Permit Application Status

PRCOM20152126


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20152126
Building Permit - Commercial
Final Completion
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
NEW ELEVATOR
09/14/2015
11/02/2015
03/16/2016
03/09/2016
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
UNITED PLUMBING & SERVICE CO INC, Address:301 DUCK RD, Phone:(816) 761-5262  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 10/01/2015 10/30/2015
Mike Weisenborn
LC - MEP Subs
Resolved
10/30/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed Electrical and Plumbing contractors.
Building Plan Review Approved with Conditions 10/08/2015 10/05/2015
Joe Frogge
Project cost
Resolved
10/05/2015

The project cost, which is used to establish the permit fee, has not been provided. Action required: Provide project valuation.
Miscellaneous Correction
Resolved
10/05/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide details and UL #s for fire rated shaft and exterior walls. (our records show this to be a IIIB building) 10/5/15 - additional drawing added to cover fire rated assemblies
Miscellaneous Correction
Resolved
10/05/2015

Sump pit as designed by mechanical engineer does not match structural engineer's design. Action required: Resolve conflict and revise drawings accordingly. 10/5/15 - structural drawings updated to reflect sump pit
Elevator Certificate of Inspection
Corrective Action Required
10/01/2015

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated pursuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes.
Elevator Pit Ladder
Resolved
10/05/2015

ASME A17.1-2000 2.2.4.2 - There shall be installed in the pit of each elevator, where the pit extends more than 900 mm (35 in.) below the sill of the pit access door, a fixed vertical ladder of noncombustible material, located within reach of the access door. The ladder shall extend not less than 1,200 mm (48 in.) above Action required: Revise drawings to show design and location of ladder. 10/5/15 - ladder added to drawings
Elevator Equipment Permit
Corrective Action Required
10/01/2015

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes.
Elevator Equipment Inspection
Corrective Action Required
10/01/2015

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Action required: Comment is for informational purposes.
Misc 13
Resolved
10/05/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that receptacle within 6' of mop sink will by GFCI protected. 10/5/15 - drawing revised
Misc 14
Corrective Action Required
10/01/2015

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes.
Fire Plan Review Approved with Conditions 10/08/2015 10/02/2015
Joe Dir
Misc
Corrective Action Required
10/01/2015

PLANS DID NOT SHOW THE MECHANICAL ROOM FOR THE HOIST/LIFT SYSTEM. PLANS DID NOT MENTION WHAT TYPE OF HOIST SYSTEM WAS GOING TO BE INTSALLED, ELECTRIC OR HYDRAULIC.
Construction documents for fire alarm systems
Corrective Action Required
10/01/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE SHOP DRAWINGS FOR THE FIRE ALARM SYSTEM BEING INSTALLED FOR THE ELEVATOR.
Knox box required
Corrective Action Required
10/01/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX/KEY BOX FOR THE ELEVATOR KEYS. FOR AN APPLICATION CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Misc
Corrective Action Required
10/01/2015

BEFORE USE OF ELEVTOR A MISSOURI STATE INSPECTION SHALL BE PERFORMED AND PASSED. COPY OF THE CERIFICATION CERTIFICATE SHALL BE PROVIDED AT TIME OF THE OCCPANCY INSPECTION.
Misc
Corrective Action Required
10/01/2015

ELEVATOR SHALL BE CONSTRUCTED ACCORDING TO ALL STATE ELEVATOR CODES AND REQUIREMENTS . INFORMATION PURPOSES.
Misc
Corrective Action Required
10/01/2015

[B] 607.2 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. VERIFIED AT INSPECTION.
Misc
Corrective Action Required
10/01/2015

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. SEE KNOX BOX COMMENT
Building Plan Review Rejected 09/24/2015 09/18/2015
Joe Frogge
Project cost
Corrective Action Required
09/18/2015

The project cost, which is used to establish the permit fee, has not been provided. Action required: Provide project valuation.
Miscellaneous Correction
Corrective Action Required
09/18/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide details and UL #s for fire rated shaft and exterior walls. (our records show this to be a IIIB building)
Miscellaneous Correction
Corrective Action Required
09/18/2015

