Permit Application Status

PRCOM20161110


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161110
Building Permit - Commercial
Certificate of Occupancy
CP DEER BROOK PLAZA LLC
CHANGE OF TENANT
CHANGE OF USE TO PERSONAL TRAINING GYM *drawing is in plan review file
05/13/2016
05/25/2016
08/25/2016
Locations
Contacts
ELITE PERSONAL TRAINING, Address:225 SE CHELSEA DR, Phone:(816) 716-1713  
CP DEER BROOK PLAZA LLC, Address:3400 COLLEGE BLVD STE 195  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 05/25/2016 05/25/2016
Development Center
Fire Plan Review Approved with Conditions 05/25/2016 05/18/2016
Joe Dir
Misc
Corrective Action Required
05/18/2016

ALL EXISTING EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE IN FULL OPERATING ORDER. (VERIFIED AT INSPECTION)
Posting of occupant load
Corrective Action Required
05/18/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOAD IN THE OPEN SPACE AREA. (VERIFIED AT INSPECTION)
Construction documents for fire alarm systems
Corrective Action Required
05/18/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
05/18/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1213 ON THE EXTERIOR OF THE FRONT AND REAR DOORS. THE FRONT ADDRESS SHALL BE READABLE FROM THE ADDRESSED ROADWAY (RICE RD)
Construction documents - Fire protection systems
Corrective Action Required
05/18/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF ANY ALTERATIONS TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
05/18/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE UP TO DATE WITH THE REQUIRED ANNUAL MAINTENANACE / SERVICE ALONG WITH A CURRENT SERVICE TAG ON THE RISER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - general
Corrective Action Required
05/18/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A MINIMUM OF ONE 2A-10BC (5 POUND) FIRE EXTINGUISHER. (VERIFIED AT INSPECTION)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
05/18/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHER(S) ON A WALL CLOSE TO AN EXIT WITH A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANYWHERE WITHIN THE SUITE AREA. (VERIFIED AT INSPECTION)
Building Plan Review Approved 05/25/2016 05/13/2016
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 05/25/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Codes Commercial Temporary C of O 5/27/2016 5/27/2016 05/27/2016
Misc
Corrective Action Required
05/27/2016
-OBTAIN FIRE DEPT APPROVAL
Occupancy Inspection - Fire Passed 5/27/2016 5/27/2016 05/31/2016
Occupancy Inspection - Codes Commercial Full C of O 08/25/2016
Misc
Resolved
08/25/2016
-OBTAIN FIRE DEPT APPROVAL
Documents & Images
Date Uploaded File Type Document Name
05/18/2016 Letter Fire Building Plan Review
05/25/2016 Receipt Receipt for transaction: 2016-002921
05/25/2016 Letter Codes Building Permit
05/25/2016 Letter Codes Plan Review Conditions
05/27/2016 Letter Codes Temporary Certificate of Occupancy
08/26/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home