Permit Application Status

PRCOM20152438


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20152438
Building Permit - Commercial
Certificate of Occupancy
THE UNITED METHODIST CHURCH OF LEES SUMM
NEW COMMERCIAL
NEW CHURCH WITH ATTACHED EDUCATION FACILITY FOUNDATION/UNDERSLAB PERMIT: PRCOM20161873
10/20/2015
06/08/2016
04/26/2016
10/16/2017
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
METRO AIR CONDITIONING , Address:8151 MCCOY ST, Phone:(913) 888-3991  
ELDECON INC, Address:120 SE 30TH ST, Phone:(660) 553-1121  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
MANTEL TETER ARCHITECTS, INC, Address:929 WALNUT ST, SUITE 5104, Phone:(816) 931-5600  
THE UNITED METHODIST CHURCH OF LEES SUMM, Address:114 SE DOUGLAS ST  
THE UNITED METHODIST CHURCH OF LEES SUMM, Address:3381 NW CHIPMAN RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/07/2017
Joe Dir
Alarm Plan Review Released for Construction 07/13/2016
Joe Dir
Installation acceptance testing
Corrective Action Required
07/13/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUOPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Final Development Plan Review Approved 04/26/2016 06/07/2016
Dawn Bell
Fire Plan Review Approved with Conditions 12/01/2015 11/25/2015
Joe Dir
Misc
Corrective Action Required
11/20/2015

[B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. [B] 1008.1.10.1 Installation. Where panic or fire exit hardware is installed, it shall comply with the following: 1. Panic hardware shall be listed in accordance with UL 305; 2. Fire exit hardware shall be listed in accordance with UL 10C and UL 305; 3. The actuating portion of the releasing device shall extend at least one-half of the door leaf width; and 4. The maximum unlatching force shall not exceed 15 pounds (67 N). ACKNOWLEDGED IN LETTER
Posting of occupant load
Corrective Action Required
11/20/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. INFORMATION PURPOSES. ACKNOWLEDGED IN LETTER
Construction documents for fire alarm systems
Corrective Action Required
11/20/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM. INFORMATION PURPOSES ACKNOWLEDGED IN LETTER
Fire access roads or water supply required
Corrective Action Required
11/20/2015

2012 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2. 03.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing at least 75,000 pounds (34 050 kg). D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders. ACKNOWLEDGED IN LETTER
Address numbers required
Corrective Action Required
11/20/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS DURING CONSTRUCTION AND AFTER COMPLETION READABLE FROM THE ROADWAY. INFORMATION PURPOSES ACKNOWLEDGED IN LETTER
Knox box required
Corrective Action Required
11/20/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT FOR APPLCATION 816-969-1300 ACKNOWLEDGED ON PLANS
Construction documents - Fire protection systems
Corrective Action Required
11/20/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS OF THE FIRE SPRINKLER SYSTEM. INFORMATION PURPOSES ACKNOWLEDGED IN LETTER
Installation acceptance testing
Corrective Action Required
11/20/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING IS REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM, TO SCHEDULE TESTING CONTACT THE FIRE SEPARTMENT AT 816-969-1300 ACKNOWLEDGED IN LETTER
Portable fire extinguishers - general
Corrective Action Required
11/20/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. SHOW FIRE EXTINGUISHER LOCATIONS THROUGHOUT ACKNOWLEDGED ON PLANS
Misc
Corrective Action Required
11/20/2015

PAGE E1 OF PLANS NEED TO SHOW EMERGENCY EGRESS LIGHTING IN VESTIBULE 111 OR 108 ACKNOWLEDGED ON PLANS
Misc
Corrective Action Required
11/20/2015

501.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. ACKNOWLEDGED IN LETTER
Misc
Corrective Action Required
11/20/2015

SHOW FDC ON PLANS AS TO LOCATION OF HYDRANTS. THERE SHALL BE HYDRANT WITHIN 100' OF THE FDC ACKNOWLEDGED ON PLANS
Licensed Contractors Approved 11/20/2015 11/24/2015
Joe Frogge
Building Plan Review Approved with Conditions 12/01/2015 11/24/2015
Joe Frogge
License Tax Application
Corrective Action Required
11/20/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
11/24/2015

Existing house on property. Action required: House must be entirely removed and associated demolition permit must be closed prior to issuing permit for new structure. 11/24/15 - permit issued
Misc
Resolved
11/24/2015

Foundation structural design is for >2000psi soils which is higher than normal for this area. Action required: Provide geo-tech report as justifying documentation. 11/24/15 - report was in spec
Misc
Corrective Action Required
11/20/2015

2012 IBC 410.4 Platform construction. Permanent platforms shall be constructed of materials as required for the type of construction of the building in which the permanent platform is located. Permanent platforms are permitted to be constructed of fire-retardant-treated wood for Types I, II and IV construction where the platforms are not more than 30 inches above the main floor, and not more than one-third of the room floor area and not more than 3,000 square feet in area. Where the space beneath the permanent platform is used for storage or any purpose other than equipment, wiring or plumbing, the floor assembly shall be not less than 1-hour fire-resistance-rated construction. Where the space beneath the permanent platform is used only for equipment, wiring or plumbing, the underside of the permanent platform need not be protected. Action required: Comment for informational purposes. Use of wood in under-platform areas to be verified at inspections. 11/24/15 - acknowledged in letter
Misc
Resolved
11/24/2015

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 11/24/15 - received
Misc
Resolved
11/24/2015

