Permit Application Status

PRCOM20150016


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20150016
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW COMMERCIAL
COMMON AREA SERVING ATTACHED MULTI-FAMILY INDEPENDENT SENIOR LIVING - INCLUDES KITCHEN, DINING, OFFICE AND GATHERING AREAS - ALSO INCLUDES ELEVATED WALKWAY CONNECTION TO PAVILION
01/06/2015
06/02/2015
07/18/2015
09/22/2016
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
SALADINO PLUMBING & HEATING COMPANY, Address:2210 TELEVISION PL, Phone:(816) 833-9900  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
UNITED PLUMBING & SERVICE CO INC, Address:301 DUCK RD, Phone:(816) 761-5262  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2015
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2015
Joe Dir
Fire Plan Review Approved with Conditions 09/18/2015 09/18/2015
Joe Dir
Posting of occupant load
Corrective Action Required
09/18/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Occupant loads shall be posted in assembly areas VERIFIED AT INSPECTION
Construction documents for fire alarm systems
Corrective Action Required
09/18/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide engineer stamped alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
09/18/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide engineer stamped sprinkler plans for approval
Misc
Corrective Action Required
09/18/2015

904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher in accordance with Section 904.11.5.1 or 904.11.5.2, as applicable. 904.11.5.1 Portable fire extinguishers for solid fuel cooking appliances. All solid fuel cooking appliances, whether or not under a hood, with fireboxes 5 cubic feet (0.14 m3) or less in volume shall have a minimum 2.5-gallon (9 L) or two 1.5-gallon (6 L) Class K wet-chemical portable fire extinguishers located in accordance with Section 904.11.5. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one Class K portable fire extinguisher of a minimum 1.5-gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one additional Class K portable fire extinguisher of a minimum 1.5-gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations. Provide K class and water extinguishers as required for the kitchen hoods and charbroiler. Will solid fuels be used for the charbroiler? EXTINGUISHER SHOWN IN DRAWING A1.2, QUESTION NOT ADDRESSED ABOUT CHARBROILER
Misc
Corrective Action Required
09/18/2015

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. Show location of manual pull device for the hoods. K class extinguisher shall be mounted below the pull MANUAL PULL SHOWN IN FS1 DRAWINGS, APPEARS TO BE TOO CLOSE ACCORDING TO THE 1/4" SCALE VERIFED AT INSPECTION.
Misc
Corrective Action Required
09/18/2015

Duct detection required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel Show on alarm plans PROVIDE ENGINEERED SHOP DRAWINGS
Misc
Corrective Action Required
09/18/2015

Will generator be natural gas or diesel? QUESTION NOT ADDRESSED.
Fire Plan Review Approved with Conditions 02/06/2015 06/02/2015
Mike Weisenborn
Posting of occupant load
Corrective Action Required
02/19/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Occupant loads shall be posted in assembly areas
Construction documents for fire alarm systems
Corrective Action Required
02/19/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide engineer stamped alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
02/19/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide engineer stamped sprinkler plans for approval
Misc
Corrective Action Required
02/19/2015

904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher in accordance with Section 904.11.5.1 or 904.11.5.2, as applicable. 904.11.5.1 Portable fire extinguishers for solid fuel cooking appliances. All solid fuel cooking appliances, whether or not under a hood, with fireboxes 5 cubic feet (0.14 m3) or less in volume shall have a minimum 2.5-gallon (9 L) or two 1.5-gallon (6 L) Class K wet-chemical portable fire extinguishers located in accordance with Section 904.11.5. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one Class K portable fire extinguisher of a minimum 1.5-gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one additional Class K portable fire extinguisher of a minimum 1.5-gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations. Provide K class and water extinguishers as required for the kitchen hoods and charbroiler. Will solid fuels be used for the charbroiler?
Misc
Corrective Action Required
02/19/2015

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. Show location of manual pull device for the hoods. K class extinguisher shall be mounted below the pull
Misc
Corrective Action Required
02/19/2015

Duct detection required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel Show on alarm plans
Misc
Corrective Action Required
02/19/2015

Will generator be natural gas or diesel?
Building Plan Review Approved with Conditions 06/17/2015 06/02/2015
Mike Weisenborn
License Tax Application
Corrective Action Required
02/19/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Health Dept Inspection
Corrective Action Required
02/19/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment for informational purposes.
Engineered truss package
Corrective Action Required
02/19/2015

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof and floor truss packages or defer to construction. Approved truss packages must be on site for inspections. 2/10/15 - deferred to construction
Bldg - Occupant load posting 1004.3
Corrective Action Required
02/19/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment for informational purposes. To be verified during inspections.
Misc
Corrective Action Required
02/19/2015

2012 IBC 1013.6 Mechanical equipment. Guards shall be provided where appliances, equipment, fans, roof hatch openings or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a sphere 21 inches in diameter. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment, fan, or component. Action required: Comment for informational purposes. May be verified during inspections.
Misc
Corrective Action Required
02/19/2015

Additional information required. Action required: Provide verification that salon will not have manicure or pedicure stations. 2/10/15 - Wall exhaust grille added near manicure station. Pedicure chair not found on drawings. Given that furniture plans sometimes vary, this will be verified in the field. Exhaust grilles must be at source.
Final Development Plan Review Approved 04/22/2015 05/15/2015
Mike Weisenborn
Special Inspections Review Approved 05/15/2015
Mike Weisenborn
Licensed Contractors Approved 02/17/2015 03/27/2015
Mike Weisenborn
Fire Plan Review Approved with Conditions 02/06/2015 02/10/2015
Brian Austerman
Posting of occupant load
Corrective Action Required
02/10/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Occupant loads shall be posted in assembly areas
Construction documents for fire alarm systems
Corrective Action Required
02/10/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide engineer stamped alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
02/10/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide engineer stamped sprinkler plans for approval
Misc
Corrective Action Required
02/10/2015

904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher in accordance with Section 904.11.5.1 or 904.11.5.2, as applicable. 904.11.5.1 Portable fire extinguishers for solid fuel cooking appliances. All solid fuel cooking appliances, whether or not under a hood, with fireboxes 5 cubic feet (0.14 m3) or less in volume shall have a minimum 2.5-gallon (9 L) or two 1.5-gallon (6 L) Class K wet-chemical portable fire extinguishers located in accordance with Section 904.11.5. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one Class K portable fire extinguisher of a minimum 1.5-gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one additional Class K portable fire extinguisher of a minimum 1.5-gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations. Provide K class and water extinguishers as required for the kitchen hoods and charbroiler. Will solid fuels be used for the charbroiler?
Misc
Corrective Action Required
02/10/2015

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. Show location of manual pull device for the hoods. K class extinguisher shall be mounted below the pull
Misc
Corrective Action Required
02/10/2015

Duct detection required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel Show on alarm plans
Misc
Corrective Action Required
02/10/2015

Will generator be natural gas or diesel?
Building Plan Review Approved with Conditions 02/10/2015 02/10/2015
Joe Frogge
License Tax Application
Corrective Action Required
01/30/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Final Development Plan
Resolved
02/03/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes.
Health Dept Inspection
Corrective Action Required
01/30/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment for informational purposes.
Health Dept Review
Resolved
02/05/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required - This comment is for information purposes. Action required: Comment for informational purposes.
Engineered truss package
Corrective Action Required
01/30/2015

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof and floor truss packages or defer to construction. Approved truss packages must be on site for inspections. 2/10/15 - deferred to construction
Misc 13
Resolved
02/10/2015

2012 IBC Chapter 7. Action required: Provide fire ratings and UL numbers for relevant wall assemblies. Also complete rating portion of door schedules. Wall schedule and door schedule information not consistent with Life Safety plans provided. 2/10/15 - schedule updated.
Bldg - Occupant load posting 1004.3
Corrective Action Required
01/30/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment for informational purposes. To be verified during inspections.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
02/10/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify drawings at Women's restroom. Minimum clear space next to latch side of door is 18". 2/10/15 - drawings updated
Misc 15
Resolved
02/10/2015

