Review Type |
Outcome |
Est. Completion Date |
Completed |
Licensed Contractors
|
Approved
|
04/14/2017
|
04/26/2017
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
7/18/17 - acknowledged in letter
|
|
LC - MEP Subs
MEP Subs:
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
7/18/17 - acknowledged in letter
|
|
|
Building Plan Review
|
Approved
|
04/21/2017
|
04/18/2017
|
|
Joe Frogge
|
|
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2.
Action required: Modify design at door into Toilet 3D202 to comply. Minimum 18" required at latch side of front approach.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
04/21/2017
|
04/18/2017
|
|
Joe Dir
|
|
Misc
Corrective Action Required
ACTION RWEQUIRED; (ACKNOWLEDGED)
ALL DELAYED EGRESS DOORS, ELECTRIC STIKES, CARD READERS, SHALL UNLOCK UPON ACTUATION OF THE FIRE SPRINKLER SYSTEM, FIRE ALARM SYSTEM, POWER LOSS TO THE LOCK, A SIGNAL FROM THE COMMAND CENTER. INFORMATION PURPOSES, VERIFIED AT TESTING.
|
|
Construction documents for fire alarm systems
Corrective Action Required
ACTION REQUIRED: (ACKNOWLEDGED)
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
PROVIDE AS BUILT PLANS FOR ANY ALTERATIONS TO THE ALARM SYSTEM. INFORMATION PURPOSES
|
|
Address numbers required
Corrective Action Required
ACTION REQUIRED: (ACKNOWLEDGED)
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
PROVIDE SUITE ADRESSING OFF THE CORRIDOR FOR ALL DOORS LEADING INTO THE SUITE. VERIFIED AT INSPECTION.
|
|
Construction documents - Fire protection systems
Corrective Action Required
ACTION REQUIRED: (ACKNOWLEDGED)
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
PROVIDE AS BUILT PLANS FOR ANY ALTERATIONS TO THE FIRE SPRINKLER SYSTEM. INFOMATION PURPOSES.
|
|
Installation acceptance testing
Corrective Action Required
ACTION REQUIRED: (ACKNOWLEDGED)
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
TESTING WILL BE REQUIRED FOR ANY ALTERATIONS DONE TO THE FIRE ALARM SYSTEM. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT @ 816-969-1300. INFORMATION PURPOSES.
|
|
Misc
Corrective Action Required
ACTION REQUIRED: (ACKNOWLEDGED)
ALL POWER OUTLETS, LIGHTS, SWITCHES POWERED BY THE GENERATOR NEED TO BE TESTED FOR CONNECTION TO THE GENERATOR PANEL PRIOR TO THE FINAL INSPECTION. DOCUMENTATION OF THE TEST PROVIDE TO THE FIRE DEPARTMENT AND CODES ADMINISTRATION.
INFORMATION PURPOSES VERIFIED AT INSPECTION.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
12/31/2016
|
|
Joe Dir
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACTION REQUIRED:(Information purposes)
Testing of the new installation will be required prior to the final occupancy inspection. To schedule the testing contact the fire dpartment at 816-969-1300.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
|
12/31/2016
|
|
Joe Dir
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
ACTION REQUIRED: (verified at inspection)
The existing sprinkler system riser shall be current with all required maintenance and certifications.
|
|
|
Building Plan Review
|
Rejected
|
02/11/2016
|
02/08/2016
|
|
Joe Frogge
|
|
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2.
Action required: Modify design at door into Toilet 3D202 to comply. Minimum 18" required at latch side of front approach.
|
|
|
Licensed Contractors
|
Rejected
|
02/11/2016
|
02/08/2016
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
|
|
LC - MEP Subs
Corrective Action Required
MEP Subs:
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Zoning Review
|
Approved
|
02/11/2016
|
02/02/2016
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/11/2016
|
02/02/2016
|
|
Joe Dir
|
|
Misc
Corrective Action Required
ALL DELAYED EGRESS DOORS, ELECTRIC STIKES, CARD READERS, SHALL UNLOCK UPON ACTUATION OF THE FIRE SPRINKLER SYSTEM, FIRE ALARM SYSTEM, POWER LOSS TO THE LOCK, A SIGNAL FROM THE COMMAND CENTER. INFORMATION PURPOSES, VERIFIED AT TESTING.
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
PROVIDE AS BUILT PLANS FOR ANY ALTERATIONS TO THE ALARM SYSTEM. INFORMATION PURPOSES
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
PROVIDE SUITE ADRESSING OFF THE CORRIDOR FOR ALL DOORS LEADING INTO THE SUITE. VERIFIED AT INSPECTION.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
PROVIDE AS BUILT PLANS FOR ANY ALTERATIONS TO THE FIRE SPRINKLER SYSTEM. INFOMATION PURPOSES.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
TESTING WILL BE REQUIRED FOR ANY ALTERATIONS DONE TO THE FIRE ALARM SYSTEM. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT @ 816-969-1300. INFORMATION PURPOSES.
|
|
Misc
Corrective Action Required
ALL POWER OUTLETS, LIGHTS, SWITCHES POWERED BY THE GENERATOR NEED TO BE TESTED FOR CONNECTION TO THE GENERATOR PANEL PRIOR TO THE FINAL INSPECTION. DOCUMENTATION OF THE TEST PROVIDE TO THE FIRE DEPARTMENT AND CODES ADMINISTRATION.
INFORMATION PURPOSES VERIFIED AT INSPECTION.
|
|
|