Permit Application Status

PRCOM20161181


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161181
Building Permit - Commercial
Final Completion
JOHN KNOX VILLAGE
PARTIAL COMMERCIAL
BUILDING B - FOUNDATION AND UNDERSLAB
05/23/2016
10/03/2016
03/15/2017
03/27/2017
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
TORGESON ELECTRIC CO INC, Address:3545 SW 6TH AVE, Phone:(785) 233-2213 Ext:101  
LMG CONSTRUCTION, Address:3011 ROANOKE RD, Phone:(816) 474-0333  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
KRUGER TECHNOLOGIES INC, Address:8271 MELROSE DR, Phone:(913) 498-1114  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 04/21/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
04/21/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Field and acceptance tests will be required of the system prior to the final occupancy inspection. To schedule a test contact the fire department at 816-969-1300.
Fire Plan Review Approved 06/30/2016 09/30/2016
Mike Weisenborn
Construction documents for fire alarm systems
Corrective Action Required
09/16/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED
Address numbers required
Corrective Action Required
09/16/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF EACH BUILDING READABLE FROM THE ADDRESSES ROADWAY. MAY REQUIRE POSTING THE ADDRESS ON MORE THAN ONE SIDE. (VERIFIED AT INSPECTION)
Knox box required
Corrective Action Required
09/16/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX FOR EACH BUILDING AND ELEVATOR BANK. BOXES CAN BE OBTAINED ONLINE knoxbox.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
09/16/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
09/16/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SPRINKLER, ALARM, AND HOOD SUPRESSION SYSTEMS PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
09/16/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Portable fire extinguishers - general
Corrective Action Required
09/16/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. MINIMUM SIZE FIRE EXTINGUISHERS SAHLL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/16/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MINIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER SHALL BE 75'
Misc
Corrective Action Required
09/16/2016

DO NOT INSTALL STROBES (ALARM NOTIFICATION DEVICES) IN THE STAIRWAYS.
Misc
Corrective Action Required
09/16/2016

LABEL ALL DOORS TO SPRINKLER RROMS, MECHANICAL ROOMS, ELECTRICAL ROOMS WITH THE ROOM DESIGNATIONS. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
09/16/2016

ALL EXTERIOR HORN STROBES SHALL BE LOCATED AT OR ABOVE THE FDCS
Misc
Corrective Action Required
09/16/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR DESIGNATIONS. (VERIFIED AT INSPECTION)
Building Plan Review Approved 06/30/2016 09/30/2016
Mike Weisenborn
License Tax Application
Corrective Action Required
09/16/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Final Development Plan
Corrective Action Required
09/16/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Corrective Action Required
09/16/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 6/23/16 - not included in submittal
Elevator Certificate of Inspection
Corrective Action Required
09/16/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Permit
Corrective Action Required
09/16/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
09/16/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Miscellaneous Correction
Corrective Action Required
09/16/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified. 6/23/16 - acknowledged in letter (field verify)
Fire Plan Review Approved with Conditions 06/27/2016 06/24/2016
Joe Dir
06/24/2016

06/24/2016

06/24/2016

Construction documents for fire alarm systems
Corrective Action Required
06/23/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED
Address numbers required
Corrective Action Required
06/23/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF EACH BUILDING READABLE FROM THE ADDRESSES ROADWAY. MAY REQUIRE POSTING THE ADDRESS ON MORE THAN ONE SIDE. (VERIFIED AT INSPECTION)
Knox box required
Corrective Action Required
06/23/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX FOR EACH BUILDING AND ELEVATOR BANK. BOXES CAN BE OBTAINED ONLINE knoxbox.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/23/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/23/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SPRINKLER, ALARM, AND HOOD SUPRESSION SYSTEMS PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/23/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Portable fire extinguishers - general
Corrective Action Required
06/23/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. MINIMUM SIZE FIRE EXTINGUISHERS SAHLL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/23/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MINIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER SHALL BE 75'
Misc
Corrective Action Required
06/23/2016

DO NOT INSTALL STROBES (ALARM NOTIFICATION DEVICES) IN THE STAIRWAYS.
Misc
Corrective Action Required
06/23/2016

LABEL ALL DOORS TO SPRINKLER RROMS, MECHANICAL ROOMS, ELECTRICAL ROOMS WITH THE ROOM DESIGNATIONS. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/23/2016