2012 IBC 718.3 Draftstopping in floors. In combustible construction, draftstopping shall be installed to subdivide floor/ceiling assemblies in the locations prescribed in Sections 718.3.2 through 718.3.3 2012 IBC 718.4 Draftstopping in attics. In combustible construction, draftstopping shall be installed to subdivide attic spaces and concealed roof spaces in the locations prescribed in Sections 718.4.2 and 718.4.3. Ventilation of concealed roof spaces shall be maintained in accordance with Section 1203.2 Action required: Provide draftstopping at relevant locations in floors and attics. 2/10/15 - meets exemption
Misc 12
Resolved
02/10/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide fire protection at Canopy columns and at Porte Cochere. 2/10/15 - details updated
Misc
Resolved
02/10/2015

ICC A117.1-2009 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met at spaces under stairs. 2/10/15 - clarified
Bldg - Guard height 1013.3
Resolved
02/10/2015

2012 IBC 1013.3 – Height. Required guards shall not be less than 42 inches high, measured vertically as follows: 1. From the adjacent walking surface; 2. On stairs, from the line connecting the leading edges of the tread nosings; and 3. On ramps, from the ramp surface at the guard. (See code section for possible exceptions.) Action required: Provide compliant guard at stairs. Ref: 10/A8.2. 2/10/15 - drawings updated
Miscellaneous Correction
Resolved
02/10/2015

2012 IBC 803.5. Textile wall coverings. Where used as interior wall finish materials, textile wall coverings, including materials having woven or unwoven, napped, tufted, looped or similar surface and carpet and similar textile materials, shall be tested in the manner intended for use, using the product mounting system, including adhesive, and shall comply with the requirements of Section 803.1.2, 803.1.3 or 803.1.4 Action required: Provide verification that silk panels are compliant. 2/10/15 - silk panels not being installed.
Misc
Corrective Action Required
01/30/2015

2012 IBC 1013.6 Mechanical equipment. Guards shall be provided where appliances, equipment, fans, roof hatch openings or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a sphere 21 inches in diameter. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment, fan, or component. Action required: Comment for informational purposes. May be verified during inspections.
Misc
Corrective Action Required
01/30/2015

Additional information required. Action required: Provide verification that salon will not have manicure or pedicure stations. 2/10/15 - Wall exhaust grille added near manicure station. Pedicure chair not found on drawings. Given that furniture plans sometimes vary, this will be verified in the field. Exhaust grilles must be at source.
Misc 19
Resolved
02/10/2015

Additional information required. Action required: Provide verification that replacement unit RTU-7 is the same or less weight or verify that existing roof structure is adequate to carry the new load. 2/10/15 - clarified
Miscellaneous Correction
Resolved
02/10/2015

2012 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision ins made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Protect pipes from potential freezing. Ref: Piping in wall at 3"CW entry. 2/10/15 - drawings updated
Misc 14
Resolved
02/10/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: All receptacles in kitchen (including serving bar) to be GFCI protected. 2/10/15 - note added to drawings
Bldg - Illumination required 1006.1
Resolved
02/10/2015

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at Dining C109. 2/10/15 - added to drawings
Misc 16
Resolved
02/10/2015

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit lighting at Stair C124. 2/10/15 - drawings updated
Health Department Review Approved 02/05/2015
Joe Frogge
D. SEES - 1/5/15
Fire Plan Review Approved with Conditions 02/06/2015 02/02/2015
Brian Austerman
Posting of occupant load
Corrective Action Required
01/30/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Occupant loads shall be posted in assembly areas
Construction documents for fire alarm systems
Corrective Action Required
01/30/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide engineer stamped alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
01/30/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide engineer stamped sprinkler plans for approval
Misc
Corrective Action Required
01/30/2015

904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher in accordance with Section 904.11.5.1 or 904.11.5.2, as applicable. 904.11.5.1 Portable fire extinguishers for solid fuel cooking appliances. All solid fuel cooking appliances, whether or not under a hood, with fireboxes 5 cubic feet (0.14 m3) or less in volume shall have a minimum 2.5-gallon (9 L) or two 1.5-gallon (6 L) Class K wet-chemical portable fire extinguishers located in accordance with Section 904.11.5. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one Class K portable fire extinguisher of a minimum 1.5-gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one additional Class K portable fire extinguisher of a minimum 1.5-gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations. Provide K class and water extinguishers as required for the kitchen hoods and charbroiler. Will solid fuels be used for the charbroiler?
Misc
Corrective Action Required
01/30/2015

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. Show location of manual pull device for the hoods. K class extinguisher shall be mounted below the pull
Misc
Corrective Action Required
01/30/2015

Duct detection required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel
Misc
Corrective Action Required
02/02/2015

Will generator be natural gas or diesel?
Building Plan Review Rejected 01/20/2015 01/19/2015
Joe Frogge
License Tax Application
Corrective Action Required
01/19/2015

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Final Development Plan
Corrective Action Required
01/19/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes.
Health Dept Inspection
Corrective Action Required
01/19/2015

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment for informational purposes.
Health Dept Review
Corrective Action Required
01/19/2015

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required - This comment is for information purposes. Action required: Comment for informational purposes.
Engineered truss package
Corrective Action Required
01/19/2015

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof and floor truss packages or defer to construction. Approved truss packages must be on site for inspections.
Misc 13
Corrective Action Required
01/19/2015

2012 IBC Chapter 7. Action required: Provide fire ratings and UL numbers for relevant wall assemblies. Also complete rating portion of door schedules. Wall schedule and door schedule information not consistent with Life Safety plans provided.
Bldg - Occupant load posting 1004.3
Corrective Action Required
01/19/2015

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment for informational purposes. To be verified during inspections.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
01/19/2015

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify drawings at Women's restroom. Minimum clear space next to latch side of door is 18".
Misc 15
Corrective Action Required
01/19/2015

2012 IBC 718.3 Draftstopping in floors. In combustible construction, draftstopping shall be installed to subdivide floor/ceiling assemblies in the locations prescribed in Sections 718.3.2 through 718.3.3 2012 IBC 718.4 Draftstopping in attics. In combustible construction, draftstopping shall be installed to subdivide attic spaces and concealed roof spaces in the locations prescribed in Sections 718.4.2 and 718.4.3. Ventilation of concealed roof spaces shall be maintained in accordance with Section 1203.2 Action required: Provide draftstopping at relevant locations in floors and attics.
Misc 12
Corrective Action Required
01/19/2015

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide fire protection at Canopy columns and at Porte Cochere.
Misc
Corrective Action Required
01/19/2015

ICC A117.1-2009 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met at spaces under stairs.
Bldg - Guard height 1013.3
Corrective Action Required
01/19/2015

2012 IBC 1013.3 – Height. Required guards shall not be less than 42 inches high, measured vertically as follows: 1. From the adjacent walking surface; 2. On stairs, from the line connecting the leading edges of the tread nosings; and 3. On ramps, from the ramp surface at the guard. (See code section for possible exceptions.) Action required: Provide compliant guard at stairs. Ref: 10/A8.2.
Miscellaneous Correction
Corrective Action Required
01/19/2015

2012 IBC 803.5. Textile wall coverings. Where used as interior wall finish materials, textile wall coverings, including materials having woven or unwoven, napped, tufted, looped or similar surface and carpet and similar textile materials, shall be tested in the manner intended for use, using the product mounting system, including adhesive, and shall comply with the requirements of Section 803.1.2, 803.1.3 or 803.1.4 Action required: Provide verification that silk panels are compliant.
Misc
Corrective Action Required
01/19/2015