Sump pit as designed by mechanical engineer does not match structural engineer's design. Action required: Resolve conflict and revise drawings accordingly.
Elevator Certificate of Inspection
Corrective Action Required
09/18/2015

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated pursuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes.
Elevator Pit Ladder
Corrective Action Required
09/18/2015

ASME A17.1-2000 2.2.4.2 - There shall be installed in the pit of each elevator, where the pit extends more than 900 mm (35 in.) below the sill of the pit access door, a fixed vertical ladder of noncombustible material, located within reach of the access door. The ladder shall extend not less than 1,200 mm (48 in.) above Action required: Revise drawings to show design and location of ladder.
Elevator Equipment Permit
Corrective Action Required
09/18/2015

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes.
Elevator Equipment Inspection
Corrective Action Required
09/18/2015

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Action required: Comment is for informational purposes.
Misc 13
Corrective Action Required
09/18/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that receptacle within 6' of mop sink will by GFCI protected.
Misc 14
Corrective Action Required
09/18/2015

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes.
Licensed Contractors Rejected 09/24/2015 09/18/2015
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/18/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed Electrical and Plumbing contractors.
Fire Plan Review Approved with Conditions 09/24/2015 09/18/2015
Joe Dir
Misc
Corrective Action Required
09/18/2015

PLANS DID NOT SHOW THE MECHANICAL ROOM FOR THE HOIST/LIFT SYSTEM. PLANS DID NOT MENTION WHAT TYPE OF HOIST SYSTEM WAS GOING TO BE INTSALLED, ELECTRIC OR HYDRAULIC.
Construction documents for fire alarm systems
Corrective Action Required
09/18/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE SHOP DRAWINGS FOR THE FIRE ALARM SYSTEM BEING INSTALLED FOR THE ELEVATOR.
Knox box required
Corrective Action Required
09/18/2015

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX/KEY BOX FOR THE ELEVATOR KEYS. FOR AN APPLICATION CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Misc
Corrective Action Required
09/18/2015

BEFORE USE OF ELEVTOR A MISSOURI STATE INSPECTION SHALL BE PERFORMED AND PASSED. COPY OF THE CERIFICATION CERTIFICATE SHALL BE PROVIDED AT TIME OF THE OCCPANCY INSPECTION.
Misc
Corrective Action Required
09/18/2015

ELEVATOR SHALL BE CONSTRUCTED ACCORDING TO ALL STATE ELEVATOR CODES AND REQUIREMENTS . INFORMATION PURPOSES.
Misc
Corrective Action Required
09/18/2015

[B] 607.2 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. VERIFIED AT INSPECTION.
Misc
Corrective Action Required
09/18/2015

