Permit Application Status

PRCOM20150580


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150580
Building Permit - Commercial
Certificate of Occupancy
RED LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR CLOTHING SALES
03/24/2015
05/28/2015
09/26/2015
07/14/2015
Locations
Contacts
HORIZON RETAIL CONSTRUCTION INC, Address:9999 E EXPLORATION CT, Phone:(262) 638-6000  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
D'AGOSTINO MECHANICAL CONTRACTORS, INC, Address:4440 OLIVER ST, Phone:(913) 384-5170  
PATRICK G BLEES, ARCHITECT, Address:800 WASHINGTON AVE N, STE 208, Phone:(612) 547-1300  
RED LEES SUMMIT EAST LLC, Address:1 E WASHINGTON ST STE 300  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 07/07/2015
Joe Dir
Misc
Corrective Action Required
07/07/2015

Flow switch and tamper / isolation valve to be addressed at the FACP according to suite designation. verified at inspection alarm test required call 816-969-1300 to schedule a test.
Sprinkler Plan Review Released for Construction 07/07/2015
Joe Dir
Misc
Corrective Action Required
07/07/2015

Isolation valve will be addressed according to suite designation and monitored at the FACP. Flow test required, call 816-969-1300 to schedule a test verified at inspection
Building Plan Review Approved with Conditions 04/17/2015 04/20/2015
Joe Frogge
Bldg - Premises identification/address 501.2
Resolved
04/14/2015

2012 IBC 501.2 – Premises identification. New and existing buildings shall have approved numbers or letters. Each character shall not be less than 3 inches high with a minimum stroke width of 0.5 inch. They should be installed on a contrasting background and be plainly legible and visible from the street or road fronting the property. When required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Address numbers and letters shall be Arabic numbers or alphabetical letters. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address numbers shall be maintained. In multi-tenant commercial buildings where tenants have multiple entrances located on different sides of the building, each door shall be addressed. Address characters shall be capable of being illuminated by an internal or external lighting source. Action required: Comment for informational purposes. Please note that the address originally submitted was incorrect. Permit reflects correct address. 4/14/15 - acknowledged by architect and corrected in permit files
License Tax Application
Corrective Action Required
04/10/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Resolved
04/16/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Specify fire ratings for new rear corridor walls and door (#111). Include UL # for wall and any associated construction details. 4/16/15 - provided
Misc 12
Resolved
04/14/2015

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide illumination at both sides of egress doors. 4/14/15 - note added to plans
Misc 13
Resolved
04/14/2015

2011 NEC 422.31 Disconnection of Permanently Connected Appliances. (A) Rated at Not over 300 Volt-Amperes or 1/8 Horsepower. For permanently connected appliances rated at not over 300 volt-amperes or 1/8 hp, the branch-circuit overcurrent device shall be permitted to serve as the disconnecting means. (B) Appliances Rated over 300 Volt-Amperes. For permanently connected appliances rated over 300 volt-amperes, the branch-circuit switch or circuit breaker shall be permitted to serve as the disconnecting means where the switch or circuit breaker is within sight from the appliance or is capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Action required: Provide disconnect switch at water heater or provide lock-out at breaker. 4/14/15 - lockout provided in updated panel sched
Fire Plan Review Approved with Conditions 04/17/2015 04/16/2015
Joe Frogge
Misc
Corrective Action Required
04/14/2015

4/14/15 - No further FD comments
Misc
Corrective Action Required
04/16/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Misc
Corrective Action Required
04/16/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide construction documents for any alterations to the sprinkler system
Misc
Corrective Action Required
04/16/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide construction documents for any alterations to the alarm system
Misc 20
Corrective Action Required
04/16/2015

907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Licensed Contractors Rejected 04/10/2015 04/14/2015
Joe Frogge
LC - General Contractor
Resolved
05/27/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
05/27/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Rejected 04/03/2015 03/30/2015
Joe Frogge
Bldg - Premises identification/address 501.2
Corrective Action Required
03/30/2015

2012 IBC 501.2 – Premises identification. New and existing buildings shall have approved numbers or letters. Each character shall not be less than 3 inches high with a minimum stroke width of 0.5 inch. They should be installed on a contrasting background and be plainly legible and visible from the street or road fronting the property. When required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Address numbers and letters shall be Arabic numbers or alphabetical letters. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address numbers shall be maintained. In multi-tenant commercial buildings where tenants have multiple entrances located on different sides of the building, each door shall be addressed. Address characters shall be capable of being illuminated by an internal or external lighting source. Action required: Comment for informational purposes. Please note that the address originally submitted was incorrect. Permit reflects correct address.
License Tax Application
Corrective Action Required
03/30/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
03/30/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Specify fire ratings for new rear corridor walls and door (#111). Include UL # for wall and any associated construction details.
Misc 12
Corrective Action Required
03/30/2015

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide illumination at both sides of egress doors.
Misc 13
Corrective Action Required
03/30/2015

