Permit Application Status

PRCOM20151580


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151580
Building Permit - Commercial
Final Completion
MIDWEST DIVISION LSH LLC
NEW OTHER (COMMERCIAL)
ELECTRIC CAR CHARGING STATIONS
07/16/2015
08/26/2015
01/17/2016
10/12/2015
Locations
Contacts
MARK ONE ELECTRIC CO INC, Address:1414 GENESSEE ST, Phone:(816) 842-7023  
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 08/05/2015 08/05/2015
Joe Frogge
Building Plan Review Approved 08/12/2015 08/05/2015
Joe Frogge
Misc
Resolved
08/05/2015

The charging station location is ok, but the mid span 25kVA OH TX pole appears to be too close to a 20” and a 12” water line. They will need to locate this pole a minimum of ten (10) feet from any of these water lines. Action required: propose alternate location or verify (via official locate) that current location is compliant. Contact Gene Williams with questions - 816.969.1800.
Building Plan Review Rejected 07/30/2015 07/21/2015
Joe Frogge
Misc
Resolved
08/05/2015

The charging station location is ok, but the mid span 25kVA OH TX pole appears to be too close to a 20” and a 12” water line. They will need to locate this pole a minimum of ten (10) feet from any of these water lines. Action required: propose alternate location or verify (via official locate) that current location is compliant. Contact Gene Williams with questions - 816.969.1800.
Public Works Review Rejected 07/30/2015 07/21/2015
Joe Frogge
Misc
Corrective Action Required
07/21/2015

The charging station location is ok, but the mid span 25kVA OH TX pole appears to be too close to a 20” and a 12” water line. They will need to locate this pole a minimum of ten (10) feet from any of these water lines. Action required: propose alternate location or verify (via official locate) that current location is compliant. Contact Gene Williams with questions - 816.969.1800.
Licensed Contractors Approved 07/30/2015 07/16/2015
Development Center
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $36.74 $36.74 Paid 08/26/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Not Ready 10/12/2015 10/12/2015 at 12:00 AM 10/12/2015
Final Electrical Inspection - Commercial Passed 10/12/2015 10/12/2015 at 12:00 AM 10/12/2015
Documents & Images
Date Uploaded File Type Document Name
07/21/2015 Letter Codes P/R Corrections Document
08/26/2015 Receipt Receipt for transaction: 2015-005044
08/26/2015 Letter Codes Building Permit
10/12/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide: