Permit Application Status

PRCOM20150741


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150741
Building Permit - Commercial
Certificate of Occupancy
RED LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR NEW CLOTHING STORE
04/09/2015
06/03/2015
10/18/2015
08/28/2015
Locations
Contacts
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
DMR SERVICES INC, Address:27215 S LEWIS RD, Phone:(816) 899-2159  
RIDEN SERVICE CO INC, Address:11306 W 89TH ST, Phone:(913) 432-8495  
GREENBERG FARROW, Address:4425 NORTH HIGH ST, SUITE 300, Phone:(614) 653-7193  
RED LEES SUMMIT EAST LLC, Address:1 E WASHINGTON ST STE 300  
PINNACLE CONSTRUCTION, INC, Address:22060 221ST SOUTH, Phone:(712) 527-9745  
ELDER-JONES INC, Address:1120 E 80TH ST STE 211, Phone:(952) 345-6059  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 07/09/2015
Joe Dir
Sprinkler Plan Review Released for Construction 07/07/2015
Joe Dir
Misc
Corrective Action Required
07/07/2015

Isolation valves will be addressed according to suite designation and monitored at the FACP Flow test required, call 816-969-1300 to schedule a test. verified at inspection
Building Plan Review Approved 05/11/2015 05/06/2015
Joe Frogge
Miscellaneous Correction
Resolved
05/06/2015

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment for informational purposes. The correct address for this project is 860 NW Blue Pkwy; unit P. Update your records accordingly. There is no need to reprint plan sets. 5/6/15 - acknowledged
Miscellaneous Correction
Resolved
05/06/2015

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Update drawing to demonstrate that Women's Room will have non-absorbent wall surfaces as appropriate. Re: sheet A05.01. 5/6/15 - walls will be vinyl per updated schedule
Misc
Resolved
05/06/2015

2012 IBC 1006.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that required two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required: Extend emergency illumination to exterior side of exits. 5/6/15 - light is existing and now noted as such
Licensed Contractors Rejected 05/04/2015 05/06/2015
Joe Frogge
Fire Plan Review Approved with Conditions 05/11/2015 05/05/2015
Brian Austerman
Miscellaneous Correction
Corrective Action Required
05/06/2015

907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Provide duct detection for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Miscellaneous Correction
Corrective Action Required
05/06/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Alarm contractor shall provide plans showing work done to the system
Misc 12
Corrective Action Required
05/06/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All exterior doors shall have addressing for the business, if not existing
Misc 13
Corrective Action Required
05/06/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All exterior doors shall have addressing for the business, if not existing
Misc 14
Corrective Action Required
05/06/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher for every 3,000 sq/ft or every 75' travel distance
Misc
Corrective Action Required
05/05/2015

No further FD comments
Building Plan Review Rejected 04/21/2015 04/21/2015
Joe Frogge
Suite address
Corrective Action Required
04/21/2015

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment for informational purposes. The correct address for this project is 860 NW Blue Pkwy; unit P. Update your records accordingly. There is no need to reprint plan sets.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
04/21/2015

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Update drawing to demonstrate that Women's Room will have non-absorbent wall surfaces as appropriate. Re: sheet A05.01.
Bldg - Emergency power for illumination 1006.3
Corrective Action Required
04/21/2015

2012 IBC 1006.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that required two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required: Extend emergency illumination to exterior side of exits.
Licensed Contractors Rejected 04/21/2015 04/21/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
04/21/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
04/21/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 04/21/2015 04/15/2015
Brian Austerman
Misc
Corrective Action Required
04/15/2015

907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Provide duct detection for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Construction documents for fire alarm systems
Corrective Action Required
04/15/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Alarm contractor shall provide plans showing work done to the system
Address numbers required
Corrective Action Required
04/15/2015

