Permit Application Status

PRCOM20151943


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151943
Building Permit - Commercial
Certificate of Occupancy
ROCKY TOP HOLDINGS LLC
NEW TENANT FINISH
TENANT FINISH FOR NEW FITNESS CENTER
08/21/2015
10/27/2015
02/29/2016
07/15/2016
Locations
Contacts
SCHARHAG ARCHITECTS, Address:310 ARMOR RD, #22, Phone:(816) 221-9297  
PHOENIX CONSTRUCTION INC, Address:1305 HOLLY CT, Phone:(816) 716-8208  
BRADLEY-READE INC, Address:810 W 7TH AVE, Phone:(816) 898-2947  
ROCKY TOP HOLDINGS LLC, Address:244 W MILL ST STE 101  
ALWAYS PLUMBING LLC, Address:807 NASHUA ROAD, Phone:(819) 781-7749  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 10/01/2015 09/28/2015
Joe Frogge
License Tax Application
Corrective Action Required
09/24/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Occupant load posting 1004.3
Corrective Action Required
09/24/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Occupant load posting required. To be field verified during inspections.
Misc
Corrective Action Required
09/24/2015

[B] 1011.5 Internally illuminated exit signs. Electrically powered, self-luminous and photoluminescent exit signs shall be listed and labeled in accordance with UL 924 and shall be installed in accordance with the manufacturer’s instructions and Chapter 27 of the International Building Code. Exit signs shall be illuminated at all times. [B] 1011.6 Externally illuminated exit signs. Externally illuminated exit signs shall comply with Sections 1011.6.1 through 1011.6.3. [B] 1011.6.1 Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 3/4 inch (19.1 mm) wide. The word “EXIT” shall have letters having a width not less than 2 inches (51 mm) wide, except the letter “I,” and the minimum spacing between letters shall not be less than 3/8 inch (9.5 mm). Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height. The word “EXIT” shall be in high contrast with the background and shall be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit sign, the construction shall be such that the direction of the chevron directional indicator cannot be readily changed. [B] 1011.6.2 Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 footcandles (54 lux). [B] 1011.6.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604. drawings did not indicate exit signs or emergency lighting in the suite. provide exit signs and emergency lighting as needed. Verified at inspection.
Posting of occupant load
Corrective Action Required
09/24/2015

2012IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Post the occipant load of 87 as per plans. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
09/24/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for any alterations to the alarm system. Extend alarm system devices into the suite as needed. Information purposes
Address numbers required
Corrective Action Required
09/24/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Post the numeric address of the suite on the exterior of any door front or rear that leads into the suite. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
09/24/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for any alterations done to the sprinkler system
Installation acceptance testing
Corrective Action Required
09/24/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Testing required for any alterations done to the alarm asystem. To schedule a test contact the fire department 816-969-1300.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/24/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Provide a 2A-10BC (5 pound) fire extinguisher for every 6000 sq ft. Information purposes
Misc
Corrective Action Required
09/24/2015

906.5 Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Travel distance shall not exceed 75' from anywhere within the suite. Verified at inspection.
Licensed Contractors Approved 09/09/2015 09/18/2015
Joe Frogge
LC - General Contractor
Resolved
09/14/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
09/18/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 09/16/2015 09/14/2015
Joe Frogge
License Tax Application
Corrective Action Required
09/09/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Code analysis required
Resolved
09/14/2015

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis to show that occupancy is A3 (gymnasium).
Bldg - Occupant load posting 1004.3
Corrective Action Required
09/09/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Occupant load posting required. To be field verified during inspections.
Misc
Resolved
09/14/2015

Inadequate information to complete review. Action rquired: Provide the following: - Identify use of all spaces - Designate what work is new vs. existing. - Clarify plumbing scope (fixtures all designated as existing but a new waste pipe is installed?) - Show exit lighting.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
09/14/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Rear door near restrooms required to have minimum 12" clearance at latch side if a closer is installed.
Fire Plan Review Approved with Conditions 09/16/2015 09/11/2015
Joe Dir
Misc
Corrective Action Required
09/09/2015

[B] 1011.5 Internally illuminated exit signs. Electrically powered, self-luminous and photoluminescent exit signs shall be listed and labeled in accordance with UL 924 and shall be installed in accordance with the manufacturer’s instructions and Chapter 27 of the International Building Code. Exit signs shall be illuminated at all times. [B] 1011.6 Externally illuminated exit signs. Externally illuminated exit signs shall comply with Sections 1011.6.1 through 1011.6.3. [B] 1011.6.1 Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 3/4 inch (19.1 mm) wide. The word “EXIT” shall have letters having a width not less than 2 inches (51 mm) wide, except the letter “I,” and the minimum spacing between letters shall not be less than 3/8 inch (9.5 mm). Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height. The word “EXIT” shall be in high contrast with the background and shall be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit sign, the construction shall be such that the direction of the chevron directional indicator cannot be readily changed. [B] 1011.6.2 Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 footcandles (54 lux). [B] 1011.6.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604. drawings did not indicate exit signs or emergency lighting in the suite. provide exit signs and emergency lighting as needed. Verified at inspection.
Posting of occupant load
Corrective Action Required
09/09/2015