2012 IBC 1013.6 Mechanical equipment. Guards shall be provided where appliances, equipment, fans, roof hatch openings or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a sphere 21 inches in diameter. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment, fan, or component. Action required: Comment for informational purposes. May be verified during inspections.
Misc
Corrective Action Required
01/19/2015

Additional information required. Action required: Provide verification that salon will not have manicure or pedicure stations.
Misc 19
Corrective Action Required
01/19/2015

Additional information required. Action required: Provide verification that replacement unit RTU-7 is the same or less weight or verify that existing roof structure is adequate to carry the new load.
Miscellaneous Correction
Corrective Action Required
01/19/2015

2012 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision ins made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Protect pipes from potential freezing. Ref: Piping in wall at 3"CW entry.
Misc 14
Corrective Action Required
01/19/2015

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: All receptacles in kitchen (including serving bar) to be GFCI protected.
Bldg - Illumination required 1006.1
Corrective Action Required
01/19/2015

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide emergency lighting at Dining C109.
Misc 16
Corrective Action Required
01/19/2015

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit lighting at Stair C124.
Misc 17
Corrective Action Required
01/19/2015

2011 NEC Article 110.26 (C) (2) Large Equipment. For equipment rated 1200 amperes or more and over 6 feet wide that contains overcurrent devices, switching devices, or control devices, there shall be on entrance to and egress from the required working space not less than 24” wide and 6’6” high at each end to the working space. A single entrance to and egress from the required working space shall be permitted where either of the conditions in 110.26(C)(2)(a) or (C)(2)(b) is met. (a) Unobstructed Egress. Where the location permits a continuous and unobstructed way of egress travel, a single entrance to the working space shall be permitted. (b) Extra Working Space. Where the depth of the working space is twice that required by 110.26(A)(1), a single entrance to the working space shall be permitted. It shall be located such that the distance from the equipment to the nearest edge of the entrance3 is not less than the minimum clear distance specified in Table 110.26(A)(1) for equipment operating at that voltage and in that condition. 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At Mechanical Room C119 two exits with panic hardware required.
Licensed Contractors Rejected 01/21/2015 01/19/2015
Joe Frogge
LC - MEP Subs
Resolved
03/27/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 01/20/2015 01/08/2015
Brian Austerman
Misc
Corrective Action Required
01/08/2015

Confirming the hoods will be type 1
Posting of occupant load
Corrective Action Required
01/08/2015

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Occupant loads shall be posted in assembly areas
Construction documents for fire alarm systems
Corrective Action Required
01/08/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide engineer stamped alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
01/08/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide engineer stamped sprinkler plans for approval
Misc
Corrective Action Required
01/08/2015

904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher in accordance with Section 904.11.5.1 or 904.11.5.2, as applicable. 904.11.5.1 Portable fire extinguishers for solid fuel cooking appliances. All solid fuel cooking appliances, whether or not under a hood, with fireboxes 5 cubic feet (0.14 m3) or less in volume shall have a minimum 2.5-gallon (9 L) or two 1.5-gallon (6 L) Class K wet-chemical portable fire extinguishers located in accordance with Section 904.11.5. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one Class K portable fire extinguisher of a minimum 1.5-gallon ( 6 L) capacity. 2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: one additional Class K portable fire extinguisher of a minimum 1.5-gallon (6 L) capacity shall be provided. 3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations. Provide K class and water extinguishers as required for the kitchen hoods and charbroiler. Will solid fuels be used for the charbroiler?
Misc
Corrective Action Required
01/08/2015

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. Show location of manual pull device for the hoods. K class extinguisher shall be mounted below the pull
Misc
Corrective Action Required
01/08/2015

Duct detection required for units over 2,000 cfm. Activation shall shut down the unit and transmit a supervisory signal to the panel
Misc
Corrective Action Required
01/08/2015

Provide exterior egress lighting for the commons 1. out of the dining room to the exterior (west door) 2. outside north stair exit
Misc
Resolved
01/20/2015