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. SEE KNOX BOX COMMENT
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $441.26 $441.26 Paid 11/02/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 11/25/2015 at 12:00 AM 11/25/2015
Foundation Inspection - Commercial Passed 12/1/2015 at 12:00 AM 12/01/2015
All Rough Inspection - Commercial Partial 2/22/2016 2/22/2016 02/22/2016
Rated Assembly Inspection Not Ready 2/24/2016 2/24/2016 02/24/2016
Rated Assembly Inspection Not Ready 2/25/2016 2/25/2016 02/25/2016
Rated Assembly Inspection Partial 2/26/2016 02/26/2016
Misc
Partial Correction
02/26/2016
RATED LID AT ELEVATOR SHAFT: 1ST LAYER 5/8" TYPE X GWB;
Misc
Partial Correction
02/26/2016
ELEVATOR DOOR FRONTS: AT 1ST FLOOR 1 LAYER 5/8" TYPE X GWB SCREWED @ 8" O/C;
Rated Assembly Inspection Partial 2/29/2016 02/29/2016
Misc
Partial Correction
02/26/2016
RATED LID AT ELEVATOR SHAFT: 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-STOP
Misc
Partial Correction
02/26/2016
ELEVATOR DOOR FRONTS: AT 1ST FLOOR 1 LAYER 5/8" TYPE X GWB SCREWED @ 8" O/C;
Rated Assembly Inspection Failed 3/1/2016 3/1/2016 03/01/2016
Misc
Corrective Action Required
03/01/2016
RATED LID AT ELEVATOR SHAFT: 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-STOP. TAPE DOES NOT ADHERE TO CMU. USE FIRE-CAULK AT PERIMETER.
Misc
Partial Correction
02/29/2016
ELEVATOR DOOR FRONTS: AT 1ST FLOOR 1 LAYER 5/8" TYPE X GWB SCREWED @ 8" O/C;
Rated Assembly Inspection Passed 3/3/2016 03/03/2016
Misc
Resolved
03/03/2016
RATED LID AT ELEVATOR SHAFT: 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-STOP. TAPE DOES NOT ADHERE TO CMU. USE FIRE-CAULK AT PERIMETER.
Misc
Partial Correction
03/01/2016
ELEVATOR DOOR FRONTS: AT 1ST FLOOR 1 LAYER 5/8" TYPE X GWB SCREWED @ 8" O/C;
Above Ceiling Inspection Failed 3/4/2016 03/04/2016
Misc
Corrective Action Required
03/04/2016
INSTALL LIGHT FIXTURES @ 1ST & 2ND FLOORS
Misc
Corrective Action Required
03/04/2016
SECURE MC CABLES WITHIN 12" OF ENTRY TO BOXES
Misc
Corrective Action Required
03/04/2016
CLOSE ELECTRICAL BOXES
Above Ceiling Inspection Partial 3/8/2016 3/8/2016 03/08/2016
Misc
Corrective Action Required
03/04/2016
AT 1ST FLOOR INSTALL TWO SLACK WIRES ON LAY-IN LIGHT FIXTURE. CALL FOR RE-INSPECTION. OK TO COVER WHEN READY CEILING AT 2ND FLOOR. AFFIX PERMANENT SIGN ON WALL BELOW CEILING INDICATING ELEVATOR DISCONNECT SWITCH IS ABOVE CEILING.
Misc
Resolved
03/08/2016
SECURE MC CABLES WITHIN 12" OF ENTRY TO BOXES
Misc
Resolved
03/08/2016
CLOSE ELECTRICAL BOXES
Above Ceiling Inspection Passed 3/9/2016 3/9/2016 03/09/2016
Misc
Resolved
03/09/2016
AT 1ST FLOOR INSTALL TWO SLACK WIRES ON LAY-IN LIGHT FIXTURE. CALL FOR RE-INSPECTION. OK TO COVER WHEN READY CEILING AT 2ND FLOOR. AFFIX PERMANENT SIGN ON WALL BELOW CEILING INDICATING ELEVATOR DISCONNECT SWITCH IS ABOVE CEILING.
All Rough Inspection - Commercial Passed 3/2/2016 2/22/2016 03/09/2016
Occupancy Inspection - Fire Passed 03/09/2016
Final Inspection - Commercial Passed 3/9/2016 3/9/2016 03/09/2016
Documents & Images
Date Uploaded File Type Document Name
09/18/2015 Letter Fire Building Plan Review
09/18/2015 Letter Codes P/R Corrections Document
09/18/2015 Letter Codes P/R Corrections Document
10/02/2015 Letter Fire Building Plan Review
11/02/2015 Receipt Receipt for transaction: 2015-005996
11/02/2015 Letter Codes Plan Review Conditions
11/02/2015 Letter Codes Building Permit
11/25/2015 Letter Inspection Summary
12/01/2015 Letter Inspection Summary
02/26/2016 Letter Inspection Summary
02/29/2016 Letter Inspection Summary
03/01/2016 Letter Inspection Summary
03/03/2016 Letter Inspection Summary
03/04/2016 Letter Inspection Summary
03/08/2016 Letter Inspection Summary
03/09/2016 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home