ALL EXTERIOR HORN STROBES SHALL BE LOCATED AT OR ABOVE THE FDCS
Misc
Corrective Action Required
06/23/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR DESIGNATIONS. (VERIFIED AT INSPECTION)
Building Plan Review Rejected 06/30/2016 06/23/2016
Joe Frogge
License Tax Application
Corrective Action Required
06/23/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Final Development Plan
Corrective Action Required
06/23/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Corrective Action Required
06/23/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 6/23/16 - not included in submittal
Elevator Certificate of Inspection
Corrective Action Required
06/23/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Permit
Corrective Action Required
06/23/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
06/23/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Resolved
06/23/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Resolved
06/23/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide blocking for future accessible features as noted in all Type B units.
Misc
Resolved
06/23/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Maintain minimum water closet clearance width at Type A units.
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48 inches minimum in width, measured perpendicular from the side of the clearance that is 16 inches minimum and 18 inches maximum from the water closet centerline. Action required: Maintain minimum water closet clearance width at unit Type C.
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches minimum in width and 36 inches minimum in depth. A clearance of 48 inches minimum in length, measured perpendicular from the shower head wall, and 30 inches minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches in width and 36 inches in depth. Action required: Provide minimum shower compartment floor dimensions. Not compliant as scaled.
Misc
Resolved
06/23/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Miscellaneous Correction
Corrective Action Required
06/23/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified. 6/23/16 - acknowledged in letter (field verify)
Engineered truss package
Resolved
06/23/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction. 6/23/16 - deferred
Screening - Ground mounted equipment
Resolved
06/23/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Miscellaneous Correction
Resolved
06/23/2016

2012 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: Modify drawings to show compliance. 6/23/16 - it has been decided to allow based upon complexity/quantity of loop vents, quantity of penetrations in fire rated horizontal assembly, and presence of maintenance staff.
Misc 12
Resolved
06/23/2016

20012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack. Action required: Modify drawings and/or diagrams to demonstrate compliance.
Misc 13
Resolved
06/23/2016

2012 IPC 1101.3 Prohibited drainage. (as amended by LSCO 7-414) Storm water shall not be drained into sewers intended for sewage only. Sanitary sewer systems shall be designed, built and maintained in such a manner to prevent all storm or ground water from draining, discharging or entering into the sanitary sewer system. Connection of sump pumps, foundation drains, yard drains, gutter downspouts and any other storm water drainage receptacle(s) or system(s) are specifically prohibited from being connected to the sanitary sewer system. Action required: Re-route elevator sump discharge to approved storm drainage location. Drainage into sanitary sewer is prohibited.
Misc 14
Resolved
06/23/2016

2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At rooms with large electrical equipment as defined above provide outswinging doors with panic hardware and emergency exit light.
Licensed Contractors Rejected 06/23/2016 06/23/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
06/23/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 06/07/2016 06/01/2016
Joe Dir
Misc
Corrective Action Required
06/01/2016

1ST FLOOR EGRESS FROM STAIRWAY #2, DOORS A102 & A103 NEED TO SWING IN THE DIRECTION OF EGRESS
Construction documents for fire alarm systems
Corrective Action Required
06/01/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED
Access roads required for building and facilities
Corrective Action Required
06/01/2016

2012 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. PROVIDE DETAILS OF THE ACCESS ROADWAY AS PER PDP
Address numbers required
Corrective Action Required
06/01/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF EACH BUILDING READABLE FROM THE ADDRESSES ROADWAY. MAY REQUIRE POSTING THE ADDRESS ON MORE THAN ONE SIDE.
Knox box required
Corrective Action Required
06/01/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX FOR EACH BUILDING AND ELEVATOR BANK. BOXES CAN BE OBTAINED ONLINE knoxbox.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/01/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/01/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SPRINKLER, ALARM, AND HOOD SUPRESSION SYSTEMS PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/01/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Portable fire extinguishers - general
Corrective Action Required
06/01/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. MINIMUM SIZE FIRE EXTINGUISHERS SAHLL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/01/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MINIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER SHALL BE 75'
Misc
Corrective Action Required
06/01/2016

NO STROBES (ALARM NOTIFICATION DEVICES) IN THE STAIRWAYS.
Misc
Corrective Action Required
06/01/2016

LABEL ALL DOORS TO SPRINKLER RROMS, MECHANICAL ROOMS, ELECTRICAL ROOMS WITH THE ROOM DESIGNATIONS.
Misc
Corrective Action Required
06/01/2016

ALL EXTERIOR HORN STROBES SHALL BE LOCATED AS CLOSE TO OR ABOVE THE FDCS
Misc
Corrective Action Required
06/01/2016

