Permit Application Status

PRCOM20150035


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150035
Building Permit - Commercial
Final Completion
ROCKY TOP HOLDINGS LLC
CHANGE OF TENANT
RELOCATE EXISTING WALL TO RECONFIGURE OFFICE
01/07/2015
01/30/2015
07/21/2015
07/15/2015
Locations
Contacts
PHOENIX CONSTRUCTION INC, Address:1305 HOLLY CT, Phone:(816) 716-8208  
ROCKY TOP HOLDINGS LLC, Address:244 W MILL ST STE 101  
BRADLEY-READE INC, Address:810 W 7TH AVE, Phone:(816) 898-2947  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 01/30/2015 01/23/2015
Joe Frogge
Bldg - Types I and II construction allowable materials 602.2
Resolved
01/23/2015

2012 IBC 602.2 – Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required: Specify wall construction. Demonstrate that materials used are compliant. 1/23/15 - specified in email attached to drawing
Misc 16
Corrective Action Required
01/23/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Dimension between latch side of main entry door and new wall is to be minimum 12" if the door has a closer. This can be verified during inspections.
Fire Plan Review Approved with Conditions 01/30/2015 01/23/2015
Joe Frogge
Misc
Corrective Action Required
01/23/2015

Exit signs and emergency lighting shall be in appropriate locations and in good working order
Construction documents for fire alarm systems
Corrective Action Required
01/23/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If alterations to notification devices are needed provide plans for work done
Construction documents - Fire protection systems
Corrective Action Required
01/23/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If alterations to the sprinkler system are required provide plans showing work
Portable fire extinguishers - general
Corrective Action Required
01/23/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Licensed Contractors Approved 01/23/2015 01/23/2015
Joe Frogge
LC - MEP Subs
Resolved
01/23/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Rejected 01/20/2015 01/22/2015
Joe Frogge
Bldg - Types I and II construction allowable materials 602.2
Corrective Action Required
01/22/2015

2012 IBC 602.2 – Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code. Action required: Specify wall construction. Demonstrate that materials used are compliant.
Misc 16
Corrective Action Required
01/22/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Dimension between latch side of main entry door and new wall is to be minimum 12" if the door has a closer. This can be verified during inspections.
Licensed Contractors Rejected 01/20/2015 01/22/2015
Joe Frogge
LC - MEP Subs
Corrective Action Required
01/22/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 01/20/2015 01/13/2015
Brian Austerman
Misc
Corrective Action Required
01/13/2015

Exit signs and emergency lighting shall be in appropriate locations and in good working order
Construction documents for fire alarm systems
Corrective Action Required
01/13/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If alterations to notification devices are needed provide plans for work done
Construction documents - Fire protection systems
Corrective Action Required
01/13/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If alterations to the sprinkler system are required provide plans showing work
Portable fire extinguishers - general
Corrective Action Required
01/13/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 01/30/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Commercial Passed 7/15/2015 at 12:00 AM 07/15/2015
Documents & Images
Date Uploaded File Type Document Name
01/13/2015 Letter Fire Building Plan Review
01/22/2015 Letter Codes P/R Corrections Document
01/23/2015 Letter Codes Plan Review Conditions
01/30/2015 Receipt Receipt for transaction: 2015-000136
01/30/2015 Letter Codes Building Permit
07/09/2015 Letter Codes 140 Day Letter
07/15/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home