2011 NEC 422.31 Disconnection of Permanently Connected Appliances. (A) Rated at Not over 300 Volt-Amperes or 1/8 Horsepower. For permanently connected appliances rated at not over 300 volt-amperes or 1/8 hp, the branch-circuit overcurrent device shall be permitted to serve as the disconnecting means. (B) Appliances Rated over 300 Volt-Amperes. For permanently connected appliances rated over 300 volt-amperes, the branch-circuit switch or circuit breaker shall be permitted to serve as the disconnecting means where the switch or circuit breaker is within sight from the appliance or is capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Action required: Provide disconnect switch at water heater or provide lock-out at breaker.
Licensed Contractors Rejected 04/03/2015 03/30/2015
Joe Frogge
LC - General Contractor
Corrective Action Required
03/30/2015

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
03/30/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved 04/03/2015 03/25/2015
Brian Austerman
Misc
Corrective Action Required
03/25/2015

907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the alarm panel
Construction documents for fire alarm systems
Corrective Action Required
03/25/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide construction documents for any alterations to the alarm system
Construction documents - Fire protection systems
Corrective Action Required
03/25/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide construction documents for any alterations to the sprinkler system
Portable fire extinguishers - general
Corrective Action Required
03/25/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $703.36 $703.36 Paid 05/28/2015
8331507-Sewer Connection Fee $120.00 $120.00 Paid 05/28/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 6/4/2015 6/4/2015 at 12:00 AM 06/04/2015
Misc
Partial Correction
06/04/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: PERIMETER WALLS;
Rated Assembly Inspection Failed 6/10/2015 6/10/2015 at 12:00 AM 06/10/2015
Misc
Corrective Action Required
06/10/2015
CORRECT FASTENER PATTERN TO 8"&12" EVERYWHERE INCLUDING BOTTOM OF STUDS AND AT PANEL JOINTS.
Misc
Corrective Action Required
06/10/2015
INTEGRITY OF GWB AND FASTENER PATTERN UNKNOWN WHERE ELECTRICAL BACKBOARD WAS INSTALLED PRIOR TO INSPECTION.
Underslab Electrical Inspection - Commercial Passed 6/10/2015 at 12:00 AM 06/10/2015
Underslab Plumbing Inspection - Commercial Passed 6/10/2015 at 12:00 AM 06/10/2015
Rated Assembly Inspection Partial 6/11/2015 6/11/2015 at 12:00 AM 06/11/2015
Misc
Resolved
06/11/2015
CORRECT FASTENER PATTERN TO 8"&12" EVERYWHERE INCLUDING BOTTOM OF STUDS AND AT PANEL JOINTS.
Misc
Resolved
06/11/2015
INTEGRITY OF GWB AND FASTENER PATTERN UNKNOWN WHERE ELECTRICAL BACKBOARD WAS INSTALLED PRIOR TO INSPECTION.
Misc
Partial Correction
06/11/2015
OK TO TAPE, MUD, AND FIRE-SEAL ONE LAYER 5/8" TYPE X GWB AT PERIMETER INTERIOR FACE. COMPLETION OF PENETRATION SEALING SUBJECT TO APPROVAL.
In-wall Inspection Partial 6/17/2015 6/17/2015 at 12:00 AM 06/17/2015
Misc
Partial Correction
06/04/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: PERIMETER WALLS; INTERIOR WALLS EXCEPT OK TO ONE-SIDE ONLY AT WET WALLS;
In-wall Inspection Passed 6/18/2015 6/18/2015 at 12:00 AM 06/18/2015
Misc
Resolved
06/18/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: PERIMETER WALLS; INTERIOR WALLS THROUGHOUT
Above Ceiling Inspection Passed 6/18/2015 6/18/2015 at 12:00 AM 06/18/2015
Misc
Partial Correction
06/18/2015
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: FITTING ALCOVE; SOFFIT AT FRONT(WEST) WALL;
Rated Assembly Inspection Partial 6/19/2015 6/19/2015 at 12:00 AM 06/19/2015
Misc
Partial Correction
06/11/2015
OK TO TAPE, MUD, AND FIRE-SEAL ONE LAYER 5/8" TYPE X GWB AT INTERIOR FACE OF PERIMETER WALLS. COMPLETION OF PENETRATION SEALING SUBJECT TO APPROVAL.
Misc
Partial Correction
06/19/2015
PERIMETER WALLS OF REAR (EAST) VESTIBULE ARE APPROVED AS BUILT AND FIRE-SEALED TO ROOF DECK. OK TO CONSTRUCT (INCLUDING TAPE&MUD) WITHOUT ITERIM INSPECTION TWO-LAYER CEILING IN VESTIBULE PER A/E LTR DTD 6/9/15.
