Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Plan Review
|
Approved
|
10/12/2015
|
10/13/2015
|
|
Khanh Nguyen
|
|
Misc
Additional information required.
Action required:
1) Provide all construction information and details for raised platform including stairs, handrails, etc.
2) Specify exhaust fan for Family RR 102.
10/6/15 - exhaust fan information approved - Platform information incomplete. Reference 410.4 for platform construction materials. Reference 1009.7 for stair treads and risers. Reference 1013 for guard requirements. Reference 1012 for handrail requirements. All of this needs to be shown on the drawings.
10/13/15 - drawings updated
|
|
Bldg - Occupant load posting 1004.3
2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Comment is for informational purposes. Posting to be verified during inspections.
|
|
Misc
2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Action required: Provide emergency lighting at exterior side of exit discharges.
|
|
Misc
2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions)
Action required: Modify drawings to show additional exit signs at rear vestibule and at north door in corridor serving Pre-K Classrooms.
10/6/15 - exit sign provided at rear vestibule as directed, but still missing at north door of corridor serving Pre-K Classrooms.
10/13/15 - sign added to drawing
|
|
Mech - Outdoor air required 403.2
2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space.
Action required: Revise drawings to show outside air calculations as well as method of delivery.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
10/12/2015
|
|
Joe Dir
|
|
DE Corps of Engineers
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
TO SCHEDULE A TEST PRIOR TO THE FINAL OCCUPANCY INSEPCTION CONTACT THE FIRE DEPARTMENT AT 816-969-1300
|
|
|
Fire Plan Review
|
Approved with Conditions
|
10/12/2015
|
10/08/2015
|
|
Joe Dir
|
|
Misc
Corrective Action Required
|
|
Posting of occupant load
Corrective Action Required
2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
POST THE OCCUPANT LOADS IN THE WORSHIP CENTER, KIDS CLASS ROOMS, NURSERY, MEETING ROOMS. VERIFIED AT INSPECTION
ADDRESSED IN LETTER AND PLANS
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
PROVIDE ENGINEERED SHOP DRAWINGS TO THE ALTERATIONS TO THE ALARM SYSTEM. INFORMATION PURPOSES
ADDRESSED IN LETTER
|
|
Address numbers required
Corrective Action Required
2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF THE SUITE ON THE EXTERIOR OF ALL DOORS LEADING INTO THE SUITE. INFORMATION PURPOSES, VERIFIED AT INSPECTION.
ADDRESSED IN LETTER
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
PROVIDE ENGINEERED SHOP DRAWINGS OF THE ALTERATIONS OF THE SPRINKLER SYSTEM. INFORMATION PURPOSES.
ADDRESSED IN LETTER
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING REQUIRED FOR THE ALARM SYSTEM. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. INFORMATION PURPOSES.
ADDRESSED IN LETTER
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE FIRE SPRINKLER SYSTEM SHALL BE CURRENT ON THE REQUIRED ANNUAL SERVICING OF THE SYSTEM. SERVICE TAG DISPLAYED ON THE RISER. INFORMATION PURPOSES, VERIFIED AT INSPECTION.
ADDRESSED IN LETTER
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. PROVIDE 5 POUND FIRE EXTINGUISHERS, MOUNT AT LOCATIONS ACCORDING TO PLANS. VERIFED AT INSPECTION.
ADDRESSED IN LETTER AND PLANS
|
|
Misc
Corrective Action Required
REAR EXIT OFF OF THE WORSHIP CENTER AND THE K-CLASS ROOM. THE VESTIBULE DOES NOT SHOW EXIT SIGNAGE, EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING.
ADDRESSED IN LETTER AND PLANS
|
|
Misc
Corrective Action Required
SOUTHWEST EXIT OF WORSHIP CENTER DOES NOT SHOW EXTERIOR EGRESS LIGHTING
ADDRESSED IN LETTER AND PLANS
|
|
Misc
Corrective Action Required
LOBBY MAIN ENTRANCE, DOES NOT SHOW INTERIOR EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING. NIGHT LIGHTS DO NOT ACCOUNT FOR EMERGENCY LIGHTING.
