Permit Application Status

PRCOM20160500


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20160500
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
NEW TENANT FOR MEDICAL EXAMS AND DIAGNOSTIC IMAGING - SUITE 300
03/14/2016
05/26/2016
09/21/2016
09/15/2016
Locations
Contacts
MCCARTHY BUILDING COMPANIES INC, Address:12851 MANCHESTER RD, Phone:(314) 646-4179  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
HEARTLAND ELECTRIC CORPORATION, Address:947 LOCUST HILL CIR, Phone:(816) 318-8500  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/25/2016
Joe Dir
Installation acceptance testing
Corrective Action Required
07/25/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FEILD ACCEPTANCE TESTING MAY BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TOV SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/25/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXSITING FIRE SPRINKLER RISERS SHALL BE CURRENT WITH THE REQUIRED ANNUAL SERIVE/MAINTENANCE WITH CURRENT TAGS ON THE RISERS. (VERIIFED AT INSPECTION)
Licensed Contractors Approved 03/24/2016 05/09/2016
Joe Frogge
LC - General Contractor
Resolved
05/09/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Building Plan Review Approved with Conditions 03/24/2016 05/09/2016
Joe Frogge
License Tax Application
Corrective Action Required
03/18/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
05/09/2016

2012 IBC 711.4 Continuity. Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 712.1, 714.4, 715, 1009.3 and 1022.1. Skylights and other penetrations through a fire-resistance-rated roof deck or slab are permitted to be unprotected, provided that the structural integrity of the fire-resistance-rated roof assembly is maintained. Unprotected skylights shall not be permitted in roof assemblies required to be fire-resistance-rated in accordance with Section 705.8.6. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported. Action required: Detail/specify penetrations at fire rated assemblies. Provide detail that describes how to maintain fire rating at Fire Extinguisher Cabinet (FEC). 5/9/16 - flame-sheild product to be used
Misc
Resolved
05/09/2016

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in exam rooms will have redundant ground system. 5/9/16 - clarified in letter. hospital's standard spec is sufficient.
Fire Plan Review Approved with Conditions 05/09/2016
Joe Dir
Portable fire extinguishers - conspicuous locations
Corrective Action Required
05/09/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. FIRE EXTINGUISHERS NEED TO BE ADDED TO THE INTERIOR OF THE TENANT FINISH AREA.
Installation acceptance testing
Corrective Action Required
05/09/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE NEW ALARM SYSTEM DEVICES WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Construction documents - Fire protection systems
Corrective Action Required
05/09/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE PLANS FOR THE ALTERATION OF THE SPRINKLER SYSTEM.
Construction documents for fire alarm systems
Corrective Action Required
05/09/2016

