PRCOM20161018


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161018
Building Permit - Commercial
Final Completion
MARION RIDGE SAFETY STORAGE LLC
PARTIAL COMMERCIAL
FOUNDATION AND UNDERSLAB FOR NEW OFFICE BUILDING BUILDING PERMIT - PRCOM20160836
05/03/2016
08/11/2016
07/27/2017
Locations
Contacts
WARD DEVELOPMENT & INVESTMENT CO, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 229-8115  
MARK ONE ELECTRIC CO INC, Address:1414 GENESSEE ST, Phone:(816) 842-7023  
STINE-NICHOLS PLUMBING INC, Address:318 E 16TH AVE, Phone:(816) 348-3481  
MARION RIDGE SAFETY STORAGE LLC, Address:1101 C NW PAMELA BLVD  
DONALDSON MECHANICAL INC, Address:934 SE 7TH TER, Unit B, Phone:(816) 246-9500  
SILVER BULLET LLC, Address:1120 NW EAGLE RIDGE BLVD STE A  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 05/03/2016 05/04/2016
Development Center
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Partial Commercial $63.92 $63.92 Paid 08/10/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 8/18/2016 (8:30) 8/18/2016 08/18/2016
Misc
Corrective Action Required
08/18/2016
GRADE BEAMS AND PIERS OK BELOW: -N/E/S GB FROM A2.5 TO L1.5
Footing Inspection - Commercial Partial 8/24/2016 (9:00) 8/24/2016 08/24/2016
Misc
Corrective Action Required
08/18/2016
GRADE BEAMS AND PIERS OK BELOW: -EXTERIOR GB AND PILASTERS OK, EXCEPT AT VEHICLE DRIVE-THROUGH AT SOUTH END **GROUNDING CONNECTION TO FOOTING REBAR NOT DONE
Footing Inspection - Commercial Partial 9/1/2016 (10:00) 9/1/2016 09/01/2016
Misc
Corrective Action Required
08/24/2016
GRADE BEAMS AND PIERS OK BELOW: -EXTERIOR GB AND PILASTERS OK, EXCEPT AT VEHICLE DRIVE-THROUGH AT SOUTH END -8 INTERIOR 5'X5' PIER PADS **GROUNDING CONNECTION TO FOOTING REBAR NOT DONE
Footing Inspection - Commercial Passed 9/7/2016 (9:00) 9/7/2016 09/07/2016
Misc
Resolved
09/07/2016
GRADE BEAMS AND PIERS OK BELOW: -EXTERIOR GB AND PILASTERS OK, EXCEPT AT VEHICLE DRIVE-THROUGH AT SOUTH END -8 INTERIOR 5'X5' PIER PADS **GROUNDING CONNECTION TO FOOTING REBAR NOT DONE
Concrete Walls and Columns Inspection Partial 9/13/2016 (8:00) 9/13/2016 09/13/2016
Misc
Partial Correction
09/13/2016
-INTERIOR CENTER SHELTER CONCRETE WALL-OK
Suspended Slab Inspection Passed 9/22/2016 (8:00) 9/22/2016 09/22/2016
Underslab Plumbing Inspection - Commercial Partial 9/27/2016 09/27/2016
Misc
Corrective Action Required
09/27/2016
UNDERSLAB PLUMBING OK ALL EXCEPT THE SPRINKLER RM & ITS CONNECTION TO BUILDING DRAIN
Underslab Plumbing Inspection - Commercial Partial 10/4/2016 10/4/2016 10/04/2016
Misc
Corrective Action Required
09/27/2016
UNDERSLAB PLUMBING OK ALL EXCEPT THE SPRINKLER RM & ITS CONNECTION TO BUILDING DRAIN
Underslab Electrical Inspection - Commercial Failed 10/4/2016 10/04/2016
Misc
Corrective Action Required
10/04/2016
-THE SPLICE OF THE UFER GROUNDING ELECTRODE CONDUCTOR SHALL BE IRREVERSIBLE. SPLIT BOLT NOT ALLOWED **ALL OTHER UE OK
Concrete Walls and Columns Inspection Passed 07/27/2017
Misc
Resolved
07/27/2017
-INTERIOR CENTER SHELTER CONCRETE WALL-OK
Underslab Plumbing Inspection - Commercial Passed 07/27/2017
Misc
Resolved
07/27/2017
UNDERSLAB PLUMBING OK ALL EXCEPT THE SPRINKLER RM & ITS CONNECTION TO BUILDING DRAIN
Underslab Electrical Inspection - Commercial Passed 07/27/2017
Misc
Resolved
07/27/2017
**ALL OTHER UE OK, EXCEPT INCOMPLETE UE TO SPRINKLER
Final Inspection - Commercial Passed 07/27/2017
Documents & Images
Date Uploaded File Type Document Name
08/10/2016 Receipt Receipt for transaction: 2016-005376
08/11/2016 Letter Codes Building Permit
08/18/2016 Letter Inspection Summary
08/24/2016 Letter Inspection Summary
09/01/2016 Letter Inspection Summary
09/07/2016 Letter Inspection Summary
09/13/2016 Letter Inspection Summary
09/22/2016 Letter Inspection Summary
09/27/2016 Letter Inspection Summary
10/04/2016 Letter Inspection Summary
07/27/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home