Electrical Service Inspection Passed 6/23/2015 6/23/2015 at 12:00 AM 06/23/2015
Gas Service Inspection - Commercial Not Ready 6/26/2015 at 12:00 AM 06/26/2015
Gas Piping Inspection - Commercial Not Ready 6/26/2015 6/26/2015 at 12:00 AM 06/26/2015
Above Ceiling Inspection Partial 6/26/2015 6/26/2015 at 12:00 AM 06/26/2015
Misc
Partial Correction
06/26/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SALES AREA;
Rated Assembly Inspection Passed 6/26/2015 at 12:00 AM 06/26/2015
Misc
Resolved
06/26/2015
OK TO TAPE, MUD, AND FIRE-SEAL ONE LAYER 5/8" TYPE X GWB AT INTERIOR FACE OF PERIMETER WALLS. COMPLETION OF PENETRATION SEALING SUBJECT TO APPROVAL.
Misc
Partial Correction
06/19/2015
PERIMETER WALLS OF REAR (EAST) VESTIBULE ARE APPROVED AS BUILT AND FIRE-SEALED TO ROOF DECK. OK TO CONSTRUCT (INCLUDING TAPE&MUD) WITHOUT ITERIM INSPECTION TWO-LAYER CEILING IN VESTIBULE PER A/E LTR DTD 6/9/15.
Above Ceiling Inspection Passed 6/30/2015 6/30/2015 at 12:00 AM 06/30/2015
Misc
Resolved
06/30/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SALES AREA;
Gas Service Inspection - Commercial Passed 6/30/2015 at 12:00 AM 06/30/2015
Gas Piping Inspection - Commercial Failed 6/30/2015 6/30/2015 at 12:00 AM 06/30/2015
Misc
Corrective Action Required
06/30/2015
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING
Misc
Corrective Action Required
06/30/2015
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING.
Misc
Corrective Action Required
06/30/2015
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Miscellaneous Inspection Passed 7/10/2015 at 12:00 AM 07/10/2015
Sprinkler - Flow Test Passed 7/13/2015 at 12:00 AM 07/13/2015
Alarm Test Passed 7/13/2015 at 12:00 AM 07/13/2015
Occupancy Inspection - Fire Passed 7/13/2015 at 12:00 AM 07/13/2015
Occupancy Inspection - Codes Commercial Failed 7/13/2015 7/13/2015 at 12:00 AM 07/13/2015
Misc
Corrective Action Required
07/13/2015
DESIGNATE THE TWO ELECTRICAL PANELS PER DRAWING WITH LABLE ON PANEL FRONT.
Misc
Corrective Action Required
07/13/2015
CORRECT ELECTRICALPANEL SCHEDULES
Misc
Corrective Action Required
07/13/2015
SUPPORT CANTILEVERED END OF EXISTING GAS PIPE ABOVE CORRIDOR AT REAR
Misc
Corrective Action Required
07/13/2015
SEAL WATER CLOSET TO FLOOR.
Misc
Corrective Action Required
07/13/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO CUSTOMERS OR PUBLIC BEFORE COFO APPROVAL.
Occupancy Inspection - Codes Commercial Full C of O 7/14/2015 7/14/2015 at 12:00 AM 07/14/2015
Misc
Resolved
07/14/2015
DESIGNATE THE TWO ELECTRICAL PANELS PER DRAWING WITH LABLE ON PANEL FRONT.
Misc
Resolved
07/14/2015
CORRECT ELECTRICALPANEL SCHEDULES
Misc
Resolved
07/14/2015
SUPPORT CANTILEVERED END OF EXISTING GAS PIPE ABOVE CORRIDOR AT REAR
Misc
Resolved
07/14/2015
SEAL WATER CLOSET TO FLOOR.
Misc
Resolved
07/14/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO CUSTOMERS OR PUBLIC BEFORE COFO APPROVAL.
Documents & Images
Date Uploaded File Type Document Name
03/25/2015 Letter Fire Building Plan Review
03/30/2015 Letter Codes P/R Corrections Document
04/14/2015 Letter Fire Building Plan Review
05/27/2015 Letter Codes Plan Review Conditions
05/28/2015 Receipt Receipt for transaction: 2015-001848
05/28/2015 Letter Codes Building Permit
06/04/2015 Letter Inspection Summary
06/10/2015 Letter Inspection Summary
06/10/2015 Letter Inspection Summary
06/11/2015 Letter Inspection Summary
06/17/2015 Letter Inspection Summary
06/18/2015 Letter Inspection Summary
06/19/2015 Letter Inspection Summary
06/23/2015 Letter Inspection Summary
06/26/2015 Letter Inspection Summary
06/30/2015 Letter Inspection Summary
07/07/2015 Letter Fire (Sprinkler) Plan Review
07/07/2015 Letter Fire (Alarm) Plan Review Notice
07/13/2015 Letter Inspection Summary
07/14/2015 Letter Field Certificate of Occupancy
07/15/2015 Letter Codes Final Certificate of Occupancy
07/16/2015 Engineer Report/Study DOC071615-001
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home