Permit Application Status

PRCOM20152121


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20152121
Building Permit - Commercial
Final Completion
MAR ARBORWALK LLC
NEW OTHER (COMMERCIAL)
NEW STORAGE BUILDING
09/11/2015
10/19/2015
03/01/2016
Locations
Contacts
MAR ARBORWALK LLC, Address:5429 LBJ FREEWAY STE 800  
STOKED OUT SERVICES, Address:777 RIDING CLUB RD, Phone:(972) 771-3789  
PRO ELECTRIC LC, Address:510 MIAMI AVE, Phone:(913) 621-6611  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 12/15/2015 10/19/2015
Joe Frogge
FDP #PL2015138
Fire Plan Review Approved with Conditions 09/24/2015 09/15/2015
Joe Dir
Misc
Corrective Action Required
09/15/2015

PLANS STATED THAT THE STRUCTURE WAS GOING TO BE A STORAGE BUILDING. WHAT ARE CONTENTS BEING STORED. ANY FUELS, HAZ MAT ITEMS WILL NEED FURTHER CONSIDERATIONS ANF REQUIREMENTS.
Address numbers required
Corrective Action Required
09/15/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1318 ON THE BUILDING READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
Portable fire extinguishers - general
Corrective Action Required
09/15/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE ONE 2A-10BC FIRE EXTINGUISHER. VERIFIED AT INSPECTION
Building Plan Review Approved with Conditions 09/24/2015 09/15/2015
Joe Frogge
Final Development Plan
Resolved
10/19/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Bldg - Attic access 1209.2
Corrective Action Required
09/15/2015

2012 IBC 1209.2 – Attic spaces. An opening not less than 20 inches by 30 inches shall be provided to any attic area having a clear height of over 30 inches. Clear headroom of not less than 30 inches shall be provided in the attic space at or above the access opening. Action required: Provide means of attic access. This can be field verified.
Misc
Corrective Action Required
09/15/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: All receptacles in storage building to be GFCI protected. This may be verified in field.
Misc
Corrective Action Required
09/15/2015

2012 IBC 2308.9 Wall Framing. Walls and partitions shall be constructed in accordance with the applicable provisions of Sections 2308.9.1 through 2308.9.4.2. Action required: Brace wall provisions will apply to this building. Exterior sheathing and nail patterns to be inspected in field.
Licensed Contractors Approved 09/25/2015 09/14/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $180.32 $180.32 Paid 10/19/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Foundation Inspection - Commercial Passed 10/29/2015 (8:00) 10/29/2015 at 12:00 AM 10/29/2015
All Rough Inspection - Commercial Partial 11/10/2015 at 12:00 AM 11/10/2015
Misc
Corrective Action Required
11/10/2015
FRAMING INSPECTION ELECTRICAL ROUGH INSPECTION OK TO ROCK -EXCEPT AT UFFER GROUND AND AT PANEL FOR INSPECTION OF SE CABLE. PANEL NOT INSPECTED
All Rough Inspection - Commercial Failed 12/17/2015
Misc
Corrective Action Required
11/10/2015
FRAMING INSPECTION ELECTRICAL ROUGH INSPECTION OK TO ROCK -EXCEPT AT UFFER GROUND AND AT PANEL FOR INSPECTION OF SE CABLE. isolate nuetrals and ground and install uffer ground from grounding bus bar to uffer
Final Inspection - Commercial Failed 12/17/2015 12/17/2015 12/17/2015
Misc
Corrective Action Required
12/17/2015
install uffer ground and isolate nuetrals and grounds at panel. install fire extinguisher per FD\recall when complete
Occupancy Inspection - Fire Failed 12/17/2015 12/17/2015
Occupancy Inspection - Fire Passed 12/29/2015 12/29/2015
Final Inspection - Commercial Failed 12/29/2015 12/29/2015 12/29/2015
Misc
Corrective Action Required
12/17/2015
install uffer ground and isolate neutrals and grounds at panel. recall when complete Install final grade and sod, remove basketball goal from yard. per Planning dept. Fire ok
Occupancy Inspection - Planning Temporary C of O 12/30/2015 12/29/2015
Corrective Action Required
12/29/2015
The dismanteled basketball goals shall be removed from the site.
Corrective Action Required
12/29/2015
All tire ruts shall be repaired and all areas disturbed by construction shall be sodded. Deadline extended until April 1, 2016 due to inclement weather.
Final Inspection - Commercial Partial 12/31/2015 12/30/2015 12/30/2015
Misc
Corrective Action Required
12/29/2015
Install final grade and sod, remove basketball goal from yard. per Planning dept. ok pending planning approval.
All Rough Inspection - Commercial Passed 12/30/2015
Misc
Resolved
12/30/2015
FRAMING INSPECTION ELECTRICAL ROUGH INSPECTION OK TO ROCK -EXCEPT AT UFFER GROUND AND AT PANEL FOR INSPECTION OF SE CABLE. isolate nuetrals and ground and install uffer ground from grounding bus bar to uffer
Electrical Service Inspection Passed 12/30/2015
Underground Electrical Inspection - Commercial Passed 12/30/2015
Final Inspection - Commercial Passed 3/1/2016 3/1/2016 03/01/2016
Misc
Resolved
03/01/2016
Install final grade and sod, remove basketball goal from yard. per Planning dept. ok pending planning approval.
Documents & Images
Date Uploaded File Type Document Name
09/15/2015 Letter Fire Building Plan Review
10/19/2015 Letter Codes Building Permit
10/19/2015 Letter Codes Plan Review Conditions
10/19/2015 Receipt Receipt for transaction: 2015-005818
10/29/2015 Letter Inspection Summary
11/10/2015 Letter Inspection Summary
12/17/2015 Letter Inspection Summary
12/29/2015 Letter Inspection Summary
12/29/2015 Letter Planning Inspection Summary
12/30/2015 Letter Inspection Summary
03/01/2016 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home