Permit Application Status

PRCOM20152209


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20152209
Building Permit - Commercial
Certificate of Occupancy
LBP IV LLC
CHANGE OF TENANT
MODIFY SPACE TO BECOME A CHURCH THAT INCLUDES A WORSHIP CENTER AND CLASSROOMS
09/22/2015
10/13/2015
04/06/2016
12/11/2015
Locations
Contacts
3 SQUARE CONTRACTING INC, Address:1243 MERRIAM LANE, Phone:(913) 754-3033  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INTERSTATE ELECTRICAL CONSTRUCTION, Address:3710 ROBINSON PIKE RD, Phone:(816) 761-0200  
ALLIANCE MECHANICAL CONTRACTORS, Address:305 W CEDAR , Phone:(913) 553-2600  
DAVID KASTER, Address:KASTER ARCHITECTS, Phone:(913) 681-1200  
LBP IV LLC, Address:3215 NE CARNEGIE DR STE 200  
LBP IV LLC, Address:3170 NE CARNEGIE DR STE 400  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 10/12/2015 10/13/2015
Khanh Nguyen
Misc
Resolved
10/13/2015

Additional information required. Action required: 1) Provide all construction information and details for raised platform including stairs, handrails, etc. 2) Specify exhaust fan for Family RR 102. 10/6/15 - exhaust fan information approved - Platform information incomplete. Reference 410.4 for platform construction materials. Reference 1009.7 for stair treads and risers. Reference 1013 for guard requirements. Reference 1012 for handrail requirements. All of this needs to be shown on the drawings. 10/13/15 - drawings updated
Bldg - Occupant load posting 1004.3
Resolved
10/06/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. Posting to be verified during inspections.
Misc
Resolved
10/06/2015

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of exit discharges.
Misc
Resolved
10/13/2015

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Modify drawings to show additional exit signs at rear vestibule and at north door in corridor serving Pre-K Classrooms. 10/6/15 - exit sign provided at rear vestibule as directed, but still missing at north door of corridor serving Pre-K Classrooms. 10/13/15 - sign added to drawing
Mech - Outdoor air required 403.2
Resolved
10/06/2015

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Revise drawings to show outside air calculations as well as method of delivery.
Alarm Plan Review Released for Construction 10/12/2015
Joe Dir
DE Corps of Engineers
10/12/2015

Installation acceptance testing
Corrective Action Required
10/12/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TO SCHEDULE A TEST PRIOR TO THE FINAL OCCUPANCY INSEPCTION CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Fire Plan Review Approved with Conditions 10/12/2015 10/08/2015
Joe Dir
Misc
Corrective Action Required
10/05/2015

Posting of occupant load
Corrective Action Required
10/05/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOADS IN THE WORSHIP CENTER, KIDS CLASS ROOMS, NURSERY, MEETING ROOMS. VERIFIED AT INSPECTION ADDRESSED IN LETTER AND PLANS
Construction documents for fire alarm systems
Corrective Action Required
10/05/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS TO THE ALTERATIONS TO THE ALARM SYSTEM. INFORMATION PURPOSES ADDRESSED IN LETTER
Address numbers required
Corrective Action Required
10/05/2015

2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF THE SUITE ON THE EXTERIOR OF ALL DOORS LEADING INTO THE SUITE. INFORMATION PURPOSES, VERIFIED AT INSPECTION. ADDRESSED IN LETTER
Construction documents - Fire protection systems
Corrective Action Required
10/05/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS OF THE ALTERATIONS OF THE SPRINKLER SYSTEM. INFORMATION PURPOSES. ADDRESSED IN LETTER
Installation acceptance testing
Corrective Action Required
10/05/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING REQUIRED FOR THE ALARM SYSTEM. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. INFORMATION PURPOSES. ADDRESSED IN LETTER
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/05/2015

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE FIRE SPRINKLER SYSTEM SHALL BE CURRENT ON THE REQUIRED ANNUAL SERVICING OF THE SYSTEM. SERVICE TAG DISPLAYED ON THE RISER. INFORMATION PURPOSES, VERIFIED AT INSPECTION. ADDRESSED IN LETTER
Portable fire extinguishers - conspicuous locations
Corrective Action Required
10/05/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. PROVIDE 5 POUND FIRE EXTINGUISHERS, MOUNT AT LOCATIONS ACCORDING TO PLANS. VERIFED AT INSPECTION. ADDRESSED IN LETTER AND PLANS
Misc
Corrective Action Required
10/05/2015