[B] 1011.2 Floor-level exit signs in Group R-1. Where exit signs are required in Group R-1 occupancies by Section 1011.1, additional low-level exit signs shall be provided in all areas serving guestrooms in Group R-1 occupancies and shall comply with Section 1011.5. The bottom of the sign shall be not less than 10 inches (254 mm) nor more than 12 inches (305 mm) above the floor level. The sign shall be flush mounted to the door or wall. Where mounted on the wall, the edge of the sign shall be within 4 inches (102 mm) of the door frame on the latch side. Provide high and low level exit signage Mike Weisenborn 01/20/2015 9:29 AM - This project is an R-2 occupancy so this section is not applicable.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Addition to Commercial $9,667.57 $9,667.57 Paid 06/02/2015
Water Meter Fee $2,517.48 $2,517.48 Paid 06/02/2015
Water Tap Fee $10,660.00 $10,660.00 Paid 06/02/2015
8331507-Sewer Connection Fee $750.00 $750.00 Paid 06/02/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Hydrostatic Test Passed 8/31/2015 at 12:00 AM 08/31/2015
Footing Inspection - Commercial Partial 9/3/2015 (11:30) 9/3/2015 at 12:00 AM 09/03/2015
Misc
Partial Correction
09/03/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: A4.1/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 L.4/8 TO K/8 TO K/9 TO J/9 TO J/9.7;
Footing Inspection - Commercial Partial 9/4/2015 at 12:00 AM 09/04/2015
Footing Inspection - Commercial Passed 9/4/2015 (1:00) 9/3/2015 at 12:00 AM 09/09/2015
B1805 FOOTINGS AND FOUNDATIONS
Partial Correction
09/04/2015
Footing Inspection - Commercial Partial 9/9/2015 (1:00) 9/9/2015 at 12:00 AM 09/09/2015
Misc
Partial Correction
09/04/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Footing Inspection - Commercial Partial 9/10/2015 (1:30) 9/10/2015 at 12:00 AM 09/10/2015
Misc
Partial Correction
09/09/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Footing Inspection - Commercial Partial 9/11/2015 (1:00) 9/11/2015 at 12:00 AM 09/11/2015
Misc
Partial Correction
09/10/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/11/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Footing Inspection - Commercial Partial 9/12/2015 at 12:00 AM 09/12/2015
Misc
Partial Correction
09/11/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/11/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
09/12/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H;
Footing Inspection - Commercial Partial 9/16/2015 (1:30) 9/16/2015 at 12:00 AM 09/16/2015
Misc
Partial Correction
09/12/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/12/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
09/12/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7;
Footing Inspection - Commercial Partial 9/17/2015 (1:00) 9/17/2015 at 12:00 AM 09/17/2015
Misc
Partial Correction
09/16/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/16/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
09/16/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8;
Footing Inspection - Commercial Partial 9/22/2015 at 12:00 AM 09/22/2015
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4;
Footing Inspection - Commercial Partial 9/28/2015 at 12:00 AM 09/28/2015
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4;
Misc
Partial Correction
09/28/2015
ELEVATOR PIT SLAB POUR INSPECTED BY 3RD PARTY INSPECTOR 9/26/15
Footing Inspection - Commercial Not Ready 9/22/2015 (1:30) 9/17/2015 at 12:00 AM 09/29/2015
Misc
Partial Correction
09/17/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/17/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Concrete Walls and Columns Inspection Partial 9/29/2015 at 12:00 AM 09/29/2015
Misc
Partial Correction
09/29/2015
ELEVATOR PIT WALLS OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 10/7/2015 (1:00) 10/7/2015 at 12:00 AM 10/07/2015
Misc
Partial Correction
09/29/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/29/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
09/29/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB;
Underslab Plumbing Inspection - Commercial Partial 10/19/2015 10/19/2015 at 12:00 AM 10/19/2015
Misc
Partial Correction
10/19/2015
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, GREASE WASTE, & VENT PIPING AT: ALL NORTH OF (AC.7) EXCEPT FLOOR SINK AT (1)/(A0.4) TO BE INSTALLED NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Footing Inspection - Commercial Partial 10/20/2015 (1:00) 10/21/2015 at 12:00 AM 10/21/2015
Misc
Partial Correction
10/07/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Partial Correction
10/07/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/07/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB;
Footing Inspection - Commercial Partial 10/21/2015 at 12:00 AM 10/21/2015
Misc
Partial Correction
10/21/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Partial Correction
10/21/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/21/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB; D/AC.8;
Underslab Plumbing Inspection - Commercial Partial 9/29/2015 (1:00) 10/23/2015 at 12:00 AM 10/23/2015
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Partial Correction
09/22/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/23/2015
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, GREASE WASTE, & VENT PIPING AT: ALL NORTH OF (AC.7) INCLUDING FLOOR SINK AT (1)/(A0.4) RELOCATED TO EAST PER RFI NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Footing Inspection - Commercial Not Ready 10/27/2015 (9:00) 10/27/2015 at 12:00 AM 10/27/2015
Misc
Partial Correction
10/21/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Partial Correction
10/21/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/21/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB; D/AC.8;
Underground Electrical Inspection - Commercial Partial 10/27/2015 10/27/2015 at 12:00 AM 10/27/2015
Misc
Partial Correction
10/27/2015
-6 FOUR INCH CONDUIT FOR PRIMARY CONDUCTORS APPROVED. RE-INFORCEMENT FOR UNDERMINED FOOTING WILL BE NECCESSARY.
Footing Inspection - Commercial Partial 10/29/2015 (9:45) 10/29/2015 at 12:00 AM 10/29/2015
Misc
Partial Correction
10/27/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Partial Correction
10/27/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/27/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB; D/AC.8;
Misc
Partial Correction
10/29/2015
OK TO POUR WHEN READY SPREAD FOOTING FOR STAIR WALL AT EX A2/AA.7;
Concrete Walls and Columns Inspection Partial 11/2/2015 at 12:00 AM 11/02/2015
Misc
Partial Correction
11/02/2015
OK TO POUR WHEN READY CONCRETE WALLS AT: ELEVATOR PIT WALLS; STAIR WALLS AT EX A2/AA.7;
Footing Inspection - Commercial Partial 11/19/2015 (8:00) 11/19/2015 at 12:00 AM 11/19/2015
Misc
Partial Correction
10/29/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Partial Correction
10/29/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/29/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB; D/AC.8;
Misc
Partial Correction
10/29/2015
OK TO POUR WHEN READY SPREAD FOOTING FOR STAIR WALL AT EX A2/AA.7;
Misc
Partial Correction
11/19/2015
NO ISSUES FOUND ON PREP TO POUR MASS 4'x12'x4' FOUNDATION OVER PREVIOUSLY-POURED FOOTING ALONGSIDE SOUTH WALL OF ELEVATOR SHAFT WALL. THIS POUR IS SITUATION-ADAPTED FROM SUPPLEMENTAL DWG. S26 DTD 11/9/15 TO SUPPORT ADDED COLUMN AND FLOOR SLAB DROPPED EDGE.
Underslab Plumbing Inspection - Commercial Not Ready 11/24/2015 11/24/2015 at 12:00 AM 11/24/2015
Misc
Resolved
11/24/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ;
Misc
Resolved
11/24/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
10/23/2015
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, GREASE WASTE, & VENT PIPING AT: ALL NORTH OF (AC.7) INCLUDING FLOOR SINK AT (1)/(A0.4) RELOCATED TO EAST PER RFI; UNDER-SLAB DWV AT SALON NOT READY -- UNCERTAINTY RE # OF SINKS REQUIRED. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Footing Inspection - Commercial Partial 12/22/2015 12/22/2015 12/22/2015
