSIONED DETACHED GARAGE FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR.
Underground Electrical Inspection - Commercial Partial 5/25/2017 5/25/2017 05/25/2017
Misc
Partial Correction
04/26/2017
NO MATERIAL OR WORKMANSHIP ISSUES FOUND ON DATACOMM CONDUITS RUN FROM FOOTING ELEVATION UP OUTSIDE OF BUILDING WEST FOUNDATION WALL -- THREE 3"; TWO 1-1/4"; ONE 3/4"
Misc
Partial Correction
04/26/2017
OK TO COVER WHEN READY SECONDARY SERVICE CONDUITS FROM TRANSFORMER LOCATION AT NE CORNER OF BLDG #2 TO BLDG ENTRY AT SW CORNER OF BLDG #3; THREE 3" FROM XFRMR LOC @ S END OF #7 SOUTH TO N END OF #3;
Misc
Partial Correction
05/25/2017
OK TO COVER WHEN READY CONNDUITS FROM UPPER LEVEL BUILDING W/NW TO Q-BOX LOCATION IN ISLAND THEN TO SPACE BETWEEN THE DETACHED GARAGE BUILDINGS -- ONE 3/4", ONE 1", ONE 1-1/4"
Concrete Walls and Columns Inspection Passed 3/23/2017 06/27/2017
Misc
Resolved
06/27/2017
OK TO POUR WHEN READY C.I.P. CONCRETE WING WALLS AT: OUTSIDE SW & NW CORNERS OF BLDG
Footing Inspection - Commercial Passed 5/12/2017 06/27/2017
Misc
Resolved
06/27/2017
OK TO POUR UPPER LEVEL POST-TENSIONED FLOOR SLAB SYSTEM AS APPROVED BY SPECIAL INSPECTOR
Underground Electrical Inspection - Commercial Passed 5/25/2017 06/27/2017
Misc
Resolved
06/27/2017
NO MATERIAL OR WORKMANSHIP ISSUES FOUND ON DATACOMM CONDUITS RUN FROM FOOTING ELEVATION UP OUTSIDE OF BUILDING WEST FOUNDATION WALL -- THREE 3"; TWO 1-1/4"; ONE 3/4"
Misc
Resolved
06/27/2017
OK TO COVER WHEN READY SECONDARY SERVICE CONDUITS FROM TRANSFORMER LOCATION AT NE CORNER OF BLDG #2 TO BLDG ENTRY AT SW CORNER OF BLDG #3; THREE 3" FROM XFRMR LOC @ S END OF #7 SOUTH TO N END OF #3;
Misc
Resolved
06/27/2017
OK TO COVER WHEN READY CONDUITS FROM UPPER LEVEL BUILDING W/NW TO Q-BOX LOCATION IN ISLAND THEN TO SPACE BETWEEN THE DETACHED GARAGE BUILDINGS -- ONE 3/4", ONE 1", ONE 1-1/4"
Final Inspection - Commercial Passed 6/27/2017 6/28/2017 06/28/2017
Documents & Images
Date Uploaded File Type Document Name
10/10/2016 Receipt Receipt for transaction: 2016-006306
10/10/2016 Letter Codes Building Permit
12/12/2016 Letter Inspection Summary
12/30/2016 Letter Inspection Summary
01/11/2017 Letter Inspection Summary
02/07/2017 Letter Inspection Summary
02/08/2017 Letter Inspection Summary
02/16/2017 Letter Inspection Summary
02/21/2017 Letter Inspection Summary
03/16/2017 Letter Inspection Summary
03/20/2017 Letter Inspection Summary
03/23/2017 Letter Inspection Summary
04/12/2017 Letter Inspection Summary
04/17/2017 Letter Inspection Summary
04/21/2017 Letter Inspection Summary
04/25/2017 Letter Inspection Summary
04/26/2017 Letter Inspection Summary
04/27/2017 Letter Inspection Summary
05/10/2017 Letter Inspection Summary
05/12/2017 Letter Inspection Summary
05/22/2017 Letter Inspection Summary
05/25/2017 Letter Inspection Summary
06/28/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home