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE PLANS FOR THE ALTERATIONS OF THE ALARM SYSTEM
Fire Plan Review Rejected 03/24/2016 03/25/2016
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
03/16/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE PLANS FOR THE ALTERATIONS OF THE ALARM SYSTEM (ACKNOWLEDGED IN LETTER)
Construction documents - Fire protection systems
Corrective Action Required
03/16/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE PLANS FOR THE ALTERATION OF THE SPRINKLER SYSTEM. (ACKNOWLEDGED IN LETTER)
Installation acceptance testing
Corrective Action Required
03/16/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING OF THE NEW ALARM SYSTEM DEVICES WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. (ACKNOWLEDGED IN LETTER)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
03/16/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. FIRE EXTINGUISHERS NEED TO BE ADDED TO THE INTERIOR OF THE TENANT FINISH AREA. (ACKNOWLEDGED IN LETTER)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $7,780.92 $7,780.92 Paid 05/25/2016
7232302-Saint Lukes Road and Bridge Escrow $1,743.49 $1,743.49 Paid 04/11/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rated Assembly Inspection Partial 6/27/2016 6/27/2016 06/27/2016
Misc
Corrective Action Required
06/27/2016
PRE- RATED WALL INSPECTION,
Rated Assembly Inspection Partial 7/8/2016 7/8/2016 07/08/2016
Misc
Partial Correction
07/08/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: WALL ON (5.8) FROM (F.5) TO (J.1);
Rated Assembly Inspection Partial 7/8/2016 07/08/2016
Misc
Partial Correction
07/08/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: WALL ON (5.8) FROM (F.5) TO (J.1) EAST FACE ONLY;
Rated Assembly Inspection Partial 7/11/2016 7/11/2016 07/11/2016
Misc
Partial Correction
07/08/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: WALL ON (5.8) FROM (F.5) TO (J.1) EAST FACE ONLY;
Misc
Partial Correction
07/11/2016
GWB AT 2 HR FIRE-RATED WALLS: FRAMING & LINER BOARD AT BACK SIDE OF WALL OK TO INSTALL ONE LAYER 5/8" TYPE X GWB ON INSIDE FACE AT: J.1/5.8 TO J.1/4.9 TO G/4.9 TO G/4 AFTER DAMAGED STUDS ARE REINFORCED AND FIRESTOPPING IS COMPLETED AS DISCUSSED;
In-wall Inspection Failed 7/15/2016 07/15/2016
Misc
Corrective Action Required
07/15/2016
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
In-wall Inspection Partial 7/18/2016 7/18/2016 07/18/2016
Misc
Partial Correction
07/18/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F029 THRU 3F034;
In-wall Inspection Partial 7/22/2016 7/22/2016 07/22/2016
Misc
Partial Correction
07/18/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F029 THRU 3F034; 3F039 THRU 3F044;
In-wall Inspection Partial 7/27/2016 07/27/2016
Misc
Partial Correction
07/22/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F029 THRU 3F034; 3F039 THRU 3F044; 3F045 THRU 3F050; WALLS AND SOFFIT AT 3F020;
In-wall Inspection Passed 7/28/2016 7/28/2016 07/28/2016
Misc
Resolved
07/28/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F029 THRU 3F034; 3F039 THRU 3F044; 3F045 THRU 3F050; WALLS AND SOFFIT AT 3F020;
Rated Assembly Inspection Partial 8/2/2016 8/2/2016 08/02/2016
Misc
Partial Correction
07/11/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: CORRIDOR 3F020 WALL ON (5.8) FROM (F.5) TO (J.1) EAST AND WEST FACES + DOOR CROSSWALL NORTH FACE ONLY;
Misc
Partial Correction
07/11/2016
GWB AT 2 HR FIRE-RATED WALLS: FRAMING & LINER BOARD AT BACK SIDE OF WALL OK TO INSTALL ONE LAYER 5/8" TYPE X GWB ON INSIDE FACE AT: J.1/5.8 TO J.1/4.9 TO G/4.9 TO G/4; 3F014 NORTH WALL SOUTH FACE;
Rated Assembly Inspection Partial 8/5/2016 8/5/2016 08/05/2016
Misc
Partial Correction
08/02/2016
GWB AT 2 HR FIRE-RATED WALLS: FRAMING & LINER BOARD AT BACK SIDE OF WALL OK TO INSTALL ONE LAYER 5/8" TYPE X GWB ON INSIDE FACE AT: J.1/5.8 TO J.1/4.9 TO G/4.9 TO G/4; 3F014 NORTH WALL SOUTH FACE; 3F053/55 SOUTH WALL SOUTH FACE: COMPLETE GWB AND FASTENERS AT TOP 3'; CALL FOR RE-INSPECTION
Misc
Partial Correction
08/02/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: CORRIDOR 3F020 WALL ON (5.8) FROM (F.5) TO (J.1) EAST AND WEST FACES + DOOR CROSSWALL NORTH FACE ONLY;
Rated Assembly Inspection Partial 8/12/2016 8/12/2016 08/12/2016
Misc
Partial Correction
08/05/2016
GWB AT 2 HR FIRE-RATED WALLS: FRAMING & LINER BOARD AT BACK SIDE OF WALL OK TO INSTALL ONE LAYER 5/8" TYPE X GWB ON INSIDE FACE AT: J.1/5.8 TO J.1/4.9 TO G/4.9 TO G/4; 3F014 NORTH WALL SOUTH FACE; COMPLETE UPPER CORNER @ WEST END THEN OK TO COVER 3F053/55 SOUTH WALL SOUTH FACE;
Misc
Partial Correction
