Permit Application Status

PRCOM20160269


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20160269
Building Permit - Commercial
Certificate of Occupancy
RED LEES SUMMIT EAST LLC
CHANGE OF TENANT
TENANT FINISH FOR PREP AND SALES OF COOKIES AND ICE CREAM
02/22/2016
03/30/2016
08/24/2016
06/13/2016
Locations
Contacts
CAMM CONSTRUCTION INC, Address:PO BOX 1417, Phone:(816) 607-3602  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
PALMER ELECTRIC CO, Address:6600 ROYAL ST, BLDG B, Phone:(816) 479-2587  
STEVE THE PLUMBER INC, Address:601 S STELLA, Phone:(913) 226-6140  
GRUBER & ASSOCIATES ARCHITECTS LLC, Address:245 PEACHTREE CENTER AVENUE NE STE 2445, Phone:(404) 584-1683  
RED LEES SUMMIT EAST LLC, Address:1 E WASHINGTON ST STE 300  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/31/2016
Joe Dir
Alarm Plan Review Released for Construction 05/05/2016
Joe Dir
Misc
Corrective Action Required
05/05/2016

Acceptance testing of alarm devices will be required prior to the final occupancy inspection. to schedule a test contact the fire deaprtment at 816-969-1300
Fire Plan Review Approved with Conditions 04/06/2016 04/06/2016
Joe Dir
Construction documents - Fire protection systems
Corrective Action Required
04/06/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide sprinkler and alarm plans for modifications to the existing systems due to changes in the walls, walk in cooler, and addition of the cloud.
Posting of occupant load
Corrective Action Required
04/06/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection. OCCUPANCY 50
Installation acceptance testing
Corrective Action Required
04/06/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Contact Fire Prevention at (816) 969-1300 to schedule a test of the alarm system. Tests are to be completed before regular business hours for the shopping center.
Address numbers required
Corrective Action Required
04/06/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC OR ALPHBETIC SUITE DESIGNATION ON THE FRONT AND REAR DOORS (VERIFIED AT INSPECTION)
Building Plan Review Approved with Conditions 03/10/2016 03/30/2016
Joe Frogge
License Tax Application
Corrective Action Required
03/03/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 3/7/16 - acknowledged in letter from architect.
Health Dept Inspection
Corrective Action Required
03/03/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 3/7/16 - acknowledged in letter from architect.
Health Dept Review
Resolved
03/30/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 3/7/16 - acknowledged in letter from architect.
Accessibility - Fixed sidewall grab bars 604.5.1
Resolved
03/07/2016

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: provide side wall vertical grab bars. 3/7/16 - elevations updated to show bar
Misc
Resolved
03/07/2016

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of exits. 3/7/16 - exterior emergency lights are existing per letter from architect. A note has been added to field verify.
Health Department Review Approved 03/03/2016 03/30/2016
Joe Frogge
Licensed Contractors Approved 03/03/2016 03/28/2016
Development Center
LC - General Contractor
Resolved
03/28/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 3/7/16 - acknowledged in letter from architect.
LC - MEP Subs
Resolved
03/28/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/7/16 - acknowledged in letter from architect.
Fire Plan Review Approved with Conditions 03/10/2016 03/04/2016
Joe Dir
Construction documents - Fire protection systems
Corrective Action Required
03/03/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide sprinkler and alarm plans for modifications to the existing systems due to changes in the walls, walk in cooler, and addition of the cloud.
Posting of occupant load
Corrective Action Required
03/03/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection. OCCUPANCY 50
Installation acceptance testing
Corrective Action Required
03/03/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Contact Fire Prevention at (816) 969-1300 to schedule a test of the alarm system. Tests are to be completed before regular business hours for the shopping center.
Address numbers required
Corrective Action Required
03/04/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC OR ALPHBETIC SUITE DESIGNATION ON THE FRONT AND REAR DOORS (VERIFIED AT INSPECTION)
Fire Plan Review Approved with Conditions 03/03/2016 02/25/2016
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/25/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide sprinkler and alarm plans for modifications to the existing systems due to changes in the walls, walk in cooler, and addition of the cloud.
Posting of occupant load
Corrective Action Required
02/25/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Installation acceptance testing
Corrective Action Required
02/25/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Contact Fire Prevention at (816) 969-1300 to schedule a test of the alarm system. Tests are to be completed before regular business hours for the shopping center.
Building Plan Review Rejected 03/03/2016 02/24/2016
Joe Frogge
License Tax Application
Corrective Action Required
02/24/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
02/24/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
02/24/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
02/24/2016

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: provide side wall vertical grab bars.
Misc
Corrective Action Required
02/24/2016

