Permit Application Status

PRCOM20151616


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151616
Building Permit - Commercial
Certificate of Occupancy
LBC INVESTMENTS LLC
CHANGE OF TENANT
INTERIOR ALTERATIONS FOR CHANGE OF TENANT FOR WHOLESALE HVAC PARTS - SERVED BY EXISTING WAREHOUSE *drawings are in plan review file
07/20/2015
07/28/2015
11/06/2015
Locations
Contacts
RIVER OAK CONSTRUCTION INC, Address:3810 NE BEECHWOOD DR, Phone:(816) 525-2100  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
INTEGRITY PLUMBING SERVICES LLC, Address:405 SW Nelson Dr., Phone:(816) 803-9032  
HIRST & ASSOCIATES P.C., Address:621 NE WOODS CHAPEL RD , Phone:(816) 525-2100  
LBC INVESTMENTS LLC, Address:PO BOX 7258  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 07/30/2015 07/31/2015
Jim Eden
Misc
Corrective Action Required
07/28/2015

What type of product does the company sell, and how will it be stored in the warehouse? Submit a rack storage plan if that is how product will be stored. Jily 31, 2015. A rack layout plan was provided. The following information is needed. 3201.3 Construction documents. At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. Following approval of the plans, a copy of the approved plans shall be maintained on the premises in an approved location. The plans shall include the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Usable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 3203. 8. Location of commodities which are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers. 12. Type, location and specifications of smoke removal and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area shall be provided at the time of permit, when required by the fire code official.
Misc
Corrective Action Required
07/28/2015

IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Existing systems shall have documentation of a current annual inspection. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
07/28/2015

IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. One fire extinguisher in the front office will be fine.
Construction documents - Fire protection systems
Corrective Action Required
07/28/2015

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for modification of fire sprinkler coverage.
Construction documents for fire alarm systems
Corrective Action Required
07/28/2015

IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit plans for relocated alarm notification appliances.
DE Corps of Engineers
Corrective Action Required
07/28/2015

Provide an exit light over the front door unless alaready existing.
Licensed Contractors Approved 07/30/2015 07/28/2015
Development Center
LC - General Contractor
Corrective Action Required
07/28/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Building Plan Review Approved 07/30/2015 07/28/2015
Joe Frogge
Plumb - Minimum number of fixtures 403.1
Resolved
07/28/2015

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Per my calculations an additional accessible water closet and lavatory are required. Modify documents.
Misc
Resolved
07/28/2015

2012 IPC 403.2 Separate Facilities. (As amended by Lee’s Summit Code of Ordinances Section 7-405) Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 1. Separate facilities shall not be required for dwelling units and sleeping units. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 25 or fewer. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer. Action required: Per my calculations an additional accessible water closet and lavatory are required. Modify documents.
Fire Plan Review Approved with Conditions 07/30/2015 07/23/2015
Jim Eden
DE Corps of Engineers
Corrective Action Required
07/23/2015

Provide an exit light over the front door unless alaready existing.
Construction documents for fire alarm systems
Corrective Action Required
07/23/2015

IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit plans for relocated alarm notification appliances.
Construction documents - Fire protection systems
Corrective Action Required
07/23/2015

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for modification of fire sprinkler coverage.
Portable fire extinguishers - general
Corrective Action Required
07/23/2015

IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. One fire extinguisher in the front office will be fine.
Misc
Corrective Action Required
07/23/2015

IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Existing systems shall have documentation of a current annual inspection. Verified at inspection.
Misc
Corrective Action Required
07/23/2015

What type of product does the company sell, and how will it be stored in the warehouse? Submit a rack storage plan if that is how product will be stored.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $285.95 $285.95 Paid 07/28/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 8/18/2015 at 12:00 AM 08/18/2015
Misc
Corrective Action Required
08/18/2015
-PROTECT PLUMBING AT FORMER LOCATION OF DRINKING FOUNTAIN -COMPLETE ELECTRICAL TO BREAK ROOM AND RELOCATED DRINKING FOUNTAIN
In-wall Inspection Passed 8/20/2015 8/20/2015 at 12:00 AM 08/20/2015
Misc
Resolved
08/20/2015
-PROTECT PLUMBING AT FORMER LOCATION OF DRINKING FOUNTAIN -COMPLETE ELECTRICAL TO BREAK ROOM AND RELOCATED DRINKING FOUNTAIN
Above Ceiling Inspection Passed 9/10/2015 9/10/2015 at 12:00 AM 09/10/2015
Occupancy Inspection - Codes Commercial Temporary C of O 10/13/2015 10/13/2015 at 12:00 AM 10/13/2015
Misc
Corrective Action Required
10/13/2015
-OBTAIN FIRE DEPT APPROVAL -POST NO SMOKING SIGN AT FRONT DOOR -COMPLETE RESTROOM
Occupancy Inspection - Fire Passed 10/13/2015 10/13/2015 at 12:00 AM 10/13/2015
Occupancy Inspection - Codes Commercial Failed 11/6/2015 11/6/2015 at 12:00 AM 11/06/2015
Misc
Corrective Action Required
10/13/2015
-COMPLETE RESTROOM **THE ELECTRICAL BOX CANNOT BE RECESSED MORE THAN 1/4" BEHIND THE NON-COMBUSTIBLE WALL FINISH **THE BATH SIGN MUST BE ON THE WALL ON THE LATCH SIDE OF THE DOOR
Occupancy Inspection - Codes Commercial Full C of O 11/6/2015 at 12:00 AM 11/06/2015
Misc
Resolved
11/06/2015
-COMPLETE RESTROOM **THE ELECTRICAL BOX CANNOT BE RECESSED MORE THAN 1/4" BEHIND THE NON-COMBUSTIBLE WALL FINISH **THE BATH SIGN MUST BE ON THE WALL ON THE LATCH SIDE OF THE DOOR
Documents & Images
Date Uploaded File Type Document Name
07/28/2015 Letter Codes P/R Corrections Document
07/28/2015 Letter Codes Plan Review Conditions
07/28/2015 Letter Codes Building Permit
07/28/2015 Receipt Receipt for transaction: 2015-004418
08/18/2015 Letter Inspection Summary
08/20/2015 Letter Inspection Summary
09/10/2015 Letter Inspection Summary
10/13/2015 Letter Codes Temporary Certificate of Occupancy
11/06/2015 Letter Inspection Summary
11/06/2015 Letter Field Certificate of Occupancy
11/11/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home