Misc
Partial Correction
11/19/2015
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Partial Correction
11/19/2015
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Partial Correction
11/19/2015
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB; D/AC.8;
Misc
Partial Correction
11/19/2015
OK TO POUR WHEN READY SPREAD FOOTING FOR STAIR WALL AT EX A2/AA.7;
Misc
Partial Correction
11/19/2015
NO ISSUES FOUND ON PREP TO POUR MASS 4'x12'x4' FOUNDATION OVER PREVIOUSLY-POURED FOOTING ALONGSIDE SOUTH WALL OF ELEVATOR SHAFT WALL. THIS POUR IS SITUATION-ADAPTED FROM SUPPLEMENTAL DWG. S26 DTD 11/9/15 TO SUPPORT ADDED COLUMN AND FLOOR SLAB DROPPED EDGE.
Misc
Partial Correction
12/22/2015
OK TO POUR WHEN READY THREE STRIP FOOTINGS AT ATRIUM RAMP AT (E)-(H) x EXIST (AD)-(AE)
Rough Framing Inspection - Commercial Partial 1/11/2016 01/11/2016
Misc
Partial Correction
01/11/2016
SHEATHING OF EXTERIOR WALLS OK TO COVER WHEN READY.
In-wall Inspection Partial 1/29/2016 1/29/2016 01/29/2016
Misc
Partial Correction
01/29/2016
OK TO ONE-SIDE WALL AT ELECTRICAL PANELS AT [C115];
Misc
Corrective Action Required
01/29/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATE 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Corrective Action Required
01/29/2016
AT CORRIDOR [205]: COMPLETE FASTENING OF STEEL COLUMNS TO ADJACENT STUDS
Rough Framing Inspection - Commercial Partial 1/29/2016 01/29/2016
Misc
Partial Correction
01/11/2016
SHEATHING OF EXTERIOR WALLS OK TO COVER WHEN READY INCLUDING AT C/5.2 TO B.5/5.2 TO B.5/1.8 TO D/1.8 TO D/AE - 10' SOUTH;
In-wall Inspection Failed 2/2/2016 2/2/2016 02/02/2016
Misc
Partial Correction
01/29/2016
OK TO ONE-SIDE WALL AT ELECTRICAL PANELS AT [C115];
Misc
Corrective Action Required
01/29/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATE 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Corrective Action Required
01/29/2016
AT CORRIDOR [205]: COMPLETE FASTENING OF STEEL COLUMNS TO ADJACENT STUDS TO PROVIDE CONTINUITY OF SEVERED TOP PLATES.
Rough Framing Inspection - Commercial Not Ready 2/11/2016 2/11/2016 02/11/2016
Misc
Partial Correction
01/29/2016
SHEATHING OF EXTERIOR WALLS OK TO COVER WHEN READY INCLUDING AT C/5.2 TO B.5/5.2 TO B.5/1.8 TO D/1.8 TO D/AE - 10' SOUTH;
In-wall Inspection Partial 2/12/2016 02/12/2016
Misc
Corrective Action Required
02/22/2016
Misc
Corrective Action Required
02/22/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATE 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Partial Correction
02/22/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
Rough Framing Inspection - Commercial Passed 2/12/2016 02/12/2016
Misc
Resolved
02/12/2016
SHEATHING OF EXTERIOR WALLS OK TO COVER WHEN READY INCLUDING AT C/5.2 TO B.5/5.2 TO B.5/1.8 TO D/1.8 TO D/AE - 10' SOUTH;
Underground Electrical Inspection - Commercial Passed 10/27/2015 02/12/2016
Misc
Resolved
02/12/2016
-6 FOUR INCH CONDUIT FOR PRIMARY CONDUCTORS APPROVED. RE-INFORCEMENT FOR UNDERMINED FOOTING WILL BE NECCESSARY.
Concrete Walls and Columns Inspection Passed 11/2/2015 02/12/2016
Misc
Resolved
02/12/2016
OK TO POUR WHEN READY CONCRETE WALLS AT: ELEVATOR PIT WALLS; STAIR WALLS AT EX A2/AA.7;
Footing Inspection - Commercial Passed 12/22/2015 02/12/2016
Misc
Resolved
02/12/2016
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: L/AD.8 TO L/4.5 TO L.5/4.5 TO L.5/5.7 TO L/5.7 TO L/7 TO L.4/7 TO L.4/8 TO K/8 TO K/9 TO J/9 TO J/10; TO C/10 TO C/9.6; C/9.6 TO C/5.5; C/5.5 TO C/5.2 TO B/5.2 TO B/1.8 TO B.5/1.8; B.5/1.8 TO D/1.8 TO D/AD.6 ; D/AD.6 TO D/1.8 TO B/1.8
Misc
Resolved
02/12/2016
OK TO POUR WHEN READY SECTION OF CONCRETE GRADE BEAM ON E/W LINE 5' S OF (AA) FROM (A2.5) TO (A3.8);
Misc
Resolved
02/12/2016
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: 2/E; 2/F; 2/G; 2/H; 3/H; 4/H; 5/D; 5/E; 5/F; 5/G; 5/H; D.5/8.1; E/7; G/7; PEDESTRIAN BRIDGE COLUMN FOOTINGS E.8/; E.8/B3; E.8/B4; E.8/B5; E.8/B6; E.8/B7; E.8/B8; M/5.8; N/4.4; B1-B2/BA-BB; D/AC.8;
Misc
Resolved
02/12/2016
OK TO POUR WHEN READY SPREAD FOOTING FOR STAIR WALL AT EX A2/AA.7;
Misc
Resolved
02/12/2016
NO ISSUES FOUND ON PREP TO POUR MASS 4'x12'x4' FOUNDATION OVER PREVIOUSLY-POURED FOOTING ALONGSIDE SOUTH WALL OF ELEVATOR SHAFT WALL. THIS POUR IS SITUATION-ADAPTED FROM SUPPLEMENTAL DWG. S26 DTD 11/9/15 TO SUPPORT ADDED COLUMN AND FLOOR SLAB DROPPED EDGE.
Misc
Resolved
02/12/2016
OK TO POUR WHEN READY THREE STRIP FOOTINGS AT ATRIUM RAMP AT (E)-(H) x EXIST (AD)-(AE)
Underslab Plumbing Inspection - Commercial Passed 11/25/2015 02/12/2016
Misc
Partial Correction
11/24/2015
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, GREASE WASTE, & VENT PIPING AT: ALL NORTH OF (AC.7) INCLUDING FLOOR SINK AT (1)/(A0.4) RELOCATED TO EAST PER RFI; UNDER-SLAB DWV AT SALON NOT READY -- UNCERTAINTY RE # OF SINKS REQUIRED. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
In-wall Inspection Partial 2/22/2016 02/22/2016
Misc
Resolved
02/22/2016
OK TO ONE-SIDE WALL AT ELECTRICAL PANELS AT [C115];
Misc
Resolved
02/22/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATE 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Resolved
02/22/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
All Rough Inspection - Commercial Partial 2/22/2016 2/22/2016 02/22/2016
Misc
Partial Correction
02/22/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
Misc
Partial Correction
02/22/2016
OK TO ONE-SIDE WALL AT ELECTRICAL PANELS AT [C115];
Misc
Corrective Action Required
02/22/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATES 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Partial Correction
02/22/2016
OK TO INSTALL ABOVE-CEILING INSULATION BELOW ROOF AT: C107-C112;
Misc
Corrective Action Required
02/22/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES
Misc
Partial Correction
02/22/2016
OK TO COVER WHEN READY WALLS AND CEILING AT TIE-IN OF CORR [205] @ (B1)
All Rough Inspection - Commercial Not Ready 2/24/2016 2/24/2016 02/24/2016
Misc
Partial Correction
02/22/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
Misc
Partial Correction
02/22/2016
OK TO ONE-SIDE WALL AT ELECTRICAL PANELS AT [C115];
Misc
Corrective Action Required
02/22/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATES 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Partial Correction
02/22/2016
OK TO INSTALL ABOVE-CEILING INSULATION BELOW ROOF AT: C107-C112;
Misc
Corrective Action Required
02/22/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES
Misc
Partial Correction
02/22/2016
OK TO COVER WHEN READY WALLS AND CEILING AT TIE-IN OF CORR [205] @ (B1)
Sprinkler - Hydrostatic Test Passed 2/25/2016 02/25/2016
All Rough Inspection - Commercial Partial 2/25/2016 2/25/2016 02/25/2016
Misc
Partial Correction
02/24/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
Misc
Partial Correction
02/24/2016
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: [C115]; [C116]; [C119]; [C120];
Misc
Resolved
02/25/2016
AT [C119]: 1) COMPLETE STRUCTURAL TIE-DOWNS 2) TIE SEVERED TOP PLATES 3) PROTECT PVC PLUMBING PIPE 4) FIRE-BLOCK TOP PLATE PENETRATIONS
Misc
Partial Correction
02/24/2016
OK TO INSTALL ABOVE-CEILING INSULATION BELOW ROOF AT: C107-C112;
Misc
Corrective Action Required
02/24/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES
Misc
Partial Correction
02/24/2016
OK TO COVER WHEN READY WALLS AND CEILING AT TIE-IN OF CORR [205] @ (B1)
All Rough Inspection - Commercial Partial 3/1/2016 3/1/2016 03/01/2016
Misc
Partial Correction
02/25/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
Misc
Partial Correction
02/25/2016
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: [C115]; [C116]; [C119]; [C120];
Misc
Partial Correction
02/25/2016
OK TO INSTALL ABOVE-CEILING INSULATION BELOW ROOF AT: C107-C112;
Misc
Corrective Action Required
02/25/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES
Misc
Partial Correction
02/25/2016
OK TO COVER WHEN READY WALLS AND CEILING AT TIE-IN OF CORR [205] @ (B1)
