Permit Application Status

PRCOM20151648


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151648
Building Permit - Commercial
Final Completion
RAVID LEE SUMMIT LLC
ALTERATION COMMERCIAL
RELOCATE WALL - REDUCE SIZE OF STORAGE AREAS, INCREASE SIZE OF OPEN AREA - SOME ELECTRICAL - NO NEW MANI-PEDI-CHAIRS TO BE ADDED
07/22/2015
07/27/2015
09/01/2015
Locations
Contacts
GILL SOLUTIONS LLC, Address:7607 PHEASANT COURT, Phone:(816) 896-2462  
KASA ELECTRIC LLC, Address:1206 NW VALLEY RIDGE DR, Phone:(816) 228-4886  
RAVID LEE SUMMIT LLC, Address:1901 HARRISON ST FL 2ND  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2015
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2015
Joe Dir
Fire Plan Review Approved 08/03/2015 07/27/2015
Joe Dir
Misc
Corrective Action Required
07/27/2015

No FD Comments
Building Plan Review Approved 08/03/2015 07/22/2015
Joe Frogge
Licensed Contractors Approved 08/03/2015 07/22/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 07/27/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 7/29/2015 at 12:00 AM 07/29/2015
Misc
Corrective Action Required
07/29/2015
METTALIC ELECTRICAL BOXES NOT FOUND TO BE GROUNDED
Misc
Corrective Action Required
07/29/2015
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES.
Misc
Corrective Action Required
07/29/2015
BULKHEAD AT REAR NOT EXPOSED FOR INSPECTION
In-wall Inspection Passed 7/31/2015 at 12:00 AM 07/31/2015
Misc
Resolved
07/31/2015
METTALIC ELECTRICAL BOXES NOT FOUND TO BE GROUNDED
Misc
Resolved
07/31/2015
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES.
Misc
Resolved
07/31/2015
BULKHEAD AT REAR NOT EXPOSED FOR INSPECTION
Occupancy Inspection - Fire Passed 7/31/2015 at 12:00 AM 07/31/2015
Above Ceiling Inspection Passed 08/03/2015
Final Inspection - Commercial Partial 8/3/2015 at 12:00 AM 08/03/2015
Misc
Partial Correction
08/03/2015
OK TO RE-OPEN BUSINESS. RE-PLUMBING OF PEDICURE CHAIRS SUBJECT TO APPROVAL WHEN COMPLETED.
Final Inspection - Commercial Passed 9/1/2015 9/1/2015 at 12:00 AM 09/01/2015
Misc
Resolved
09/01/2015
OK TO RE-OPEN BUSINESS. RE-PLUMBING OF PEDICURE CHAIRS SUBJECT TO APPROVAL WHEN COMPLETED.
Documents & Images
Date Uploaded File Type Document Name
07/27/2015 Letter Fire Building Plan Review
07/27/2015 Receipt Receipt for transaction: 2015-004384
07/27/2015 Letter Codes Building Permit
07/29/2015 Letter Inspection Summary
07/31/2015 Letter Inspection Summary
08/03/2015 Letter Inspection Summary
09/01/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home