2012 IBC 1009.15 Handrails. Stairways shall have handrails on each side and shall comply with Section 1012. Where glass is used to provide the handrail, the handrail shall also comply with Section 2407. (see code for exceptions) Action required: Modify drawings and details to show handrails on both sides of stairs serving raised platform in sanctuary. 11/24/15 - approved via CMR
Plumb - Minimum number of fixtures 403.1
Resolved
11/24/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Modify drawings to specify and indicate location of drinking fountains as directed by Table 403.1. 11/24/15 - drinking fountains added
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
11/24/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify documents to provide minimum 18" clearance at latch side of door #143. 11/24/15 - drawings modified
Bldg - Handrail extensions 1012.6
Resolved
11/24/2015

2012 IBC 1012.6 – Handrail extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continuous to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrails shall extend horizontally above the landing 12 inches minimum beyond the top and bottom of ramp runs. The extensions of handrails shall be in the same direction of the stair flights at stairways and the ramp runs at ramps. (See code section for possible exceptions.) Action required: Modify drawings/details to show that handrails will return to a wall, guard or walking surface. Ref: handrails at dock - detail 3/A3.32. 11/24/15 - note added to section detail
Bldg - Occupant load posting 1004.3
Corrective Action Required
11/20/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. To be verified at inspections. 11/24/15 - acknowledged in letter
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
11/20/2015

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Comment is for informational purposes. To be verified at inspections. 11/24/15 - acknowledged in letter
Misc
Resolved
11/24/2015

2011 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Revise electrical riser diagram to show grounding to all means available. Wire types and sizes to be included. 11/24/15 - grounding information added
Misc
Resolved
11/24/2015

2012 IBC 1108.2 Assembly area seating. A building, room or space used for assembly purposes with fixed seating shall comply with Sections 1108.2.1 through 1108.2.5. Lawn seating shall comply with Section 1108.2.6. Assistive listening systems shall comply with Section 1108.2.7. Performance areas viewed from assembly seating areas shall comply with Section 1108.2.8. Dining areas shall comply with Section 1108.2.9. Action required: Modify drawings to show compliance with 1108.2.2 for wheelchair seating and 1108.2.7 for assistive listening systems. 11/24/15 - per letter from architect there will be no fixed seating
Misc
Resolved
11/24/2015

Unified Development Ordinance Article 7, Section 7.180.G All exterior trash storage containers shall be screened so that they are not visible from off the property. Each trash enclosure shall be constructed of masonry walls with a steel gate painted to be compatible with the color of the masonry walls and building it is to serve. (Amend. #2) Action required: Trash enclosure gates must be made of metal and painted similar to building. Make needed correction to drawings. 11/24/15 - acknowledged in letter to be enforced via FDP process
Special Inspections Review Approved 11/24/2015
Joe Frogge
Fire Plan Review Rejected 11/03/2015 10/29/2015
Joe Dir
Misc
Corrective Action Required
10/29/2015

[B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. [B] 1008.1.10.1 Installation. Where panic or fire exit hardware is installed, it shall comply with the following: 1. Panic hardware shall be listed in accordance with UL 305; 2. Fire exit hardware shall be listed in accordance with UL 10C and UL 305; 3. The actuating portion of the releasing device shall extend at least one-half of the door leaf width; and 4. The maximum unlatching force shall not exceed 15 pounds (67 N).
Posting of occupant load
Corrective Action Required
10/29/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. INFORMATION PURPOSES.
Construction documents for fire alarm systems
Corrective Action Required
10/29/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS FOR THE ALARM SYSTEM. INFORMATION PURPOSES
Fire access roads or water supply required
Corrective Action Required
10/29/2015

2012 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2. 03.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing at least 75,000 pounds (34 050 kg). D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders.
Address numbers required
Corrective Action Required
10/29/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE A NUMERIC ADDRESS DURING CONSTRUCTION AND AFTER COMPLETION READABLE FROM THE ROADWAY. INFORMATION PURPOSES
Knox box required
Corrective Action Required
10/29/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. KNOX BOX CAN BE OBTAINED AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT FOR APPLCATION 816-969-1300
Construction documents - Fire protection systems
Corrective Action Required
10/29/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS OF THE FIRE SPRINKLER SYSTEM. INFORMATION PURPOSES
Installation acceptance testing
Corrective Action Required
10/29/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING IS REQUIRED FOR THE ALARM SYSTEM AND SPRINKLER SYSTEM, TO SCHEDULE TESTING CONTACT THE FIRE SEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
10/29/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. SHOW FIRE EXTINGUISHER LOCATIONS THROUGHOUT
Misc
Corrective Action Required
10/29/2015

PAGE E1 OF PLANS NEED TO SHOW EMERGENCY EGRESS LIGHTING IN VESTIBULE 111 OR 108
Misc
Corrective Action Required
10/29/2015

501.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Misc
Corrective Action Required
10/29/2015

SHOW FDC ON PLANS AS TO LOCATION OF HYDRANTS. THERE SHALL BE HYDRANT WITHIN 100' OF THE FDC
10/29/2015

10/29/2015

Building Plan Review Rejected 11/03/2015 10/23/2015
Joe Frogge
License Tax Application
Corrective Action Required
10/23/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
10/23/2015

Existing house on property. Action required: House must be entirely removed and associated demolition permit must be closed prior to issuing permit for new structure.
Misc
Corrective Action Required
10/23/2015