REAR EXIT OFF OF THE WORSHIP CENTER AND THE K-CLASS ROOM. THE VESTIBULE DOES NOT SHOW EXIT SIGNAGE, EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING. ADDRESSED IN LETTER AND PLANS
Misc
Corrective Action Required
10/05/2015

SOUTHWEST EXIT OF WORSHIP CENTER DOES NOT SHOW EXTERIOR EGRESS LIGHTING ADDRESSED IN LETTER AND PLANS
Misc
Corrective Action Required
10/05/2015

LOBBY MAIN ENTRANCE, DOES NOT SHOW INTERIOR EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING. NIGHT LIGHTS DO NOT ACCOUNT FOR EMERGENCY LIGHTING. ADDRESSED IN LETTER
Misc
Corrective Action Required
10/05/2015

B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. INFORMATIONAL PURPOSES. ADDRESSED IN LETTER
Licensed Contractors Approved 10/05/2015 10/06/2015
Joe Frogge
LC - MEP Subs
Resolved
10/06/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
Sprinkler Plan Review Released for Construction 09/29/2015 09/29/2015
Joe Dir
Installation acceptance testing
Corrective Action Required
09/29/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. HYDROSTATIC PRESSURE TEST REQUIRED, ACCEPTANCE FLOW TEST REQUIRED. TO SCHEDULE TESTS CONTACT THE FIRE DEPARTMENT AT 818-969-1300
Building Plan Review Rejected 10/02/2015 09/28/2015
Joe Frogge
Misc
Corrective Action Required
09/28/2015

Additional information required. Action required: 1) Provide all construction information and details for raised platform including stairs, handrails, etc. 2) Specify exhaust fan for Family RR 102.
Bldg - Occupant load posting 1004.3
Corrective Action Required
09/28/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. Posting to be verified during inspections.
Misc
Corrective Action Required
09/28/2015

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at exterior side of exit discharges.
Misc
Corrective Action Required
09/28/2015

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Modify drawings to show additional exit signs at rear vestibule and at north door in corridor serving Pre-K Classrooms.
Mech - Outdoor air required 403.2
Corrective Action Required
09/28/2015

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Revise drawings to show outside air calculations as well as method of delivery.
Licensed Contractors Rejected 10/02/2015 09/25/2015
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/25/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
Fire Plan Review Rejected 10/02/2015 09/24/2015
Joe Dir
Misc
Corrective Action Required
09/24/2015

Posting of occupant load
Corrective Action Required
09/24/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOADS IN THE WORSHIP CENTER, KIDS CLASS ROOMS, NURSERY, MEETING ROOMS. VERIFIED AT INSPECTION
Construction documents for fire alarm systems
Corrective Action Required
09/24/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ENGINEERED SHOP DRAWINGS TO THE ALTERATIONS TO THE ALARM SYSTEM. INFORMATION PURPOSES
Address numbers required
Corrective Action Required
09/24/2015

2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF THE SUITE ON THE EXTERIOR OF ALL DOORS LEADING INTO THE SUITE. INFORMATION PURPOSES, VERIFIED AT INSPECTION.
Construction documents - Fire protection systems
Corrective Action Required
09/24/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE ENGINEERED SHOP DRAWINGS OF THE ALTERATIONS OF THE SPRINKLER SYSTEM. INFORMATION PURPOSES.
Installation acceptance testing
Corrective Action Required
09/24/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. TESTING REQUIRED FOR THE ALARM SYSTEM. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300. INFORMATION PURPOSES.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/24/2015

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE FIRE SPRINKLER SYSTEM SHALL BE CURRENT ON THE REQUIRED ANNUAL SERVICING OF THE SYSTEM. SERVICE TAG DISPLAYED ON THE RISER. INFORMATION PURPOSES, VERIFIED AT INSPECTION.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/24/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. PROVIDE 5 POUND FIRE EXTINGUISHERS, MOUNT AT LOCATIONS ACCORDING TO PLANS. VERIFED AT INSPECTION.
Misc
Corrective Action Required
09/24/2015

REAR EXIT OFF OF THE WORSHIP CENTER AND THE K-CLASS ROOM. THE VESTIBULE DOES NOT SHOW EXIT SIGNAGE, EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING.
Misc
Corrective Action Required
09/24/2015