08/05/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: CORRIDOR 3F020 WALL ON (5.8) FROM (F.5) TO (J.1) EAST AND WEST FACES + DOOR CROSSWALL NORTH FACE ONLY;
Above Ceiling Inspection Not Ready 8/18/2016 8/18/2016 08/18/2016
Above Ceiling Inspection Not Ready 8/23/2016 8/23/2016 08/23/2016
Above Ceiling Inspection Partial 8/26/2016 8/26/2016 08/26/2016
Above Ceiling Inspection Partial 8/27/2016 08/27/2016
Misc
Partial Correction
08/27/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F024 THRU 3F034 NW TO C/L (K);
Above Ceiling Inspection Partial 8/29/2016 8/29/2016 08/29/2016
Misc
Partial Correction
08/27/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F024 THRU 3F034; 3F020 THRU 3F023; 3F026; 3F035 THRU 3F039; 3F061; 3F020 EXCEPT LEAVE TILE OUT ONE LOCATION WHERE ELECTRICAL WIRING IS NOT COMPLETED;
Alarm Test Passed 8/31/2016 08/31/2016
Above Ceiling Inspection Partial 8/31/2016 8/31/2016 08/31/2016
Misc
Partial Correction
08/29/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F024 THRU 3F034; 3F020 THRU 3F023; 3F026; 3F035 THRU 3F039; 3F061; 3F020 EXCEPT LEAVE TILE OUT ONE LOCATION WHERE ELECTRICAL WIRING IS NOT COMPLETED; REMAINDER OF UNIT ACT CEILINGS EXCEPT 3F050 & 3F053; CUT BORDERS ONLY AT 3F057;
Occupancy Inspection - Codes Commercial Not Ready 9/1/2016 9/1/2016 09/01/2016
Above Ceiling Inspection Not Ready 9/1/2016 09/01/2016
Misc
Partial Correction
08/31/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F024 THRU 3F034; 3F020 THRU 3F023; 3F026; 3F035 THRU 3F039; 3F061; 3F020 EXCEPT LEAVE TILE OUT ONE LOCATION WHERE ELECTRICAL WIRING IS NOT COMPLETED; REMAINDER OF UNIT ACT CEILINGS EXCEPT 3F050 & 3F053; CUT BORDERS ONLY AT 3F057;
Above Ceiling Inspection Passed 9/2/2016 9/2/2016 09/02/2016
Misc
Resolved
09/02/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 3F024 THRU 3F034; 3F020 THRU 3F023; 3F026; 3F035 THRU 3F039; 3F061; 3F020 EXCEPT LEAVE TILE OUT ONE LOCATION WHERE ELECTRICAL WIRING IS NOT COMPLETED; REMAINDER OF UNIT ACT CEILINGS EXCEPT 3F050 & 3F053; CUT BORDERS ONLY AT 3F057;
Occupancy Inspection - Codes Commercial Temporary C of O 9/6/2016 9/6/2016 09/06/2016
Misc
Corrective Action Required
09/06/2016
-OBTAIN FIRE DEPT. APPROVAL -FIRE ASSY. INSPECTION NOT APPROVED
Occupancy Inspection - Fire Passed 7/15/2016 9/6/2016 09/06/2016
Rated Assembly Inspection Passed 8/12/2016 09/07/2016
Misc
Partial Correction
08/12/2016
GWB AT 2 HR FIRE-RATED WALLS: FRAMING & LINER BOARD AT BACK SIDE OF WALL OK TO INSTALL ONE LAYER 5/8" TYPE X GWB ON INSIDE FACE AT: J.1/5.8 TO J.1/4.9 TO G/4.9 TO G/4; 3F014 NORTH WALL SOUTH FACE; COMPLETE UPPER CORNER @ WEST END THEN OK TO COVER 3F053/55 SOUTH WALL SOUTH FACE;
Misc
Partial Correction
08/12/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY ONE LAYER 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: CORRIDOR 3F020 WALL ON (5.8) FROM (F.5) TO (J.1) EAST AND WEST FACES + DOOR CROSSWALL NORTH FACE ONLY;
Occupancy Inspection - Codes Commercial Full C of O 9/15/2016 09/15/2016
Misc
Resolved
09/15/2016
-OBTAIN FIRE DEPT. APPROVAL -FIRE ASSY. INSPECTION NOT APPROVED
Investigation Inspection Complete 9/21/2016 09/21/2016
Misc
Informational
09/21/2016
CORRIDOR CONSTRUCTED PER STATE OF MISSOURI REQUIREMENTS. NO NOTIFICATION RECEIVED FROM G.C. OR OTHERS WORK WAS TO BEGIN OR HAD BEGUN. WORK WAS SUBSTANTIALLY COMPLETED AND COVERED BEFORE MW CALLED JB TO REQUEST INSPECTION. NO PASS; NO FAIL.
Documents & Images
Date Uploaded File Type Document Name
03/16/2016 Letter Fire Building Plan Review
03/25/2016 Letter Codes P/R Corrections Document
04/11/2016 Receipt Receipt for transaction: 2016-001076
05/09/2016 Letter Fire Building Plan Review
05/09/2016 Letter Codes Plan Review Conditions
05/25/2016 Receipt Receipt for transaction: 2016-002907
05/25/2016 Letter Codes Building Permit
06/27/2016 Letter Inspection Summary
07/08/2016 Letter Inspection Summary
07/11/2016 Letter Inspection Summary
07/15/2016 Letter Inspection Summary
07/18/2016 Letter Inspection Summary
07/22/2016 Letter Inspection Summary
07/25/2016 Letter Fire (Sprinkler) Plan Review
07/27/2016 Letter Inspection Summary
07/28/2016 Letter Inspection Summary
08/02/2016 Letter Inspection Summary
08/05/2016 Letter Inspection Summary
08/12/2016 Letter Inspection Summary
08/27/2016 Letter Inspection Summary
08/29/2016 Letter Inspection Summary
08/31/2016 Letter Inspection Summary
09/02/2016 Letter Inspection Summary
09/06/2016 Letter Codes Temporary Certificate of Occupancy
09/15/2016 Letter Field Certificate of Occupancy
09/16/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home