Foundation structural design is for >2000psi soils which is higher than normal for this area. Action required: Provide geo-tech report as justifying documentation.
Misc
Corrective Action Required
10/23/2015

2012 IBC 410.4 Platform construction. Permanent platforms shall be constructed of materials as required for the type of construction of the building in which the permanent platform is located. Permanent platforms are permitted to be constructed of fire-retardant-treated wood for Types I, II and IV construction where the platforms are not more than 30 inches above the main floor, and not more than one-third of the room floor area and not more than 3,000 square feet in area. Where the space beneath the permanent platform is used for storage or any purpose other than equipment, wiring or plumbing, the floor assembly shall be not less than 1-hour fire-resistance-rated construction. Where the space beneath the permanent platform is used only for equipment, wiring or plumbing, the underside of the permanent platform need not be protected. Action required: Comment for informational purposes. Use of wood in under-platform areas to be verified at inspections.
Misc
Corrective Action Required
10/23/2015

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Misc
Corrective Action Required
10/23/2015

2012 IBC 1009.15 Handrails. Stairways shall have handrails on each side and shall comply with Section 1012. Where glass is used to provide the handrail, the handrail shall also comply with Section 2407. (see code for exceptions) Action required: Modify drawings and details to show handrails on both sides of stairs serving raised platform in sanctuary.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
10/23/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Modify drawings to specify and indicate location of drinking fountains as directed by Table 403.1.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
10/23/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify documents to provide minimum 18" clearance at latch side of door #143.
Bldg - Handrail extensions 1012.6
Corrective Action Required
10/23/2015

2012 IBC 1012.6 – Handrail extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser and continuous to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrails shall extend horizontally above the landing 12 inches minimum beyond the top and bottom of ramp runs. The extensions of handrails shall be in the same direction of the stair flights at stairways and the ramp runs at ramps. (See code section for possible exceptions.) Action required: Modify drawings/details to show that handrails will return to a wall, guard or walking surface. Ref: handrails at dock - detail 3/A3.32.
Bldg - Occupant load posting 1004.3
Corrective Action Required
10/23/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. To be verified at inspections.
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
10/23/2015

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Comment is for informational purposes. To be verified at inspections.
Misc
Corrective Action Required
10/23/2015

2011 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Revise electrical riser diagram to show grounding to all means available. Wire types and sizes to be included.
Misc
Corrective Action Required
10/23/2015

2012 IBC 1108.2 Assembly area seating. A building, room or space used for assembly purposes with fixed seating shall comply with Sections 1108.2.1 through 1108.2.5. Lawn seating shall comply with Section 1108.2.6. Assistive listening systems shall comply with Section 1108.2.7. Performance areas viewed from assembly seating areas shall comply with Section 1108.2.8. Dining areas shall comply with Section 1108.2.9. Action required: Modify drawings to show compliance with 1108.2.2 for wheelchair seating and 1108.2.7 for assistive listening systems.
Misc
Corrective Action Required
10/26/2015