SOUTHWEST EXIT OF WORSHIP CENTER DOES NOT SHOW EXTERIOR EGRESS LIGHTING
Misc
Corrective Action Required
09/24/2015

LOBBY MAIN ENTRANCE, DOES NOT SHOW INTERIOR EMERGENCY LIGHTING OR EXTERIOR EGRESS LIGHTING. NIGHT LIGHTS DO NOT ACCOUNT FOR EMERGENCY LIGHTING.
Misc
Corrective Action Required
09/24/2015

B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. B] 1006.2 Illumination level. The means of egress illumination level shall not be less than 1 footcandle (11 lux) at the walking surface. INFORMATIONAL PURPOSES.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,719.79 $1,719.79 Paid 10/13/2015
8331507-Sewer Connection Fee $360.00 $360.00 Paid 10/13/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 10/14/2015 at 12:00 AM 10/14/2015
In-wall Inspection Failed 10/16/2015 10/16/2015 at 12:00 AM 10/16/2015
Misc
Corrective Action Required
10/16/2015
-SECURE ALL MC WITHIN 12" OF BOXES -PROTECT PLUMBING IN RESTROOM WHERE INSTALLED WITHIN 1.5" OF STUD/PLATE SURFACE
In-wall Inspection Passed 10/19/2015 10/19/2015 at 12:00 AM 10/19/2015
Misc
Resolved
10/19/2015
-SECURE ALL MC WITHIN 12" OF BOXES -PROTECT PLUMBING IN RESTROOM WHERE INSTALLED WITHIN 1.5" OF STUD/PLATE SURFACE
Gas Service Inspection - Commercial Passed 10/29/2015 10/29/2015 at 12:00 AM 10/29/2015
Above Ceiling Inspection Failed 11/23/2015 at 12:00 AM 11/23/2015
Misc
Corrective Action Required
11/23/2015
-SHALL NOT USE GRID SUPPORT WIRES TO SUPPORT THE ELECTRICAL WIRING -MC WIRING SHALL BE SUPPORTED AT INTERVAL NO MORE THAN 6 FT. INDEPENDENT SUPPORT WIRES SHALL BE PROPERLY IDENTIFIED WITH TAGS OR COLOR AND SHALL BE SECURED AT BOTH UPPER AND LOWER ENDS -SHALL SECURE MC WIRINGS WITHIN 12" OF BOXES AND ENCLOSURES -OPEN BOXES IN CEILING SPACE -SUPPORT LOW VOLTAGE WIRING IN A NEAT AND WORKMANLIKE MANNER
Above Ceiling Inspection Failed 12/1/2015 12/1/2015 at 12:00 AM 12/01/2015
Misc
Corrective Action Required
11/23/2015
-MC WIRING SHALL BE SUPPORTED AT INTERVAL NO MORE THAN 6 FT. INDEPENDENT SUPPORT WIRES SHALL BE PROPERLY IDENTIFIED WITH TAGS OR COLOR AND SHALL BE SECURED AT BOTH UPPER AND LOWER ENDS -SHALL SECURE MC WIRINGS WITHIN 12" OF BOXES AND ENCLOSURES
Above Ceiling Inspection Passed 12/2/2015 at 12:00 AM 12/02/2015
Misc
Resolved
12/02/2015
-MC WIRING SHALL BE SUPPORTED AT INTERVAL NO MORE THAN 6 FT. INDEPENDENT SUPPORT WIRES SHALL BE PROPERLY IDENTIFIED WITH TAGS OR COLOR AND SHALL BE SECURED AT BOTH UPPER AND LOWER ENDS -SHALL SECURE MC WIRINGS WITHIN 12" OF BOXES AND ENCLOSURES
Electrical Service Inspection Failed 12/7/2015 12/7/2015 at 12:00 AM 12/07/2015
Misc
Corrective Action Required
12/07/2015