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of exits.
Licensed Contractors Rejected 03/03/2016 02/24/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
02/24/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
02/24/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $326.80 $326.80 Paid 03/30/2016
8331507-Sewer Connection Fee $90.00 $90.00 Paid 03/30/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 4/21/2016 4/21/2016 04/21/2016
Misc
Corrective Action Required
04/21/2016
SIZE OF EXISTING AND NEW PIPE NOT PER APPROVED DRAWING. NO WORKMANSHIP ISSUES FOUND. APPROVED REVISED DRAWINGS REQUIRED. IF COVER AT RISK.
Underslab Electrical Inspection - Commercial Passed 4/21/2016 4/21/2016 04/21/2016
Underslab Plumbing Inspection - Commercial Passed 4/28/2016 04/28/2016
Misc
Resolved
04/28/2016
SIZE OF EXISTING AND NEW PIPE NOT PER APPROVED DRAWING. NO WORKMANSHIP ISSUES FOUND. APPROVED REVISED DRAWINGS REQUIRED. IF COVER AT RISK.
In-wall Inspection Partial 4/29/2016 04/29/2016
Misc
Partial Correction
04/29/2016
FULL-HEIGHT WALLS OK TO COVER WHEN READY
Misc
Corrective Action Required
04/29/2016
FULLY SCREW ALL FLANGE CONNECTIONS ON TENSION STUDS. DO NOT COVER SOFFITS & HANGING BULKHEADS. CALL FOR RE-INSPECTION WHEN READY.
Above Ceiling Inspection Partial 5/2/2016 05/02/2016
Misc
Partial Correction
05/02/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BULLKHEADS AND SOFFITS
In-wall Inspection Passed 5/2/2016 05/02/2016
Misc
Resolved
05/02/2016
FULL-HEIGHT WALLS OK TO COVER WHEN READY
Misc
Resolved
05/02/2016
FULLY SCREW ALL FLANGE CONNECTIONS ON TENSION STUDS. DO NOT COVER SOFFITS & HANGING BULKHEADS. CALL FOR RE-INSPECTION WHEN READY.
Above Ceiling Inspection Partial 5/12/2016 5/12/2016 05/12/2016
Misc
Partial Correction
05/02/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BULLKHEADS AND SOFFITS
Misc
Partial Correction
05/12/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WEST 3' OF SERVING AREA: - REMOVE UNUSED BOX CONNECTOR AND PLUG OPENING - SECURE MC CABLES WITHIN ~12" OF ENTRY TO BOX
Above Ceiling Inspection Partial 5/12/2016 05/12/2016
Misc
Partial Correction
05/12/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BULLKHEADS AND SOFFITS
Misc
Partial Correction
05/12/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WEST 3' OF SERVING AREA: - REMOVE UNUSED BOX CONNECTOR AND PLUG OPENING - SECURE MC CABLES WITHIN ~12" OF ENTRY TO BOX
Above Ceiling Inspection Passed 6/2/2016 06/02/2016
Misc
Resolved
06/02/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ BULLKHEADS AND SOFFITS
Misc
Resolved
06/02/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WEST 3' OF SERVING AREA: - REMOVE UNUSED BOX CONNECTOR AND PLUG OPENING - SECURE MC CABLES WITHIN ~12" OF ENTRY TO BOX
Alarm Test Passed 6/8/2016 06/09/2016
Occupancy Inspection - Codes Commercial Temporary C of O 6/9/2016 6/9/2016 06/09/2016
Misc
Corrective Action Required
06/09/2016
RESOLVE FIRE DEPT ISSUE(S)
Misc
Corrective Action Required
06/09/2016
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Occupancy Inspection - Fire Passed 6/9/2016 06/09/2016
Occupancy Inspection - Codes Commercial Full C of O 6/13/2016 6/13/2016 06/13/2016
Misc
Resolved
06/13/2016
RESOLVE FIRE DEPT ISSUE(S)
Misc
Resolved
06/13/2016
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". LABEL UNOCCUPIED POSITIONS "SPACE".
Miscellaneous Inspection Passed 5/19/2016 6/13/2016 08/16/2016
Documents & Images
Date Uploaded File Type Document Name
02/26/2016 Letter Codes P/R Corrections Document
03/04/2016 Letter Fire Building Plan Review
03/30/2016 Letter Codes Plan Review Conditions
03/30/2016 Letter Codes Building Permit
03/30/2016 Receipt Receipt for transaction: 2016-000914
04/06/2016 Letter Fire Building Plan Review
04/21/2016 Letter Inspection Summary
04/29/2016 Letter Inspection Summary
05/02/2016 Letter Inspection Summary
05/05/2016 Letter Fire (Alarm) Plan Review Notice
05/12/2016 Letter Inspection Summary
05/16/2016 msc-gac hvac adequacy cert summit fair MO
05/19/2016 Letter Inspection Summary
06/09/2016 Letter Codes Temporary Certificate of Occupancy
06/13/2016 Letter Field Certificate of Occupancy
06/14/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home