All Rough Inspection - Commercial Partial 3/2/2016 03/02/2016
Misc
Resolved
03/02/2016
PER 2/11/16 ENGINEER REPORT VIA E-MAIL CONTINUITY OF TOP PLATES INTERRUPTED AT COLUMNS AT CORRIDOR [205] IS NOT REQURED DUE TO DESIGN CONFIGURATION.
Misc
Partial Correction
03/01/2016
AFTER FIRE-BLOCKING IS COMPLETED OK TO COVER WHEN READY FRAMING AND ENCLOSED SYSTEMS AT: WALLS ONLY AT [C102] LOBBY AND [C111] KITCHEN; CEILING AND WALLS AT [109] DINING, [C115], [C116], [C119], [C120];
Misc
Resolved
03/02/2016
OK TO INSTALL ABOVE-CEILING INSULATION BELOW ROOF AND CEILING GWB AT: C107-C112;
Misc
Corrective Action Required
03/01/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES
Misc
Partial Correction
03/01/2016
OK TO COVER WHEN READY WALLS AND CEILING AT TIE-IN OF CORR [205] @ (B1)
All Rough Inspection - Commercial Partial 3/3/2016 3/3/2016 03/03/2016
Misc
Corrective Action Required
03/03/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES.
Misc
Partial Correction
03/03/2016
OK TO COVER WHEN READY FRAMING AND ENCLOSED SYSTEMS AT: WALLS ONLY AT [C102] LOBBY AND [C111] KITCHEN; CEILING AND WALLS AT [109] DINING, [C115], [C116], [C119], [C120]; WALLS @ [125], [126], [127];
Misc
Resolved
03/03/2016
OK TO COVER WHEN READY WALLS AND CEILING AT TIE-IN OF CORR [205] @ (B1)
All Rough Inspection - Commercial Partial 3/4/2016 03/04/2016
Misc
Corrective Action Required
03/03/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES.
Misc
Partial Correction
03/03/2016
OK TO COVER WHEN READY FRAMING AND ENCLOSED SYSTEMS AT: [C102] LOBBY; [104] CORRIDOR; [109] DINING; [C111] KITCHEN + VESTIBULE @ SW; [114] CORRIDOR; [C115], [C116], [C119], [C120]; [C125]; [C126]; [C127];
Rated Assembly Inspection Partial 3/4/2016 03/04/2016
Misc
Partial Correction
03/04/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: WALLS @ [119] & [120];
All Rough Inspection - Commercial Partial 3/9/2016 3/9/2016 03/09/2016
Misc
Resolved
03/09/2016
IBC 700: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES, TOPS & BOTTOMS OF CHASES / DEAD SPACES, INTERFACES OF WALLS WITH FLOOR / CEILING / FUR-DOWN SPACES.
Misc
Partial Correction
03/04/2016
OK TO COVER WHEN READY WOOD FRAMING AND ENCLOSED SYSTEMS AT: [C102] LOBBY; [104] CORRIDOR; [109] DINING; [C111] KITCHEN + VESTIBULE @ SW; [114] CORRIDOR; [C115], [C116], [C119], [C120]; [C125]; [C126]; [C127]; [C105]; [C106]; [C107]; STAIR 1 WALLS BUT NOT LID UNTIL TRUSS GUSSETS ARE CLARIFIED
Misc
Partial Correction
03/09/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL/SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: COLUMN WRAPS @ CORRIDOR [C205]; [R101] THRU [R107];
All Rough Inspection - Commercial Partial 3/17/2016 3/17/2016 03/17/2016
Misc
Partial Correction
03/09/2016
OK TO COVER WHEN READY WOOD FRAMING AND ENCLOSED SYSTEMS AT: [C102] LOBBY; [104] CORRIDOR; [109] DINING; [C111] KITCHEN + VESTIBULE @ SW; [114] CORRIDOR; [C115], [C116], [C119], [C120]; [C125]; [C126]; [C127]; [C105]; [C106]; [C107]; STAIR 1 WALLS AND LID;
Misc
Partial Correction
03/09/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL/SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: COLUMN WRAPS @ CORRIDOR [C205]; [R101] THRU [R107];
Above Ceiling Inspection Partial 3/24/2016 3/24/2016 03/24/2016
Misc
Partial Correction
03/24/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C105; C106;
In-wall Inspection Partial 3/24/2016 03/24/2016
Misc
Partial Correction
03/24/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT SPACES: WALLS SURROUNDING ADA RAMP;
Misc
Partial Correction
03/24/2016
OK TO COVER WHEN READY WOOD WALL FRAMING + ENCLOSED SYSTEMS ROUGH-IN AT LOCATIONS: C123;
Above Ceiling Inspection Partial 3/29/2016 3/29/2016 03/29/2016
Misc
Partial Correction
03/24/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR];
Rated Assembly Inspection Partial 3/29/2016 03/29/2016
Misc
Partial Correction
03/04/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: WALLS @ [119] & [120]; WALLS & LID @ [STAIR #1];
Above Ceiling Inspection Partial 3/31/2016 3/31/2016 03/31/2016
Misc
Partial Correction
03/29/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH;
Water Service Inspection Passed 4/5/2016 (8:45) 4/5/2016 04/05/2016
Underground Plumbing Inspection - Commercial Failed 4/5/2016 4/5/2016 04/05/2016
Misc
Corrective Action Required
04/05/2016
ANTI-BUOYANCY SLAB NOT INSTALLED PER APPROVED PLUMBING DRAWING.
Above Ceiling Inspection Partial 4/11/2016 4/11/2016 04/11/2016
Misc
Partial Correction
03/31/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
04/11/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY;
Hood/Duct Inspection Not Ready 4/11/2016 4/11/2016 04/11/2016
Hood/Duct Inspection Partial 4/12/2016 4/12/2016 04/12/2016
Misc
Partial Correction
04/12/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS APPROVED;
Hood/Duct Inspection Not Ready 4/14/2016 04/14/2016
Misc
Partial Correction
04/12/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS APPROVED;
Above Ceiling Inspection Partial 4/19/2016 4/19/2016 04/19/2016
Misc
Partial Correction
04/11/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
04/11/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Hood/Duct Inspection Partial 4/19/2016 04/19/2016
Misc
Partial Correction
04/14/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS OF SEAMS APPROVED; FIELD WELDS OF JOINTS IN PROGRESS;
Hood/Duct Inspection Partial 4/20/2016 04/20/2016
Misc
Partial Correction
04/19/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS AND FIELD WELDS OF SEAMS AND JOINTS APPROVED; OK TO APPLY FIRE WRAP WHEN READY
Misc
Corrective Action Required
04/20/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Hood/Duct Inspection Partial 4/21/2016 04/21/2016
Misc
Partial Correction
04/20/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS AND FIELD WELDS OF SEAMS AND JOINTS APPROVED; OK TO APPLY FIRE WRAP WHEN READY
Misc
Corrective Action Required
04/20/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Hood/Duct Inspection Partial 4/22/2016 04/22/2016
Misc
Partial Correction
04/21/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS AND FIELD WELDS OF SEAMS AND JOINTS APPROVED; FIRE WRAP 1ST LAYER APPROVED -- OK TO APPLY 2ND LAYER WHEN READY
Misc
Corrective Action Required
04/21/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Hood/Duct Inspection Partial 4/26/2016 04/26/2016
Misc
Partial Correction
04/22/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS AND FIELD WELDS OF SEAMS AND JOINTS APPROVED; FIRE WRAP 1ST LAYER APPROVED -- OK TO APPLY 2ND LAYER WHEN READY
Misc
Corrective Action Required
04/22/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Partial Correction
04/26/2016
EXHAUST DUCT FROM DISHWASHER LOCATION TO EXIT AT ROOF: OK TO COVER 1ST LAYER WHEN READY
Above Ceiling Inspection Partial 4/27/2016 4/27/2016 04/27/2016
Misc
Partial Correction
04/26/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
04/26/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Misc
Partial Correction
04/26/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
04/26/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C102; C103; C104; C127; R103; [R101; R012; R107; C101; C105; C106; C107; C112; C117; C118; C121; C123; C126;
Gas Piping Inspection - Commercial Partial 4/29/2016 4/29/2016 04/29/2016
Misc
Partial Correction
04/29/2016
GAS PIPING PRESSURE TEST HELD STEADY AT >10 PSI FOR >10 MIN. APPROVED.
Misc
Corrective Action Required
04/29/2016
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING.
Misc
Corrective Action Required
04/29/2016
IFGC 404.8: BEFORE FINAL INSPECTION METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Above Ceiling Inspection Partial 4/29/2016 04/29/2016
Misc
Partial Correction
04/27/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107]; CANOPY AT MAIN ENTRANCE;
Misc
Partial Correction
04/27/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Misc
Partial Correction
04/27/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