NO MENTION OF CO MONITORING IN THE GARAGE AREA. CONFIRM IF CO MONITORING WILL BE PRESENT OR NOT.
Misc
Corrective Action Required
06/01/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR DESIGNATIONS.
Building Plan Review Rejected 06/07/2016 05/27/2016
Joe Frogge
License Tax Application
Corrective Action Required
05/27/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
05/27/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/27/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Elevator Certificate of Inspection
Corrective Action Required
05/27/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes.
Elevator Equipment Permit
Corrective Action Required
05/27/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes.
Elevator Equipment Inspection
Corrective Action Required
05/27/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/27/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Corrective Action Required
05/27/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide blocking for future accessible features as noted in all Type B units.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Maintain minimum water closet clearance width at Type A units.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48 inches minimum in width, measured perpendicular from the side of the clearance that is 16 inches minimum and 18 inches maximum from the water closet centerline. Action required: Maintain minimum water closet clearance width at unit Type C.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches minimum in width and 36 inches minimum in depth. A clearance of 48 inches minimum in length, measured perpendicular from the shower head wall, and 30 inches minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches in width and 36 inches in depth. Action required: Provide minimum shower compartment floor dimensions. Not compliant as scaled.
Misc
Corrective Action Required
05/27/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified.
Engineered truss package
Corrective Action Required
05/27/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction.
Screening - Ground mounted equipment
Corrective Action Required
05/27/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: Modify drawings to show compliance.
Misc 12
Corrective Action Required
05/27/2016

20012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack. Action required: Modify drawings and/or diagrams to demonstrate compliance.
Misc 13
Corrective Action Required
05/27/2016

2012 IPC 1101.3 Prohibited drainage. (as amended by LSCO 7-414) Storm water shall not be drained into sewers intended for sewage only. Sanitary sewer systems shall be designed, built and maintained in such a manner to prevent all storm or ground water from draining, discharging or entering into the sanitary sewer system. Connection of sump pumps, foundation drains, yard drains, gutter downspouts and any other storm water drainage receptacle(s) or system(s) are specifically prohibited from being connected to the sanitary sewer system. Action required: Re-route elevator sump discharge to approved storm drainage location. Drainage into sanitary sewer is prohibited.
Misc 14
Corrective Action Required
05/27/2016

2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At rooms with large electrical equipment as defined above provide outswinging doors with panic hardware and emergency exit light.
Licensed Contractors Rejected 05/23/2016 05/27/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/27/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Partial Commercial $737.29 $737.29 Paid 09/26/2016
Outstanding Fees Amount Paid Owing Date Paid