Unified Development Ordinance Article 7, Section 7.180.G All exterior trash storage containers shall be screened so that they are not visible from off the property. Each trash enclosure shall be constructed of masonry walls with a steel gate painted to be compatible with the color of the masonry walls and building it is to serve. (Amend. #2) Action required: Trash enclosure gates must be made of metal and painted similar to building. Make needed correction to drawings.
Licensed Contractors Approved 11/03/2015 10/20/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $20,986.11 $20,986.11 Paid 06/07/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 06/07/2016
8331507-Sewer Connection Fee $1,530.00 $1,530.00 Paid 06/07/2016
8331401-Water Tap Fee $21,427.00 $21,427.00 Paid 06/07/2016
8350015-Water Meter Fee $2,816.73 $2,816.73 Paid 06/07/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Failed 9/28/2016 9/28/2016 09/28/2016
Misc
Corrective Action Required
09/28/2016
VERTICAL LIGHT-GAUGE STEEL FRAMING AT ROOF HEIGHT TRANSITIONS: 1) CHECK ALL DEFLECTION CLIPS AND ENSURE SCREWS ARE AT MID-HEIGHT OF SLOTS AND ARE SET SOLID 2) COMPLETE SCREWING OF FLANGES AT BOTTOM TRACK AT ONE E-W LINE
Rough Framing Inspection - Commercial Passed 9/29/2016 9/29/2016 09/29/2016
Misc
Resolved
09/29/2016
VERTICAL LIGHT-GAUGE STEEL FRAMING AT ROOF HEIGHT TRANSITIONS: 1) CHECK ALL DEFLECTION CLIPS AND ENSURE SCREWS ARE AT MID-HEIGHT OF SLOTS AND ARE SET SOLID 2) COMPLETE SCREWING OF FLANGES AT BOTTOM TRACK AT ONE E-W LINE
Underground Electrical Inspection - Commercial Partial 10/5/2016 10/5/2016 10/05/2016
Misc
Partial Correction
10/05/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #1; #3; #4; #5; #6; #8;
Rough Framing Inspection - Commercial Partial 10/6/2016 10/6/2016 10/06/2016
Misc
Partial Correction
10/06/2016
LIGHT-GAUGE STEEL WALL FRAMING ABOVE ROOF AT: (1.4) FROM (B) TO (C);
Rough Framing Inspection - Commercial Partial 10/10/2016 10/10/2016
Misc
Partial Correction
10/06/2016
LIGHT-GAUGE STEEL WALL FRAMING ABOVE LOW ROOF AT: (1.4) FROM (B) TO (C); (6) FROM (B) TO (C);
Underground Electrical Inspection - Commercial Partial 10/10/2016 10/10/2016 10/10/2016
Misc
Partial Correction
10/05/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #1; #3; #4; #5; #6; #8; ALL REMAINING EXCEPT #16;
Rough Framing Inspection - Commercial Partial 10/17/2016 10/17/2016 10/17/2016
Misc
Partial Correction
10/10/2016
LIGHT-GAUGE STEEL WALL FRAMING ABOVE LOW ROOF AT: (1.4) FROM (B) TO (C); (6) FROM (B) TO (C);
Misc
Partial Correction
10/17/2016
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG.
Rough Framing Inspection - Commercial Partial 10/17/2016 10/17/2016
Misc
Partial Correction
10/17/2016
LIGHT-GAUGE STEEL WALL FRAMING ABOVE LOW ROOF AT: (1.4) FROM (B) TO (C); (6) FROM (B) TO (C);
Misc
Partial Correction
10/17/2016
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01.
Underground Electrical Inspection - Commercial Not Ready 10/18/2016 10/18/2016 10/18/2016
Misc
Partial Correction
10/10/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #1; #3; #4; #5; #6; #8; ALL REMAINING EXCEPT #16;
Underground Electrical Inspection - Commercial Partial 10/18/2016 10/18/2016 10/18/2016
Misc
Partial Correction
10/18/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #1; #3; #4; #5; #6; #8; ALL REMAINING INCLUDING #16;
Underground Electrical Inspection - Commercial Partial 10/24/2016 10/24/2016
Misc
Partial Correction
10/18/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #1; #3; #4; #5; #6; #8; ALL REMAINING INCLUDING #16;
Misc
Partial Correction
10/24/2016
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 6. 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE.
Underground Electrical Inspection - Commercial Partial 10/27/2016 10/27/2016 10/27/2016
Misc
Resolved
10/27/2016
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #1; #3; #4; #5; #6; #8; ALL REMAINING INCLUDING #16;
Misc
Partial Correction
10/24/2016
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 5.; 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE; 1 TO 2 TO 4 TO 5; 12 TO 11 + ~30' STUBS FROM EACH TO WEST FOR FUTURE;
Underground Electrical Inspection - Commercial Partial 10/31/2016 10/31/2016 10/31/2016
Misc
Partial Correction
10/27/2016
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 5.; 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE; 1 TO 2 TO 4 TO 5; 12 TO 11 + ~30' STUBS FROM EACH TO WEST FOR FUTURE; #11 TO #12 TO #13 TO #14 TO #15 REPAIR OF DAMAGED STORM SEWER LINE IN PROGRESS 45' NORTH OF #14;
Underground Electrical Inspection - Commercial Partial 11/1/2016 11/1/2016 11/01/2016
Misc
Partial Correction
10/31/2016
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 5.; 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE; 1 TO 2 TO 4 TO 5; 12 TO 11 + ~30' STUBS FROM EACH TO WEST FOR FUTURE; #11 TO #12 TO #13 TO #14 TO #15 REPAIR OF DAMAGED STORM SEWER LINE IN PROGRESS 45' NORTH OF #14; #15 TO #16 TO #17;
Underground Electrical Inspection - Commercial Partial 11/4/2016 11/4/2016 11/04/2016
Misc
Partial Correction
11/01/2016