-HAVE THE APPROVED REVISED PLAN ON SITE -INSTALL #3 COPPER EGC FOR 400 AMP PARALLEL-CONDUCTOR CIRCUIT PER 250.122 -SECURE FMC PER CODE -INSTALL #2 COPPER CONDUCTOR FOR THE SYSTEM BONDING JUMPER, SUPPLY SIDE BONDING JUMPER, AND GROUNDING CONDUCTOR PER 250.66 BASED ON 3/0 SEPARATELY DERIVED SUPPLY CONDUCTOR -REMOVE ENAMEL AT BONDING CONNECTIONS -THE GROUNDING ELECTRODE CONDUCTOR FOR THE DERIVED SYSTEM SHALL CONNECT THE GROUNDED CONDUCTOR OF THE DERIVED SYSTEM TO THE GROUNDING ELECTRODE. 250.30(A)(5) -THE SYSTEM BONDING JUMPER SHALL CONNECT THE GROUNDED CONDUCTOR OF THE DERIVED SYSTEM TO THE SUPPLY SIDE BONDING JUMPER AND THE METAL ENCLOSURE. 250.30(A)(1)(a)
Electrical Service Inspection Passed 12/10/2015 12/10/2015 at 12:00 AM 12/10/2015
Misc
Resolved
12/10/2015
-HAVE THE APPROVED REVISED PLAN ON SITE -INSTALL #3 COPPER EGC FOR 400 AMP PARALLEL-CONDUCTOR CIRCUIT PER 250.122 -SECURE FMC PER CODE -INSTALL #2 COPPER CONDUCTOR FOR THE SYSTEM BONDING JUMPER, SUPPLY SIDE BONDING JUMPER, AND GROUNDING CONDUCTOR PER 250.66 BASED ON 3/0 SEPARATELY DERIVED SUPPLY CONDUCTOR -REMOVE ENAMEL AT BONDING CONNECTIONS -THE GROUNDING ELECTRODE CONDUCTOR FOR THE DERIVED SYSTEM SHALL CONNECT THE GROUNDED CONDUCTOR OF THE DERIVED SYSTEM TO THE GROUNDING ELECTRODE. 250.30(A)(5) -THE SYSTEM BONDING JUMPER SHALL CONNECT THE GROUNDED CONDUCTOR OF THE DERIVED SYSTEM TO THE SUPPLY SIDE BONDING JUMPER AND THE METAL ENCLOSURE. 250.30(A)(1)(a)
Alarm Test Passed 12/11/2015 at 12:00 AM 12/11/2015
Occupancy Inspection - Fire Passed 12/11/2015 at 12:00 AM 12/11/2015
Occupancy Inspection - Codes Commercial Full C of O 12/11/2015 12/11/2015 at 12:00 AM 12/11/2015
Misc
Resolved
12/11/2015
**FROM SERVICE INSPECTION: -INSTALL #2 COPPER CONDUCTOR FOR THE SYSTEM BONDING JUMPER, SUPPLY SIDE BONDING JUMPER, AND GROUNDING CONDUCTOR PER 250.66 BASED ON 3/0 SEPARATELY DERIVED SUPPLY CONDUCTOR -THE GROUNDING ELECTRODE CONDUCTOR FOR THE DERIVED SYSTEM SHALL CONNECT THE GROUNDED CONDUCTOR OF THE DERIVED SYSTEM TO THE GROUNDING ELECTRODE. 250.30(A)(5) -THE SYSTEM BONDING JUMPER SHALL CONNECT THE GROUNDED CONDUCTOR OF THE DERIVED SYSTEM TO THE SUPPLY SIDE BONDING JUMPER AND THE METAL ENCLOSURE. 250.30(A)(1)(a)
Documents & Images
Date Uploaded File Type Document Name
09/24/2015 Letter Fire Building Plan Review
09/28/2015 Letter Codes P/R Corrections Document
09/29/2015 Letter Fire (Sprinkler) Plan Review
10/08/2015 Letter Fire Building Plan Review
10/09/2015 Letter Codes P/R Corrections Document
10/13/2015 Letter Codes Plan Review Conditions
10/13/2015 Letter Codes Building Permit
10/13/2015 Receipt Receipt for transaction: 2015-005733
10/13/2015 Letter Fire (Alarm) Plan Review Notice
10/14/2015 Letter Inspection Summary
10/16/2015 Letter Inspection Summary
10/19/2015 Letter Inspection Summary
10/29/2015 Letter Inspection Summary
11/23/2015 Letter Inspection Summary
12/01/2015 Letter Inspection Summary
12/02/2015 Letter Inspection Summary
12/07/2015 Letter Inspection Summary
12/10/2015 Letter Inspection Summary
12/11/2015 Letter Field Certificate of Occupancy
12/14/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home