Permit Application Status

PRCOM20151251


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20151251
Building Permit - Commercial
Certificate of Occupancy
SARAH PEPPER ENTERPRISES LLC
CHANGE OF TENANT
OFFICE SPACE FOR MEDICAL CONSULTING BUSINESS MEDICAL RECORDS STORED ON SITE LOCK BOX: 5224 DERRICK @ 816-522-4641
06/03/2015
06/16/2015
07/29/2015
Locations
Contacts
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
SARAH PEPPER ENTERPRISES LLC, Address:5925 WALNUT  
WACHTER INC, Address:16001 W 99TH ST, Phone:(913) 541-2500  
JDS CONSTRUCTION SERVICES LLC, Address:1616 NW NICHOLAS DR, Phone:(816) 522-4641  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 06/15/2015 06/15/2015
Joe Frogge
Building Plan Review Approved 06/15/2015 06/11/2015
Joe Frogge
Licensed Contractors Approved 06/15/2015 06/09/2015
Joe Frogge
Fire Plan Review Approved 06/04/2015
Brian Austerman
Address numbers required
Corrective Action Required
06/04/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on front and rear doors, if not already existing
Portable fire extinguishers - general
Corrective Action Required
06/04/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $102.13 $102.13 Paid 06/16/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 6/26/2015 6/26/2015 at 12:00 AM 06/26/2015
Occupancy Inspection - Fire Passed 7/29/2015 7/29/2015 at 12:00 AM 07/29/2015
Occupancy Inspection - Codes Commercial Full C of O 7/29/2015 7/29/2015 at 12:00 AM 07/29/2015
Documents & Images
Date Uploaded File Type Document Name
06/04/2015 Letter Fire Building Plan Review
06/15/2015 Letter Codes Plan Review Conditions
06/16/2015 Receipt Receipt for transaction: 2015-002950
06/16/2015 Letter Codes Building Permit
06/26/2015 Letter Inspection Summary
07/29/2015 Letter Field Certificate of Occupancy
07/30/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home