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 5.; 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE; 1 TO 2 TO 4 TO 5; 12 TO 11 + ~30' STUBS FROM EACH TO WEST FOR FUTURE; #11 TO #12 TO #13 TO #14 TO #15; #15 TO #16 TO #17; #17 TO 50' EAST FOR FUTURE; #16 WEST TO BLDG; #4 TO #3 TO #18;
Underground Electrical Inspection - Commercial Partial 11/7/2016 11/7/2016 11/07/2016
Misc
Partial Correction
11/04/2016
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 5.; 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE; 1 TO 2 TO 4 TO 5; 12 TO 11 + ~30' STUBS FROM EACH TO WEST FOR FUTURE; #11 TO #12 TO #13 TO #14 TO #15; #15 TO #16 TO #17; #17 TO 50' EAST FOR FUTURE; #16 WEST TO BLDG; #4 TO #3 TO #18; FROM #1 TO (A) & TO (B); COMPLETION OF FROM #6 TO BLDG W WALL; FROM #7 TO BLDG W WALL
Gas Piping Inspection - Commercial Partial 11/17/2016 11/17/2016
Misc
Corrective Action Required
11/17/2016
WEATHER-EXPOSED STEEL PIPE MUST BE PAINTED AS CORROSION PROTECTION.
Misc
Corrective Action Required
11/17/2016
ENSURE SUPPORT BLOCKS LOCATED AT/NEAR TEES AND 90'S AT ROOPTOP PIPING
Gas Service Inspection - Commercial Passed 11/17/2016 11/17/2016 11/17/2016
In-wall Inspection Partial 11/17/2016 11/17/2016
Misc
Partial Correction
11/17/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF: - ELECT [115] - VEST [118] N WALL TWO LAYERS S FACE - TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK - MECH [145] **BOCA PLATES MISSING**
In-wall Inspection Partial 11/23/2016 11/23/2016
Misc
Partial Correction
11/17/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF: - ELECT [115] - VEST [118] N WALL TWO LAYERS S FACE - TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK - MECH [145] **BOCA PLATES MISSING** - SOUTH WALL OF E-W LEG OF N END OF CORR [128];
In-wall Inspection Partial 11/29/2016 11/29/2016 11/29/2016
Misc
Partial Correction
11/23/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF: - ELECT [115] - VEST [118] N WALL TWO LAYERS S FACE - TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK - MECH [145] **BOCA PLATES MISSING** - SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157];
Electrical Service Inspection Passed 12/5/2016 12/5/2016 12/05/2016
In-wall Inspection Not Ready 12/7/2016 12/7/2016 12/07/2016
Misc
Partial Correction
11/29/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF: - ELECT [115] - VEST [118] N WALL TWO LAYERS S FACE - TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK - MECH [145] **BOCA PLATES MISSING** - SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [1]; [1];
In-wall Inspection Partial 12/12/2016 12/12/2016 12/12/2016
Misc
Partial Correction
12/07/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145] SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156];
In-wall Inspection Partial 12/19/2016 12/19/2016 12/19/2016
Misc
Partial Correction
12/12/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156];
Underslab Plumbing Inspection - Commercial Passed 12/19/2016 12/19/2016
Rough Framing Inspection - Commercial Partial 11/23/2016 12/30/2016 12/30/2016
Misc
Resolved
11/23/2016
LIGHT-GAUGE STEEL WALL FRAMING ABOVE LOW ROOF AT: (1.4) FROM (B) TO (C); (6) FROM (B) TO (C);
Misc
Partial Correction
10/17/2016
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01. -RAISED FLOOR FRAMING UNDER RM 121-127
In-wall Inspection Partial 12/30/2016 12/30/2016 12/30/2016
Misc
Partial Correction
12/19/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102
Above Ceiling Inspection Partial 1/4/2017 01/04/2017
Misc
Partial Correction
01/04/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: VESTIBULE OUTSIDE RR'S 103 & 104; 157 CONTINGENT ON INSTALLATION OF SPRINKLER DROP & S.A. DIFFUSER + REMOVAL OF TEMP WIRING;
Rough Framing Inspection - Commercial Partial 1/4/2017 01/04/2017
Misc
Partial Correction
12/30/2016
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01. -RAISED FLOOR FRAMING UNDER RM 121-127; SAME AT 120;
Misc
Partial Correction
01/04/2017
SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP;
In-wall Inspection Partial 1/4/2017 1/4/2017 01/04/2017
Misc
Partial Correction
12/30/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102
In-wall Inspection Partial 1/6/2017 1/6/2017 01/06/2017
Misc
Partial Correction
01/04/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102
Rough Framing Inspection - Commercial Not Ready 1/6/2017 01/06/2017
Misc
Partial Correction
01/04/2017
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01. -RAISED FLOOR FRAMING UNDER RM 121-127; SAME AT 120;
Misc
Partial Correction
01/04/2017
SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP;
Misc
Corrective Action Required
01/06/2017
FRAMING OF PLATFORM AT [128] COVERED AT BOTTOM WITH INSULATION -- NOT APPROVED
Rough Framing Inspection - Commercial Partial 1/9/2017 1/9/2017 01/09/2017
Misc
Partial Correction
01/06/2017
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01.
Misc
Partial Correction
01/06/2017
OK TO COVER WHEN READY FRAMING ONLY AT: SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP; RAISED FLOOR FRAMING AT 121-127; SAME AT 120; FRAMING OF PLATFORM AT [128];
Misc
Resolved
01/09/2017
FRAMING OF PLATFORM AT [128] COVERED AT BOTTOM WITH INSULATION -- NOT APPROVED
In-wall Inspection Partial 1/11/2017 1/11/2017 01/11/2017
Misc
Partial Correction
01/06/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; [116] S/SW WALLS; PLATFORM [117] EAST, SOUTH & NORTH WALLS; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102
In-wall Inspection Partial 1/23/2017 1/23/2017 01/23/2017
Misc
Partial Correction
01/11/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; [116] S/SW WALLS; PLATFORM [117] EAST, SOUTH & NORTH WALLS; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102; CORRIDOR [128]
Rough Framing Inspection - Commercial Partial 1/23/2017 01/23/2017
Misc
Partial Correction
01/09/2017
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01.
Misc
Partial Correction
01/09/2017
OK TO COVER WHEN READY FRAMING ONLY AT: SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP; RAISED FLOOR FRAMING AT 121-127; SAME AT 120; FRAMING OF PLATFORM AT [128]; 7" HIGH PLATFORMS @ 137 & 140
Above Ceiling Inspection Partial 1/23/2017 1/23/2017 01/23/2017
Misc
Resolved
01/23/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: VESTIBULE OUTSIDE RR'S 103 & 104; 157 CONTINGENT ON INSTALLATION OF SPRINKLER DROP & S.A. DIFFUSER + REMOVAL OF TEMP WIRING;
Misc
Partial Correction
01/23/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153;
In-wall Inspection Partial 1/24/2017 01/24/2017
Misc
Partial Correction
01/23/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; [116] S/SW WALLS; PLATFORM [117] EAST, SOUTH & NORTH WALLS; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102; CORRIDOR [128]; [120] - [127];
Rough Framing Inspection - Commercial Partial 1/24/2017 01/24/2017
Misc
Partial Correction
01/23/2017
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01.
Misc
Partial Correction
01/23/2017
OK TO COVER WHEN READY FRAMING ONLY AT: SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP; RAISED FLOOR FRAMING AT 121-127; SAME AT 120; FRAMING OF PLATFORM AT [128]; 7" HIGH PLATFORMS @ 137 & 140; RAMP AT [128] N; STAIR AT [118] FRAMED FOR 7" RISERS; PLATFORMS FOR BOOTHS IN [137] & [140];
Above Ceiling Inspection Partial 1/24/2017 1/24/2017 01/24/2017
Misc
Partial Correction
01/23/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156];
Misc
Partial Correction
01/24/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153;
Above Ceiling Inspection Partial 1/27/2017 1/27/2017 01/27/2017
Misc
Partial Correction
01/24/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156];
Misc
Partial Correction
01/24/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148;
In-wall Inspection Partial 1/30/2017 01/30/2017
Misc
Partial Correction
01/24/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; [116] S/SW WALLS; PLATFORM [117] EAST, SOUTH & NORTH WALLS; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; IN-WALL OK FOR: SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102; CORRIDOR [128]; [120] - [127]; [116]; BOOTH AT [151] SOUTH;
Rough Framing Inspection - Commercial Partial 1/30/2017 1/30/2017 01/30/2017
Misc
Partial Correction
01/24/2017
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01.
Misc
Partial Correction
01/24/2017
OK TO COVER WHEN READY FRAMING ONLY AT: SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP; RAISED FLOOR FRAMING AT 121-127; SAME AT 120; FRAMING OF PLATFORM AT [128]; 7" HIGH PLATFORMS @ 137 & 140; RAMP AT [128] N; STAIR AT [118] FRAMED FOR 7" RISERS; PLATFORMS FOR BOOTHS IN [137] & [140]; [116]; RAISED FLOOR FOR [116] AND FOR BOOTH AT [151] SOUTH, WITH UNDER-FLOOR ELECTRICAL;
Above Ceiling Inspection Partial 2/2/2017 2/2/2017 02/02/2017
Misc
Partial Correction
01/27/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; [103]; [104]; [106];
Misc
Partial Correction
01/27/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148;
Above Ceiling Inspection Partial 2/9/2017 2/9/2017 02/09/2017
Misc
Partial Correction
02/02/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE;
Misc
Partial Correction
02/02/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106];
Above Ceiling Inspection Partial 2/15/2017 2/15/2017 02/15/2017
Misc
Partial Correction
02/09/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE; PROJECTING SOFFIT/ FACIA AT 102 E;
Misc
Partial Correction
02/09/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106];
In-wall Inspection Partial 2/21/2017 02/21/2017
Misc
Partial Correction
01/30/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; [116] S/SW WALLS; PLATFORM [117] EAST, SOUTH & NORTH WALLS; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102; CORRIDOR [128]; [120] - [127]; [116]; BOOTH AT [151] SOUTH; SOUND BOOTH AT SANCTUARY;
Above Ceiling Inspection Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/15/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE; PROJECTING SOFFIT/ FACIA AT 102 E; 107; 109; 110; 112; 122; 124; 127;
Misc
Partial Correction
02/15/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106];
Rough Framing Inspection - Commercial Partial 2/28/2017 02/28/2017