04/27/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C102; C103; C104; C127; R103; [R101; R012; R107; C101; C105; C106; C107; C112; C117; C118; C121; C123; C126;
Above Ceiling Inspection Not Ready 5/4/2016 5/4/2016 05/04/2016
Misc
Partial Correction
04/29/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107]; CANOPY AT MAIN ENTRANCE;
Misc
Partial Correction
04/29/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Misc
Partial Correction
04/29/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
04/29/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C102; C103; C104; C127; R103; [R101; R012; R107; C101; C105; C106; C107; C112; C117; C118; C121; C123; C126;
Footing Inspection - Commercial Passed 5/5/2016 (11:30) 5/5/2016 05/05/2016
Above Ceiling Inspection Partial 5/6/2016 5/6/2016 05/06/2016
Misc
Partial Correction
05/04/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107]; CANOPY AT MAIN ENTRANCE;
Misc
Partial Correction
05/04/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Misc
Partial Correction
05/04/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
05/04/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C102; C103; C104; C127; R103; [R101; R012; R107; C101; C105; C106; C107; C112; C117; C118; C121; C123; C126; C111 EXCLUDING WEST 4' AND RECESS ADJACENT TO ELEVATOR LOBBY;
Electrical Service Inspection Passed 5/6/2016 5/6/2016 05/06/2016
Above Ceiling Inspection Partial 5/10/2016 5/11/2016 05/11/2016
Misc
Partial Correction
05/06/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107]; CANOPY AT MAIN ENTRANCE;
Misc
Partial Correction
05/06/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Misc
Partial Correction
05/06/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Partial Correction
05/06/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C102; C103; C104; C127; R103; [R101; R012; R107; C101; C105; C106; C107; C112; C117; C118; C121; C123; C126; KITCHEN C111 OK EXCEPT EXCLUDE... - WEST 4' NOT READY (CUT BORDER TILE OK HERE) - RECESS TO ELEVATOR LOBBY NOT READY
Above Ceiling Inspection Passed 5/25/2016 5/25/2016 05/25/2016
Misc
Resolved
05/25/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107]; CANOPY AT MAIN ENTRANCE;
Misc
Resolved
05/25/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C-102; C-103; C-104; C-127; R-103;
Misc
Resolved
05/25/2016
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: [C105]; [C106]; [102]; [125]; [NORTH STORAGE ROOM @ 2ND FLOOR]; RAMP[105]; CORRIDOR[110] AFTER INSULATION IS COMPLETED AT NORTH; SOFFITS @ [C107];
Misc
Resolved
05/25/2016
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PEDESTRIAN BRIDGE [C205] CORRIDOR ONLY; C102; C103; C104; C127; R103; [R101; R012; R107; C101; C105; C106; C107; C112; C117; C118; C121; C123; C126; KITCHEN C111 OK EXCEPT EXCLUDE... - WEST 4' NOT READY (CUT BORDER TILE OK HERE) - RECESS TO ELEVATOR LOBBY NOT READY
Footing Inspection - Commercial Passed 6/1/2016 (1:00) 6/1/2016 06/01/2016
Alarm Test Passed 6/6/2016 06/06/2016
Alternate Protection Systems Inspection Passed 6/6/2016 06/06/2016
Occupancy Inspection - Fire Passed 6/6/2016 06/06/2016
Occupancy Inspection - Codes Commercial Failed 6/6/2016 6/6/2016 06/06/2016
Misc
Corrective Action Required
06/06/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/06/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY FIRE DEPT ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Corrective Action Required
06/06/2016
ROOFTOP: -PARAPET CUT OPEN AT ROOF NW -SLIPSHEETS REQ'D AT BALLY CONDENSING UNIT -DESIGNATE EF'S WITH PERMANENT STICKERS -HINGE KITS REQ'D ON GREASE EF'S -ALL GAS PIPING DRIP LEG CAPS MUST BE REMOVEABLE -TYPE 2 EF DISCHARGES UNDER ROOF OVERHANG -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Corrective Action Required
06/06/2016
RTU-7: -NEW GAS PIPE TO BE PAINTED -CLAMP EXISTING GAS PIPE TO SUPPORTS -ELECT RECEPT REQUIRED -FINAL CLEAN ROOF
Misc
Corrective Action Required
06/06/2016
ABOVE COOLER AT ELEVATED WALKWAY LEVEL: -UNTERMINATED MC COIL ABOVE -UNUSED OPENING AT J-BOX -STRAP MC WITHIN 12" OF BOXES
Misc
Corrective Action Required
06/06/2016
COMPLETE ELEVATOR CONSTRUCTION
Misc
Corrective Action Required
06/06/2016
GUARD AND HANDRAIL REQUIRED AT EXTERIOR STAIR AT SW
Misc
Corrective Action Required
06/06/2016
GUARD REQUIRED AT INTERIOR STAIR SW
Misc
Corrective Action Required
06/06/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC
Misc
Corrective Action Required
06/06/2016
RESTROOM AT ELEVATOR LOBBY: WATER CLOSET CLEARANCE TO WALL NOT 16"-18"
Misc
Corrective Action Required
06/06/2016
CHASE AND FIRESTOPPING REQ'D AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
06/06/2016
ELECT WHIPS AT CONDENSERS EXTERIOR NW: SECURE TO BUILDING WITHIN 12" OF ENTRY TO DISCONNECT.
Misc
Corrective Action Required
06/06/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
06/06/2016
PLACE PERMANENT CIRCUIT SCHEDULES AT ELECTRICAL PANELS. DESIGNATE PANELS PER DRAWINGS.
Misc
Corrective Action Required
06/06/2016
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO RESIDENTS OR PUBLIC PRIOR TO APPROVAL.
Occupancy Inspection - Water Utilities Temporary C of O 6/8/2016 06/08/2016
Occupancy Inspection - Planning Temporary C of O 06/08/2016
Occupancy Inspection - Engineering Temporary C of O 6/15/2016 06/08/2016
Occupancy Inspection - Codes Commercial Not Ready 6/9/2016 06/09/2016
Misc
Corrective Action Required
06/06/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/06/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY FIRE DEPT ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Corrective Action Required
06/06/2016
ROOFTOP: -PARAPET CUT OPEN AT ROOF NW -SLIPSHEETS REQ'D AT BALLY CONDENSING UNIT -DESIGNATE EF'S WITH PERMANENT STICKERS -HINGE KITS REQ'D ON GREASE EF'S -ALL GAS PIPING DRIP LEG CAPS MUST BE REMOVEABLE -TYPE 2 EF DISCHARGES UNDER ROOF OVERHANG -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Corrective Action Required
06/06/2016
RTU-7: -NEW GAS PIPE TO BE PAINTED -CLAMP EXISTING GAS PIPE TO SUPPORTS -ELECT RECEPT REQUIRED -FINAL CLEAN ROOF
Misc
Corrective Action Required
06/06/2016
ABOVE COOLER AT ELEVATED WALKWAY LEVEL: -UNTERMINATED MC COIL ABOVE -UNUSED OPENING AT J-BOX -STRAP MC WITHIN 12" OF BOXES
Misc
Corrective Action Required
06/06/2016
COMPLETE ELEVATOR CONSTRUCTION
Misc
Corrective Action Required
06/06/2016
GUARD AND HANDRAIL REQUIRED AT EXTERIOR STAIR AT SW
Misc
Corrective Action Required
06/06/2016
GUARD REQUIRED AT INTERIOR STAIR SW
Misc
Corrective Action Required
06/06/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC
Misc
Corrective Action Required
06/06/2016
RESTROOM AT ELEVATOR LOBBY: WATER CLOSET CLEARANCE TO WALL NOT 16"-18"
Misc
Corrective Action Required
06/06/2016
CHASE AND FIRESTOPPING REQ'D AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
06/06/2016
ELECT WHIPS AT CONDENSERS EXTERIOR NW: SECURE TO BUILDING WITHIN 12" OF ENTRY TO DISCONNECT.
Misc
Corrective Action Required
06/06/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
06/06/2016
PLACE PERMANENT CIRCUIT SCHEDULES AT ELECTRICAL PANELS. DESIGNATE PANELS PER DRAWINGS.
Misc
Corrective Action Required
06/06/2016
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO RESIDENTS OR PUBLIC PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Temporary C of O 6/10/2016 06/10/2016
Misc
Corrective Action Required
06/09/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/09/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY FIRE DEPT ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Corrective Action Required
06/09/2016
ROOFTOP: -HINGE KITS REQ'D ON GREASE EF'S -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Resolved
06/10/2016
RTU-7: -NEW GAS PIPE TO BE PAINTED -CLAMP EXISTING GAS PIPE TO SUPPORTS -ELECT RECEPT REQUIRED -FINAL CLEAN ROOF
Misc
Resolved
06/10/2016
ABOVE COOLER AT ELEVATED WALKWAY LEVEL: -UNTERMINATED MC COIL ABOVE -UNUSED OPENING AT J-BOX -STRAP MC WITHIN 12" OF BOXES
Misc
Corrective Action Required
06/09/2016
