Permit Application Status

PRCOM20161229


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161229
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
ADDING LEAD SHIELDING TO EXISTING WALLS
05/26/2016
06/03/2016
08/01/2016
Locations
Contacts
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
ACI-BOLAND, Address:1421 EAST 104TH STREET, SUITE 100, Phone:(816) 763-9600  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 06/08/2016 05/31/2016
Joe Dir
Misc
Corrective Action Required
05/31/2016

Med gas lines need to be recertified after they are reconnected
Construction documents for fire alarm systems
Corrective Action Required
05/31/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE DRAWINGS OF ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Construction documents - Fire protection systems
Corrective Action Required
05/31/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE CONTRACTOR PROVIDE DRAWINGS OF ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
Installation acceptance testing
Corrective Action Required
05/31/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE FIRE ALARM SYSTEM ALTERATIONS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT A T 816-969-1300.
Building Plan Review Approved 06/08/2016 05/26/2016
Joe Frogge
Licensed Contractors Approved 06/08/2016 05/26/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $200.54 $200.54 Paid 06/02/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 7/19/2016 7/19/2016 07/19/2016
Above Ceiling Inspection Passed 7/19/2016 07/19/2016
Final Inspection - Commercial Passed 8/4/2016 8/4/2016 08/04/2016
Occupancy Inspection - Fire Passed 8/4/2016 08/04/2016
Documents & Images
Date Uploaded File Type Document Name
05/31/2016 Letter Fire Building Plan Review
05/31/2016 Letter Codes Plan Review Conditions
06/02/2016 Receipt Receipt for transaction: 2016-003252
06/02/2016 Letter Codes Building Permit
07/19/2016 Letter Inspection Summary
08/04/2016 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home