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All exterior doors shall have addressing for the business, if not existing
Construction documents - Fire protection systems
Corrective Action Required
04/15/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Sprinkler company shall provide plans for work done to the system
Portable fire extinguishers - general
Corrective Action Required
04/15/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type extinguisher for every 3,000 sq/ft or every 75' travel distance
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,758.40 $1,758.40 Paid 06/03/2015
8331507-Sewer Connection Fee $180.00 $180.00 Paid 06/03/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 6/15/2015 at 12:00 AM 06/15/2015
In-wall Inspection Partial 6/23/2015 6/23/2015 at 12:00 AM 06/23/2015
Misc
Partial Correction
06/23/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: ELECT RM S & E WALLS;
In-wall Inspection Partial 6/30/2015 6/30/2015 at 12:00 AM 06/30/2015
Misc
Partial Correction
06/23/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: ELECT RM S & E WALLS; [#2; 3; 5; 6; FITTING RM] ALL BELOW LIDS & SOFFITS;
In-wall Inspection Partial 7/2/2015 7/2/2015 at 12:00 AM 07/02/2015
Misc
Partial Correction
06/30/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: ALL WALLS, BULKHEADS AND SOFFITS EXCEPT AT STOREFRONT;
Underslab Electrical Inspection - Commercial Passed 7/8/2015 7/8/2015 at 12:00 AM 07/08/2015
Above Ceiling Inspection Partial 7/13/2015 7/13/2015 at 12:00 AM 07/13/2015
Misc
Partial Correction
07/13/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TRANSITION SOFFITS #2, 3, 4; CASHWRAP; QUEUING ZONE; FITTING ROOMS; VESTIBULE A #2; WOMENS RR; OFFICE; COMPLETE TOP CHORD AND CHECK SPLICES AT BULKHEAD BEAM AT TRANSITION #5. DO NOT COVER.
Above Ceiling Inspection Partial 7/15/2015 7/15/2015 at 12:00 AM 07/15/2015
Misc
Partial Correction
07/13/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TRANSITION SOFFITS #2, 3, 4; CASHWRAP; QUEUING ZONE; FITTING ROOMS; VESTIBULE A #2; WOMENS RR; OFFICE; HALLWAY EXCEPT W 5' WHERE TRUSS GIRDER BOTTOM CHORD BRACES HAVE YET TO BE WELDED; COMPLETE TOP CHORD AND CHECK SPLICES AT BULKHEAD BEAM AT TRANSITION #5. DO NOT COVER.
Electrical Service Inspection Partial 7/15/2015 7/15/2015 at 12:00 AM 07/15/2015
Misc
Partial Correction
07/15/2015
RELEASE ELECTRICAL SERVICE CONTINGENT ON COMPLIANT BONDING OF METER ENCLOSURE TO LINE SIDE DISCONNECT
Gas Piping Inspection - Commercial Failed 7/15/2015 7/15/2015 at 12:00 AM 07/15/2015
Misc
Corrective Action Required
07/15/2015
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING
Misc
Corrective Action Required
07/15/2015
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Gas Service Inspection - Commercial Passed 7/15/2015 at 12:00 AM 07/15/2015
Above Ceiling Inspection Partial 7/15/2015 at 12:00 AM 07/15/2015
Misc
Partial Correction
07/15/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TRANSITION SOFFITS #2, 3, 4; CASHWRAP; QUEUING ZONE; FITTING ROOMS; VESTIBULE A #2; WOMENS RR; OFFICE; TRANSITION #5; HALLWAY @ REAR; VESTIBULE A #1;
Electrical Service Inspection Passed 7/15/2015 at 12:00 AM 07/15/2015
Misc
Resolved
07/15/2015
RELEASE ELECTRICAL SERVICE CONTINGENT ON COMPLIANT BONDING OF METER ENCLOSURE TO LINE SIDE DISCONNECT
Above Ceiling Inspection Partial 7/23/2015 at 12:00 AM 07/23/2015
Misc
Partial Correction
07/23/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TRANSITION SOFFITS #2, 3, 4; CASHWRAP; QUEUING ZONE; FITTING ROOMS; VESTIBULE A #2; WOMENS RR; OFFICE; TRANSITION #5; HALLWAY @ REAR; VESTIBULE A #1; TRANSITION #7; TRANSITION #8; TRANSITION #9;
In-wall Inspection Passed 8/3/2015 8/3/2015 at 12:00 AM 08/03/2015
Misc
Resolved
08/03/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: ALL WALLS, BULKHEADS AND SOFFITS EXCEPT AT STOREFRONT;
In-wall Inspection Passed 8/12/2015 8/12/2015 at 12:00 AM 08/12/2015
Above Ceiling Inspection Not Ready 8/13/2015 8/13/2015 at 12:00 AM 08/13/2015
Misc
Corrective Action Required
08/13/2015
COMPLETE CONNECTIONS OF HVAC FLEX CONNECTORS TO DIFUSSERS.
Misc
Corrective Action Required
08/13/2015
SUPPORT L.V. CABLE FROM ELECTRICAL SLACK WIRES -- NOT FROM CEILING SUPPORT WIRES.
Misc
Corrective Action Required
08/13/2015
CLOSE ELECT JUNCTION BOXES
Misc
Corrective Action Required
08/13/2015
REMOVE TEMPORARY ELECTRICAL WIRING.
Misc
Corrective Action Required
08/13/2015
COMPLETE SIRING OF EXIST SIGNS