2012IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Post the occipant load of 87 as per plans. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
09/09/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for any alterations to the alarm system. Extend alarm system devices into the suite as needed. Information purposes
Address numbers required
Corrective Action Required
09/09/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Post the numeric address of the suite on the exterior of any door front or rear that leads into the suite. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
09/09/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for any alterations done to the sprinkler system
Installation acceptance testing
Corrective Action Required
09/09/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Testing required for any alterations done to the alarm asystem. To schedule a test contact the fire department 816-969-1300.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/09/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Provide a 2A-10BC (5 pound) fire extinguisher for every 6000 sq ft. Information purposes
Misc
Corrective Action Required
09/09/2015

906.5 Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Travel distance shall not exceed 75' from anywhere within the suite. Verified at inspection.
Building Plan Review Rejected 09/02/2015 09/02/2015
Joe Frogge
License Tax Application
Corrective Action Required
09/02/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Code analysis required
Corrective Action Required
09/02/2015

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis to show that occupancy is A3 (gymnasium).
Bldg - Occupant load posting 1004.3
Corrective Action Required
09/02/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Occupant load posting required. To be field verified during inspections.
Misc
Corrective Action Required
09/02/2015

Inadequate information to complete review. Action rquired: Provide the following: - Identify use of all spaces - Designate what work is new vs. existing. - Clarify plumbing scope (fixtures all designated as existing but a new waste pipe is installed?) - Show exit lighting.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
09/02/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Rear door near restrooms required to have minimum 12" clearance at latch side if a closer is installed.
Licensed Contractors Rejected 09/02/2015 09/02/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
09/02/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
09/02/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 09/02/2015 08/25/2015
Joe Dir
Misc
Corrective Action Required
08/25/2015

[B] 1011.5 Internally illuminated exit signs. Electrically powered, self-luminous and photoluminescent exit signs shall be listed and labeled in accordance with UL 924 and shall be installed in accordance with the manufacturer’s instructions and Chapter 27 of the International Building Code. Exit signs shall be illuminated at all times. [B] 1011.6 Externally illuminated exit signs. Externally illuminated exit signs shall comply with Sections 1011.6.1 through 1011.6.3. [B] 1011.6.1 Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 3/4 inch (19.1 mm) wide. The word “EXIT” shall have letters having a width not less than 2 inches (51 mm) wide, except the letter “I,” and the minimum spacing between letters shall not be less than 3/8 inch (9.5 mm). Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height. The word “EXIT” shall be in high contrast with the background and shall be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit sign, the construction shall be such that the direction of the chevron directional indicator cannot be readily changed. [B] 1011.6.2 Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 footcandles (54 lux). [B] 1011.6.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604. drawings did not indicate exit signs or emergency lighting in the suite. provide exit signs and emergency lighting as needed. Verified at inspection.
Posting of occupant load
Corrective Action Required
08/25/2015

2012IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Post the occipant load of 87 as per plans. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
08/25/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for any alterations to the alarm system. Extend alarm system devices into the suite as needed. Information purposes
Address numbers required
Corrective Action Required
08/25/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Post the numeric address of the suite on the exterior of any door front or rear that leads into the suite. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
08/25/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for any alterations done to the sprinkler system
Installation acceptance testing
Corrective Action Required
08/25/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Testing required for any alterations done to the alarm asystem. To schedule a test contact the fire department 816-969-1300.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/25/2015

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Provide a 2A-10BC (5 pound) fire extinguisher for every 3000 sq ft. Information purposes
Misc
Corrective Action Required
08/25/2015

906.5 Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Travel distance shall not exceed 75' from anywhere within the suite. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $36.05 $36.05 Paid 10/27/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 11/4/2015 at 12:00 AM 11/04/2015
In-wall Inspection Passed 06/17/2016
Occupancy Inspection - Codes Commercial Temporary C of O 6/17/2016 6/17/2016 06/17/2016
Misc
Corrective Action Required
06/17/2016
-INSTALL FIRE EXTINGUISHERS PER IFC -RELABEL GAS SERVICE FOR UNIT 128 (FOR BOTH METERS SERVING THE 2 RTUs FOR UNIT 128)
Occupancy Inspection - Fire Passed 6/17/2016 06/17/2016
Occupancy Inspection - Codes Commercial Full C of O 7/15/2016 07/15/2016
Misc
Resolved
07/15/2016
-INSTALL FIRE EXTINGUISHERS PER IFC -RELABEL GAS SERVICE FOR UNIT 128 (FOR BOTH METERS SERVING THE 2 RTUs FOR UNIT 128)
Documents & Images
Date Uploaded File Type Document Name
08/25/2015 Letter Fire Building Plan Review
09/02/2015 Letter Codes P/R Corrections Document
09/11/2015 Letter Fire Building Plan Review
09/18/2015 Letter Codes Plan Review Conditions
09/25/2015 Letter Fire Building Plan Review
10/27/2015 Letter Codes Building Permit
10/27/2015 Receipt Receipt for transaction: 2015-005925
11/04/2015 Letter Inspection Summary
03/28/2016 Letter Codes 140 Day Letter
06/17/2016 Letter Codes Temporary Certificate of Occupancy
07/15/2016 Letter Field Certificate of Occupancy
07/18/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home