Misc
Partial Correction
02/28/2017
PLATFORM AT SANCTUARY 117: SUPPORT FRAMING APPROVED; JOIST INSTALLATION PARTIAL; NO ISSUES WITH ELECTRICAL CONDUIT AND BOXES TO BE CONCEALED. OK TO PROCEED WITH INSULATION AND JOIST INSTALLATION.
Above Ceiling Inspection Partial 2/28/2017 02/28/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE; PROJECTING SOFFIT/ FACIA AT 102 E;
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106]; 107; 109; 110; 112; 122; 124; 127;
Above Ceiling Inspection Partial 3/2/2017 3/2/2017 03/02/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE; PROJECTING SOFFIT/ FACIA AT 102 E;
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106]; 107; 109; 110; 112; 122; 124; 127; {114; 120; 122; 123; 125; 128 EXCLUDING S DOGLEG;
Rough Framing Inspection - Commercial Partial 3/2/2017 3/2/2017 03/02/2017
Misc
Resolved
03/02/2017
OK TO COVER WHEN READY L.G. STEEL FURRING FRAMING PER WALL SECTION 1/E1 ON ERECTION DRWG. TAPCON FASTENING APPROVED PER DETAIL 4/S4.01.
Misc
Partial Correction
01/30/2017
OK TO COVER WHEN READY FRAMING ONLY AT: SOUTH WALL OF 120 OK FOR CONSTRUCTION OF ADJACENT RAMP; RAISED FLOOR FRAMING AT 121-127; SAME AT 120; FRAMING OF PLATFORM AT [128]; 7" HIGH PLATFORMS @ 137 & 140; RAMP AT [128] N; STAIR AT [118] FRAMED FOR 7" RISERS; PLATFORMS FOR BOOTHS IN [137] & [140]; [116]; RAISED FLOOR FOR [116] AND FOR BOOTH AT [151] SOUTH, WITH UNDER-FLOOR ELECTRICAL; SANCTUARY PLATFORM COMPLETE INCLUDING ELECTRICAL;
Above Ceiling Inspection Partial 3/7/2017 3/7/2017 03/07/2017
Misc
Partial Correction
03/02/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106]; 107; 109; 110; 112; 122; 124; 127; {114; 120; 122; 123; 125; 128 EXCLUDING S DOGLEG;
Misc
Partial Correction
03/02/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE; PROJECTING SOFFIT/ FACIA AT 102 E; ROOMS 129 AND 118 APPROVED
Sprinkler - Hydrostatic Test Partial 3/8/2017 03/08/2017
Above Ceiling Inspection Passed 3/7/2017 03/27/2017
Misc
Resolved
03/27/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 130; 131; 133; 134; 136; 138; 141; 143; 145; 147; 149; 152; 153; 144; 148; [103]; [104]; [106]; 107; 109; 110; 112; 122; 124; 127; {114; 120; 122; 123; 125; 128 EXCLUDING S DOGLEG;
Misc
Resolved
03/27/2017
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [132]; [135]; [139]; [142]; [146]; [155]; [156]; VESTIBULE 108; VESTIBULE 111; LOBBY 102; ENTRY 119; ENTRY 101; 113 NE & SE; PROJECTING SOFFIT/ FACIA AT 102 E; ROOMS 129 AND 118 APPROVED
In-wall Inspection Passed 2/21/2017 03/27/2017
Misc
Resolved
03/27/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: ONE-SIDING OF ELECT[115]; VEST [118] N WALL TWO LAYERS S FACE; TWO 4' WIDE STACKS @ PLATFORM [117] FOR DUCTWORK; MECH [145]; WOMENS RR [103]; MEN'S RR[104]; JANITOR [105]; FAMILY RR [106]; ELECT [115] SOUTH WALL SOUTH FACE; 102; 129; 144; 114 NORTH WALL; [116] S/SW WALLS; PLATFORM [117] EAST, SOUTH & NORTH WALLS; SOUTH WALL OF E-W LEG OF N END OF CORR [128]; [131]-[143]; [145]; [147]-[150]; [157]; [151] THROUGH [156]; SANCTUARY 113 STARTING FROM PLATFORM (117) STAIR ALL THE WAY AROUND TO THE OTHER SIDE; RM 107 TO 112; DOUBLE STUD WALL BETWEEN 113&102; CORRIDOR [128]; [120] - [127]; [116]; BOOTH AT [151] SOUTH; SOUND BOOTH AT SANCTUARY;
Rough Framing Inspection - Commercial Passed 2/28/2017 03/27/2017
Misc
Resolved
03/27/2017
PLATFORM AT SANCTUARY 117: SUPPORT FRAMING APPROVED; JOIST INSTALLATION PARTIAL; NO ISSUES WITH ELECTRICAL CONDUIT AND BOXES TO BE CONCEALED. OK TO PROCEED WITH INSULATION AND JOIST INSTALLATION.
Underground Electrical Inspection - Commercial Passed 11/7/2016 03/27/2017
Misc
Resolved
03/27/2017
CONDUITS BETWEEN LIGHT POLE BASES AT THE FOLLOWING: 11 THROUGH 5.; 100 FEET OF CONDUIT EAST OF POLE 6 FOR HOME RUNS AND FUTURE PHASE POLE BASE; 1 TO 2 TO 4 TO 5; 12 TO 11 + ~30' STUBS FROM EACH TO WEST FOR FUTURE; #11 TO #12 TO #13 TO #14 TO #15; #15 TO #16 TO #17; #17 TO 50' EAST FOR FUTURE; #16 WEST TO BLDG; #4 TO #3 TO #18; FROM #1 TO (A) & TO (B); COMPLETION OF FROM #6 TO BLDG W WALL; FROM #7 TO BLDG W WALL
Sprinkler - Hydrostatic Test Passed 4/4/2017 04/03/2017
Alarm Test Partial 4/4/2017 04/04/2017
Sprinkler - Flow Test Passed 4/4/2017 04/04/2017
Gas Piping Inspection - Commercial Passed 4/17/2017 04/17/2017
Misc
Resolved
04/17/2017
WEATHER-EXPOSED STEEL PIPE MUST BE PAINTED AS CORROSION PROTECTION.
Misc
Resolved
04/17/2017
ENSURE SUPPORT BLOCKS LOCATED AT/NEAR TEES AND 90'S AT ROOPTOP PIPING
Miscellaneous Inspection Passed 4/17/2017 04/17/2017
Occupancy Inspection - Planning Passed 4/18/2017 04/18/2017
Occupancy Inspection - Codes Commercial Partial 4/18/2017 4/18/2017 04/18/2017
Misc
Corrective Action Required
04/17/2017
RESOLVE ANY ISSUES WITH: - WATER UTILITIES DEPT - PUBLIC WORKS
Misc
Resolved
04/18/2017
- WEATHER-EXPOSED STEEL PIPE MUST BE PAINTED AS CORROSION PROTECTION. - ENSURE SUPPORT BLOCKS LOCATED AT/NEAR TEES AND 90'S AT ROOPTOP PIPING - DIRT LEG CAPS MUST BE REMOVABLE
Misc
Corrective Action Required
04/18/2017
NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Misc
Corrective Action Required
04/18/2017