ADDRESSED IN LETTER
|
|
Misc
Corrective Action Required
B] 1006.1 Illumination required.
The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
B] 1006.2 Illumination level.
The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. INFORMATIONAL PURPOSES.
ADDRESSED IN LETTER
|
|
|
Licensed Contractors
|
Approved
|
10/05/2015
|
10/06/2015
|
|
Joe Frogge
|
|
LC - MEP Subs
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
09/29/2015
|
09/29/2015
|
|
Joe Dir
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
HYDROSTATIC PRESSURE TEST REQUIRED, ACCEPTANCE FLOW TEST REQUIRED. TO SCHEDULE TESTS CONTACT THE FIRE DEPARTMENT AT 818-969-1300
|
|
|
Building Plan Review
|
Rejected
|
10/02/2015
|
09/28/2015
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Additional information required.
Action required:
1) Provide all construction information and details for raised platform including stairs, handrails, etc.
2) Specify exhaust fan for Family RR 102.
|
|
Bldg - Occupant load posting 1004.3
Corrective Action Required
2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Comment is for informational purposes. Posting to be verified during inspections.
|
|
Misc
Corrective Action Required
2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Action required: Provide emergency lighting at exterior side of exit discharges.
|
|
Misc
Corrective Action Required
2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions)
Action required: Modify drawings to show additional exit signs at rear vestibule and at north door in corridor serving Pre-K Classrooms.
|
|
Mech - Outdoor air required 403.2
Corrective Action Required
2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space.
Action required: Revise drawings to show outside air calculations as well as method of delivery.
|
|
|
Licensed Contractors
|
Rejected
|
10/02/2015
|
09/25/2015
|
|
Joe Frogge
|
|
LC - MEP Subs
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
|
|
|
Fire Plan Review
|
Rejected
|
10/02/2015
|
09/24/2015
|
|
Joe Dir
|
|
Misc
Corrective Action Required
|
|
Posting of occupant load
Corrective Action Required
2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
POST THE OCCUPANT LOADS IN THE WORSHIP CENTER, KIDS CLASS ROOMS, NURSERY, MEETING ROOMS. VERIFIED AT INSPECTION
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
PROVIDE ENGINEERED SHOP DRAWINGS TO THE ALTERATIONS TO THE ALARM SYSTEM. INFORMATION PURPOSES
|
|
Address numbers required
Corrective Action Required
2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF THE SUITE ON THE EXTERIOR OF ALL DOORS LEADING INTO THE SUITE. INFORMATION PURPOSES, VERIFIED AT INSPECTION.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
PROVIDE ENGINEERED SHOP DRAWINGS OF THE ALTERATIONS OF THE SPRINKLER SYSTEM. INFORMATION PURPOSES.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING REQUIRED FOR THE ALARM SYSTEM. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. INFORMATION PURPOSES.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE FIRE SPRINKLER SYSTEM SHALL BE CURRENT ON THE REQUIRED ANNUAL SERVICING OF THE SYSTEM. SERVICE TAG DISPLAYED ON THE RISER. INFORMATION PURPOSES, VERIFIED AT INSPECTION.
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. PROVIDE 5 POUND FIRE EXTINGUISHERS, MOUNT AT LOCATIONS ACCORDING TO PLANS. VERIFED AT INSPECTION.
|
|
Misc
Corrective Action Required
REAR EXIT OFF OF THE WORSHIP CENTER AND THE K-CLASS ROOM. THE VESTIBULE DOES NOT SHOW EXIT SIGNAGE, EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING.
|
|
Misc
Corrective Action Required
SOUTHWEST EXIT OF WORSHIP CENTER DOES NOT SHOW EXTERIOR EGRESS LIGHTING
|
|
Misc
Corrective Action Required
LOBBY MAIN ENTRANCE, DOES NOT SHOW INTERIOR EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING. NIGHT LIGHTS DO NOT ACCOUNT FOR EMERGENCY LIGHTING.
|
|
Misc
Corrective Action Required
B] 1006.1 Illumination required.
The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
B] 1006.2 Illumination level.
The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. INFORMATIONAL PURPOSES.
|
|
|