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 10/11/2016 (1:00) 10/11/2016 10/11/2016
Misc
Partial Correction
10/11/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Footing Inspection - Commercial Partial 10/13/2016 (1:30) 10/13/2016 10/13/2016
Misc
Partial Correction
10/11/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/13/2016
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2;
Foundation Inspection - Commercial Partial 10/13/2016 10/13/2016
Misc
Partial Correction
10/13/2016
OK TO POUR WHEN READY ELEVATOR PIT WALLS AT: WING "B";
Footing Inspection - Commercial Partial 10/14/2016 (1:00) 10/14/2016 10/14/2016
Misc
Partial Correction
10/13/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/13/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2;
Misc
Partial Correction
10/14/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE SPREAD FOOTINGS: STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Footing Inspection - Commercial Partial 10/17/2016 10/17/2016
Misc
Partial Correction
10/14/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/14/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2; #2 CLOCKWISE TO #3;
Misc
Partial Correction
10/14/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE SPREAD FOOTINGS: STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Footing Inspection - Commercial Partial 10/18/2016 (1:30) 10/18/2016 10/18/2016
Misc
Partial Correction
10/17/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/17/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2; #2 CLOCKWISE TO #3; #3 TO #4;
Misc
Partial Correction
10/17/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE SPREAD FOOTINGS: STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Footing Inspection - Commercial Partial 10/20/2016 (8:00) 10/20/2016 10/20/2016
Misc
Partial Correction
10/18/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/18/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2; #2 CLOCKWISE TO #3; #3 TO #4;
Misc
Partial Correction
10/18/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE SPREAD FOOTINGS: STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Misc
Partial Correction
10/20/2016
OK TO POUR WHEN READY ALL TYPE F3.0 ISOLATED FOOTINGS INCLUDING TWO AT UNIT B106 NOT SHOWN ON APPROVED DRAWINGS;
Foundation Inspection - Commercial Partial 10/20/2016 (1:00) 10/20/2016 10/20/2016
Misc
Partial Correction
10/13/2016
OK TO POUR WHEN READY ELEVATOR PIT WALLS AT: WING "B";
Misc
Partial Correction
10/20/2016
OK TO POUR WHEN READY FOUNDATION WALL AT STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Footing Inspection - Commercial Partial 10/20/2016 10/20/2016
Misc
Partial Correction
10/20/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/20/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2; #2 CLOCKWISE TO #3; #3 TO #4; FROM #1 TO ELEVATOR PIT WEST WALL
Misc
Partial Correction
10/20/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE SPREAD FOOTINGS: STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Misc
Partial Correction
10/20/2016
OK TO POUR WHEN READY ALL TYPE F3.0 ISOLATED FOOTINGS INCLUDING TWO AT UNIT B106 NOT SHOWN ON APPROVED DRAWINGS;
Underslab Plumbing Inspection - Commercial Partial 10/25/2016 10/26/2016 10/26/2016
Misc
Partial Correction
10/26/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: NW OF BLDG DRAIN UNDER CORRIDOR AND SW OF BLDG DRAIN TO EXTERIOR AT UNIT [B114]; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Footing Inspection - Commercial Partial 10/26/2016 (2:00) 10/26/2016 10/26/2016
Misc
Resolved
10/26/2016
OK TO POUR WHEN READY WING "B" ELEVATOR PIT SLAB
Misc
Partial Correction
10/20/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2; #2 CLOCKWISE TO #3; #3 TO #4; FROM #1 TO ELEVATOR PIT WEST WALL; COMPLETION OF G.B. N & NW OF ELEVATOR, TO COMPLETE BUILDING PERIMETER FOOTING
Misc
Resolved
10/26/2016
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE SPREAD FOOTINGS: STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Misc
Resolved
10/26/2016
OK TO POUR WHEN READY ALL TYPE F3.0 ISOLATED FOOTINGS INCLUDING TWO AT UNIT B106 NOT SHOWN ON APPROVED DRAWINGS;
Underslab Plumbing Inspection - Commercial Partial 10/27/2016 10/27/2016 10/27/2016
Misc
Partial Correction
10/26/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: NW OF BLDG DRAIN UNDER CORRIDOR AND SW OF BLDG DRAIN TO EXTERIOR AT UNIT [B114]; UNITS B108 & B109 @ SW QUADRANT; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Passed 10/31/2016 10/31/2016 10/31/2016
Misc
Resolved
10/31/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: NW OF BLDG DRAIN UNDER CORRIDOR AND SW OF BLDG DRAIN TO EXTERIOR AT UNIT [B114]; UNITS B108 & B109 @ SW QUADRANT; REMAINDER OF BUILDING AREA AT NE NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Electrical Inspection - Commercial Partial 11/1/2016 11/01/2016
Misc
Partial Correction
11/01/2016
OK TO COVER WHEN READY FOUR 4" + ONE 2" PVC CONDUITS FROM ELECTRICAL ROOM TO BUILDING ENTRY;
Underslab Electrical Inspection - Commercial Passed 11/2/2016 11/02/2016
Misc
Resolved
11/02/2016
OK TO COVER WHEN READY FOUR 4" + ONE 2" PVC CONDUITS FROM ELECTRICAL ROOM TO BUILDING ENTRY;
Footing Inspection - Commercial Passed 11/15/2016 (1:30) 10/26/2016 03/23/2017
Misc
Resolved
03/23/2017
WING "B": OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS NUMBERED ON PERMIT PRINTS: FROM #1 TO #2; #2 CLOCKWISE TO #3; #3 TO #4; FROM #1 TO ELEVATOR PIT WEST WALL; COMPLETION OF G.B. N & NW OF ELEVATOR, TO COMPLETE BUILDING PERIMETER FOOTING
Foundation Inspection - Commercial Passed 10/20/2016 03/23/2017
Misc
Resolved
03/23/2017
OK TO POUR WHEN READY ELEVATOR PIT WALLS AT: WING "B";
Misc
Resolved
03/23/2017
WING "B": OK TO POUR WHEN READY FOUNDATION WALL AT STEP FOOTING 45' NW OF ELEVATOR PIT PER SUPP DWG S1
Final Inspection - Commercial Passed 3/24/2017 03/24/2017
Documents & Images
Date Uploaded File Type Document Name
06/01/2016 Letter Fire Building Plan Review
06/03/2016 Letter Codes P/R Corrections Document
06/24/2016 Letter Fire Building Plan Review
07/08/2016 Letter Statement of special inspections
09/26/2016 Receipt Receipt for transaction: 2016-006103
09/30/2016 Letter Codes Building Permit
10/11/2016 Letter Inspection Summary
10/13/2016 Letter Inspection Summary
10/14/2016 Letter Inspection Summary
10/17/2016 Letter Inspection Summary
10/18/2016 Letter Inspection Summary
10/20/2016 Letter Inspection Summary
10/26/2016 Letter Inspection Summary
10/27/2016 Letter Inspection Summary
10/31/2016 Letter Inspection Summary
11/01/2016 Letter Inspection Summary
11/02/2016 Letter Inspection Summary
03/24/2017 Letter Inspection Summary
04/21/2017 Letter Fire (Sprinkler) Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home