Above Ceiling Inspection Partial 8/14/2015 8/14/2015 at 12:00 AM 08/19/2015
Misc
Partial Correction
08/14/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: RMS #1, 2, 5;
Misc
Resolved
08/14/2015
SUPPORT L.V. CABLE FROM ELECTRICAL SLACK WIRES -- NOT FROM CEILING SUPPORT WIRES.
Misc
Resolved
08/14/2015
CLOSE ELECT JUNCTION BOXES
Misc
Corrective Action Required
08/13/2015
REMOVE TEMPORARY ELECTRICAL WIRING THROUGHOUT
Alarm Test Passed 8/20/2015 at 12:00 AM 08/20/2015
Sprinkler - Flow Test Passed 8/19/2015 at 12:00 AM 08/20/2015
Above Ceiling Inspection Partial 8/19/2015 at 12:00 AM 08/20/2015
Misc
Partial Correction
08/19/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: RMS #1, 2, 5; [#3 E 12'; #4; #6; STOCK/RECEIVING/PROCESSING; BREAK;
Above Ceiling Inspection Partial 8/20/2015 at 12:00 AM 08/20/2015
Occupancy Inspection - Codes Commercial Failed 8/21/2015 8/21/2015 at 12:00 AM 08/21/2015
Misc
Corrective Action Required
08/21/2015
COMPLETE PAINTING OF ROOFTOP GAS PIPE.
Misc
Corrective Action Required
08/21/2015
COMPLETE CLEARING/CLEANING OF ROOFTOP AT UNIT FOOTPRINT
Misc
Corrective Action Required
08/21/2015
STOREFRONT AREA NOT READY FOR INSPECTION.
Misc
Corrective Action Required
08/21/2015
ICC 117.1 INSTALL HANDICAPPED-ACCESSIBLE RESTROOM SIGNS.
Misc
Corrective Action Required
08/21/2015
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
08/21/2015
EMERGENCY EGRESS LIGHTING REQUIRED AT FRONT ENTRANCE
Misc
Corrective Action Required
08/21/2015
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600.3, IF INTERNALLY LIGHTED MUST BE SHOP-LABELED. INSTALL NO NON-LABELED SIGN.
Misc
Corrective Action Required
08/21/2015
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Misc
Corrective Action Required
08/21/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Rough Electrical Inspection - Commercial Passed 8/26/2015 8/26/2015 at 12:00 AM 08/26/2015
Occupancy Inspection - Codes Commercial Temporary C of O 8/27/2015 8/27/2015 at 12:00 AM 08/27/2015
Misc
Corrective Action Required
08/21/2015
COMPLETE PAINTING OF ROOFTOP GAS PIPE.
Misc
Corrective Action Required
08/21/2015
COMPLETE CLEARING/CLEANING OF ROOFTOP AT UNIT FOOTPRINT
Misc
Resolved
08/27/2015
STOREFRONT AREA NOT READY FOR INSPECTION.
Misc
Resolved
08/27/2015
ICC 117.1 INSTALL HANDICAPPED-ACCESSIBLE RESTROOM SIGNS.
Misc
Resolved
08/27/2015
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Resolved
08/27/2015
EMERGENCY EGRESS LIGHTING REQUIRED AT FRONT ENTRANCE
Misc
Resolved
08/27/2015
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600.3, IF INTERNALLY LIGHTED MUST BE SHOP-LABELED. INSTALL NO NON-LABELED SIGN.
Misc
Corrective Action Required
08/21/2015
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Misc
Resolved
08/27/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Passed 8/21/2015 8/27/2015 at 12:00 AM 08/27/2015
Occupancy Inspection - Codes Commercial Full C of O 8/28/2015 at 12:00 AM 08/28/2015
Misc
Resolved
08/28/2015
COMPLETE PAINTING OF ROOFTOP GAS PIPE.
Misc
Resolved
08/28/2015
COMPLETE CLEARING/CLEANING OF ROOFTOP AT UNIT FOOTPRINT
Misc
Resolved
08/28/2015
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Documents & Images
Date Uploaded File Type Document Name
04/15/2015 Letter Fire Building Plan Review
04/21/2015 Letter Codes P/R Corrections Document
05/05/2015 Letter Fire Building Plan Review
06/03/2015 Receipt Receipt for transaction: 2015-002151
06/03/2015 Letter Codes Plan Review Conditions
06/03/2015 Letter Codes Building Permit
06/15/2015 Letter Inspection Summary
06/23/2015 Letter Inspection Summary
06/30/2015 Letter Inspection Summary
07/02/2015 Letter Inspection Summary
07/07/2015 Letter Fire (Sprinkler) Plan Review
07/08/2015 Letter Inspection Summary
07/09/2015 Letter Fire (Alarm) Plan Review Notice
07/13/2015 Letter Inspection Summary
07/15/2015 Letter Inspection Summary
07/15/2015 Letter Inspection Summary
07/15/2015 Letter Inspection Summary
07/23/2015 Letter Inspection Summary
08/03/2015 Letter Inspection Summary
08/12/2015 Letter Inspection Summary
08/13/2015 Letter Inspection Summary
08/14/2015 Letter Inspection Summary
08/19/2015 Letter Inspection Summary
08/20/2015 Letter Inspection Summary
08/21/2015 Letter Inspection Summary
08/26/2015 Letter Inspection Summary
08/27/2015 Letter Codes Temporary Certificate of Occupancy
08/28/2015 Letter Field Certificate of Occupancy
08/28/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home