Permit Application Status

PRCOM20152488


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20152488
Building Permit - Commercial
Certificate of Occupancy
COMPTON HOLDINGS LC
CHANGE OF TENANT
TENANT FINISH FOR SHIPPING COMPANY
10/26/2015
11/12/2015
11/17/2015
Locations
Contacts
VANMETER CONSTRUCTION LLC, Address:8614 W 74TH TERRACE, Phone:(913) 432-4341  
BART'S ELECTRIC COMPANY INC, Address:7103 STEWART RD, Phone:(816) 421-0007  
COMPTON HOLDINGS LC, Address:901 NEW HAMPSHIRE STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 11/05/2015 12/31/2015
Joe Dir
Building Plan Review Approved with Conditions 11/05/2015 11/04/2015
Joe Frogge
Project cost
Resolved
11/10/2015

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
11/04/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Licensed Contractors Rejected 11/05/2015 11/04/2015
Joe Frogge
LC - MEP Subs
Resolved
11/10/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed Electrical Contractors.
Fire Plan Review Approved with Conditions 11/05/2015 10/29/2015
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
10/29/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE AS BUILT PLANS FOR ANT ALTERATIONS OF THE ALARM SYSTEM. ADD ALARM NOTIFICATION TO SUITE. INFORMATION PURPOSES.
Address numbers required
Corrective Action Required
10/29/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF833 AT THE FRONT AND REAR DOORS. VERIFIES AT INSPECTION.
Construction documents - Fire protection systems
Corrective Action Required
10/29/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE AS BUILT PLANS FOR ANY ALTERATIONS TO THE SPRINKLER SYSTEM. INFORMATION PURPOSES
Installation acceptance testing
Corrective Action Required
10/29/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING REQUIRED FOR ALARM DEVICES INSTALLED IN SUITE. CONTACT FIRE DEPARTMENT FOR TEST SCHEDULING 816-969-1300
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/29/2015

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. FIRE SPRINKLER SYSTEM SHALL BE CURRENT ON THE ANNUAL SERVICE/MAINTENANCE. CURRENT TAG ON RISER. VERIFIED AT INSPECTION.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $51.06 $51.06 Paid 11/12/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Alarm Test Passed 11/16/2015
Occupancy Inspection - Codes Commercial Full C of O 11/17/2015 11/17/2015 at 12:00 AM 11/17/2015
Occupancy Inspection - Fire Passed 11/17/2015 at 12:00 AM 11/17/2015
Documents & Images
Date Uploaded File Type Document Name
10/29/2015 Letter Fire Building Plan Review
11/04/2015 Letter Codes P/R Corrections Document
11/10/2015 Letter Codes Plan Review Conditions
11/12/2015 Receipt Receipt for transaction: 2015-006123
11/12/2015 Letter Codes Building Permit
11/17/2015 Letter Field Certificate of Occupancy
11/18/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home