Permit Application Status

PRCOM20150917


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150917
Building Permit - Commercial
Final Completion
DKML LLC
ALTERATION COMMERCIAL
ELECTRICAL WORK FOR ADDITION TO FACTORY (PRCOM20142793)
04/29/2015
07/21/2015
10/01/2015
Locations
Contacts
ROYAL WIRING, Address:517 NE EMERALD DR, Phone:(816) 447-4945  
DKML LLC, Address:1161 SE HAMBLEN RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 07/16/2015 07/21/2015
Development Center
Building Plan Review Approved 05/11/2015 04/29/2015
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $277.12 $277.12 Paid 07/21/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 8/6/2015 8/6/2015 at 12:00 AM 08/06/2015
Misc
Corrective Action Required
08/06/2015
-INSTALL BUSHINGS FOR RACEWAY ENTRIES INTO SERVICE ENCLOSURES -SECURE AND SUPPORT SERVICE RACEWAYS PER CODE -INSTALL GROUNDING ELECTRODE CONDUCTOR SIZED PER 250.66
Electrical Service Inspection Passed 8/11/2015 8/12/2015 at 12:00 AM 08/12/2015
Misc
Corrective Action Required
08/06/2015
-INSTALL BUSHINGS FOR RACEWAY ENTRIES INTO SERVICE ENCLOSURES -SECURE AND SUPPORT SERVICE RACEWAYS PER CODE -INSTALL GROUNDING ELECTRODE CONDUCTOR SIZED PER 250.66
Underground Electrical Inspection - Commercial Passed 8/14/2015 8/14/2015 at 12:00 AM 08/14/2015
Miscellaneous Inspection Not Ready 8/31/2015 8/31/2015 at 12:00 AM 08/31/2015
Final Electrical Inspection - Commercial Partial 10/2/2015 10/2/2015 at 12:00 AM 10/02/2015
Misc
Partial Correction
10/02/2015
OKAY TO MOVE EQUIPMENT IN NEW ADDITION AREA. INSTALL 4 EMERGENCY LIGHTS, LABEL PANELS ONCE EQUIPMENT IS PLACED.
Occupancy Inspection - Fire Passed 10/2/2015 at 12:00 AM 10/02/2015
Documents & Images
Date Uploaded File Type Document Name
07/21/2015 Letter Codes Building Permit
07/21/2015 Receipt Receipt for transaction: 2015-004254
07/21/2015 Receipt Receipt for transaction: 2015-004254
08/06/2015 Letter Inspection Summary
08/12/2015 Letter Inspection Summary
10/02/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home