GLAZING IN HAZARDOUS LOCATIONS: TO BE RE-INSPECTED FOR LABELING AFTER GLASS IS FULLY CLEANED
Misc
Corrective Action Required
04/18/2017
OCCUPANCY STATUS: OK TO SET UP FOR OPERATION. STAFF, FURNISHING, AND CONTENTS OK. NO OPERATION, GATHERINGS, OR SERVICES PRIOR TO APPROVAL.
Misc
Corrective Action Required
04/18/2017
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-PIPED EQUIPMENT EXCEPT WHERE APPROVED AIR GAP IS EXPOSED.
Alarm Test Passed 4/18/2017 04/18/2017
Occupancy Inspection - Fire Passed 4/18/2017 04/18/2017
Occupancy Inspection - Water Utilities Passed 4/18/2017 04/20/2017
Occupancy Inspection - Codes Commercial Partial 4/24/2017 4/24/2017 04/24/2017
Misc
Corrective Action Required
04/18/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Misc
Resolved
04/24/2017
NEC 600.4 ELECTRIC SIGN MARKINGS: SIGNS AND OUTSIDE LIGHTING SYSTEMS SHALL BE SHOP-LABELED WITH LISTING, MANUFACTURER'S NAME, TRADEMARK, OR OTHER MEANS OF IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
Misc
Resolved
04/24/2017
GLAZING IN HAZARDOUS LOCATIONS: TO BE RE-INSPECTED FOR LABELING AFTER GLASS IS FULLY CLEANED
Misc
Corrective Action Required
04/18/2017
OCCUPANCY STATUS: OK TO SET UP FOR OPERATION. STAFF, FURNISHING, AND CONTENTS OK. NO OPERATION, GATHERINGS, OR SERVICES PRIOR TO APPROVAL.
Misc
Resolved
04/24/2017
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-PIPED EQUIPMENT EXCEPT WHERE APPROVED AIR GAP IS EXPOSED.
Occupancy Inspection - Codes Commercial Temporary C of O 4/26/2017 04/26/2017
Misc
Corrective Action Required
04/24/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Misc
Resolved
04/26/2017
OCCUPANCY STATUS: OK TO SET UP FOR OPERATION. STAFF, FURNISHING, AND CONTENTS OK. NO OPERATION, GATHERINGS, OR SERVICES PRIOR TO APPROVAL.
Occupancy Inspection - Engineering Passed 4/18/2017 05/12/2017
Occupancy Inspection - Codes Commercial Temporary C of O 6/1/2017 06/01/2017
Misc
Corrective Action Required
04/26/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Occupancy Inspection - Codes Commercial Temporary C of O 6/14/2017 06/14/2017
Misc
Corrective Action Required
06/01/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Occupancy Inspection - Codes Commercial Temporary C of O 6/15/2017 06/15/2017
Misc
Corrective Action Required
06/14/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Occupancy Inspection - Codes Commercial Temporary C of O 7/13/2017 07/13/2017
Misc
Corrective Action Required
06/15/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Occupancy Inspection - Codes Commercial Temporary C of O 9/20/2017 at 8:30 AM 09/20/2017
Misc
Corrective Action Required
07/13/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Occupancy Inspection - Codes Commercial Full C of O 10/16/2017 at 2:40 PM 10/16/2017
Misc
Resolved
10/16/2017
RESOLVE ANY ISSUES WITH PUBLIC WORKS
Documents & Images
Date Uploaded File Type Document Name
10/29/2015 Letter Fire Building Plan Review
10/29/2015 Letter Codes P/R Corrections Document
11/24/2015 handrail CMR
11/25/2015 Letter Fire Building Plan Review
06/07/2016 Receipt Receipt for transaction: 2016-003421
06/08/2016 Letter Codes Plan Review Conditions
06/08/2016 Letter Codes Building Permit
07/13/2016 Letter Fire (Alarm) Plan Review Notice
09/28/2016 Letter Inspection Summary
09/29/2016 Letter Inspection Summary
10/05/2016 Letter Inspection Summary
10/06/2016 Letter Inspection Summary
10/10/2016 Letter Inspection Summary
10/17/2016 Letter Inspection Summary
10/18/2016 Letter Inspection Summary
10/24/2016 Letter Inspection Summary
10/27/2016 Letter Inspection Summary
10/31/2016 Letter Inspection Summary
11/01/2016 Letter Inspection Summary
11/04/2016 Letter Inspection Summary
11/07/2016 Letter Inspection Summary
11/17/2016 Letter Inspection Summary
11/23/2016 Letter Inspection Summary
11/29/2016 Letter Inspection Summary
12/05/2016 Letter Inspection Summary
12/12/2016 Letter Inspection Summary
12/19/2016 Letter Inspection Summary
12/21/2016 08-545 The Summit - Rev 7 Sheet - A1.12
12/27/2016 Summit stove
12/30/2016 Letter Inspection Summary
01/04/2017 Letter Inspection Summary
01/06/2017 Letter Inspection Summary
01/09/2017 Letter Inspection Summary
01/11/2017 Letter Inspection Summary
01/23/2017 Letter Inspection Summary
01/24/2017 Letter Inspection Summary
01/27/2017 Letter Inspection Summary
01/30/2017 Letter Inspection Summary
02/02/2017 Letter Inspection Summary
02/09/2017 Letter Inspection Summary
02/15/2017 Letter Inspection Summary
02/21/2017 Letter Inspection Summary
02/28/2017 Letter Inspection Summary
03/02/2017 Letter Inspection Summary
03/07/2017 Letter Inspection Summary
04/18/2017 Letter Inspection Summary
04/26/2017 Letter Codes Temporary Certificate of Occupancy
06/01/2017 Letter Codes Temporary Certificate of Occupancy
06/14/2017 Letter Codes Temporary Certificate of Occupancy
06/15/2017 Letter Codes Temporary Certificate of Occupancy
07/13/2017 Letter Codes Temporary Certificate of Occupancy
09/20/2017 Letter Codes Temporary Certificate of Occupancy
10/16/2017 Letter Field Certificate of Occupancy
10/17/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home