PROVIDE COPY OF ELEVATOR INSPECTION APPROVAL
Misc
Corrective Action Required
06/09/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW
Misc
Corrective Action Required
06/09/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW
Misc
Corrective Action Required
06/09/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC -- TO BE VERIFIED
Misc
Resolved
06/10/2016
RESTROOM AT ELEVATOR LOBBY: WATER CLOSET CLEARANCE TO WALL NOT 16"-18"
Misc
Corrective Action Required
06/09/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Resolved
06/10/2016
ELECT WHIPS AT CONDENSERS EXTERIOR NW: SECURE TO BUILDING WITHIN 12" OF ENTRY TO DISCONNECT.
Misc
Corrective Action Required
06/09/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
06/09/2016
PLACE PERMANENT CIRCUIT SCHEDULES AT ELECTRICAL PANELS. DESIGNATE PANELS PER DRAWINGS.
Misc
Resolved
06/10/2016
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO RESIDENTS OR PUBLIC PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Temporary C of O 6/15/2016 06/15/2016
Misc
Corrective Action Required
06/10/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/10/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY FIRE DEPT ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Corrective Action Required
06/10/2016
ROOFTOP: -HINGE KITS REQ'D ON GREASE EF'S -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Resolved
06/15/2016
PROVIDE COPY OF ELEVATOR INSPECTION APPROVAL
Misc
Corrective Action Required
06/10/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
06/10/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
06/10/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC -- TO BE VERIFIED
Misc
Corrective Action Required
06/10/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
06/10/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Resolved
06/15/2016
PLACE PERMANENT CIRCUIT SCHEDULES AT ELECTRICAL PANELS. DESIGNATE PANELS PER DRAWINGS.
Occupancy Inspection - Codes Commercial Temporary C of O 7/6/2016 06/17/2016
Misc
Corrective Action Required
06/15/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/15/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY FIRE DEPT ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Corrective Action Required
06/15/2016
ROOFTOP: -HINGE KITS REQ'D ON GREASE EF'S -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Corrective Action Required
06/15/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
06/15/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
06/15/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC -- TO BE VERIFIED
Misc
Corrective Action Required
06/15/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
06/15/2016
SEAL ALL EXTERIOR WALL OPENINGS
All Rough Inspection - Commercial Passed 3/17/2016 07/07/2016
Misc
Resolved
07/07/2016
OK TO COVER WHEN READY WOOD FRAMING AND ENCLOSED SYSTEMS AT: [C102] LOBBY; [104] CORRIDOR; [109] DINING; [C111] KITCHEN + VESTIBULE @ SW; [114] CORRIDOR; [C115], [C116], [C119], [C120]; [C125]; [C126]; [C127]; [C105]; [C106]; [C107]; STAIR 1 WALLS AND LID;
Misc
Resolved
07/07/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL/SOFFIT FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: COLUMN WRAPS @ CORRIDOR [C205]; [R101] THRU [R107];
Gas Piping Inspection - Commercial Passed 4/29/2016 07/07/2016
Misc
Resolved
07/07/2016
GAS PIPING PRESSURE TEST HELD STEADY AT >10 PSI FOR >10 MIN. APPROVED.
Misc
Resolved
07/07/2016
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED AND RE-INSTALLED FOR CLEANING.
Misc
Resolved
07/07/2016
IFGC 404.8: BEFORE FINAL INSPECTION METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Hood/Duct Inspection Passed 4/26/2016 07/07/2016
Misc
Resolved
07/07/2016
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS AND FIELD WELDS OF SEAMS AND JOINTS APPROVED; FIRE WRAP 1ST LAYER APPROVED -- OK TO APPLY 2ND LAYER WHEN READY
Misc
Corrective Action Required
04/26/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Misc
Resolved
07/07/2016
EXHAUST DUCT FROM DISHWASHER LOCATION TO EXIT AT ROOF: OK TO COVER 1ST LAYER WHEN READY
In-wall Inspection Passed 3/24/2016 07/07/2016
Misc
Resolved
07/07/2016
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT SPACES: WALLS SURROUNDING ADA RAMP;
Misc
Resolved
07/07/2016
OK TO COVER WHEN READY WOOD WALL FRAMING + ENCLOSED SYSTEMS ROUGH-IN AT LOCATIONS: C123;
Miscellaneous Inspection Passed 6/2/2016 07/07/2016
Rated Assembly Inspection Passed 3/29/2016 07/07/2016
Misc
Resolved
07/07/2016
GWB AT 1 HR FIRE-RATED WALLS: OK TO TAPE, MUD, & FIRE-SEAL WHEN READY 5/8" TYPE X GWB INSTALLATION @ FOLLOWING LOCATIONS: WALLS @ [119] & [120]; WALLS & LID @ [STAIR #1];
Underground Plumbing Inspection - Commercial Passed 4/7/2016 4/5/2016 07/07/2016
Misc
Resolved
07/07/2016
ANTI-BUOYANCY SLAB NOT INSTALLED PER APPROVED PLUMBING DRAWING.
Occupancy Inspection - Codes Commercial Not Ready 7/7/2016 07/07/2016
Misc
Corrective Action Required
06/17/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC -- TO BE VERIFIED
Misc
Corrective Action Required
06/17/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
06/17/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
06/17/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/17/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY FIRE DEPT ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Corrective Action Required
06/17/2016
ROOFTOP: -HINGE KITS REQ'D ON GREASE EF'S -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Corrective Action Required
06/17/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
06/17/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/07/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Codes Commercial Temporary C of O 7/11/2016 07/11/2016
Misc
Resolved
07/11/2016
BACKFLOW PROTECTION REQ'D AT ICEMAKER, COFFEE MAKERS, CARBONATED BEVERAGE FEED LINE, ETC -- TO BE VERIFIED
Misc
Corrective Action Required
07/07/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
07/07/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
07/07/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
07/07/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY WATER DEPT ISSUES RESOLVE ANY PUBLIC WORKS DEPT ISSUES
Misc
Resolved
07/11/2016
ROOFTOP: -HINGE KITS REQ'D ON GREASE EF'S -FINAL CLEAN ROOF SURFACE OF UNUSED MATERIAL AND DEBRIS
Misc
Corrective Action Required
07/07/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/07/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/07/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Sidewalk Inspection Passed 07/11/2016
Occupancy Inspection - Engineering Passed 7/11/2016 07/11/2016
Occupancy Inspection - Codes Commercial Partial 7/11/2016 07/11/2016
Misc
Corrective Action Required
07/11/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
07/11/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
07/11/2016
COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
07/11/2016
RESOLVE ANY PLANNING ISSUES RESOLVE ANY WATER DEPT ISSUES
Misc
Corrective Action Required
07/11/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/11/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/11/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Water Utilities Passed 7/11/2016 07/11/2016
Occupancy Inspection - Codes Commercial Partial 8/16/2016 08/16/2016
Misc
Corrective Action Required
07/11/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Resolved
08/16/2016
SEAL ALL EXTERIOR WALL OPENINGS
Misc
Corrective Action Required
07/11/2016
COMPLETE FINISH SITEWORK; RESOLVE ANY PLANNING ISSUES
Misc
Resolved
08/16/2016
RESOLVE ANY PLANNING ISSUES
Misc
Corrective Action Required
07/11/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/11/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Corrective Action Required
07/11/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Codes Commercial Temporary C of O 8/24/2016 08/24/2016
Misc
Resolved
08/24/2016
FIRESTOP HORIZONTAL CHASE AT ELEVATOR MACHINE ROOM
Misc
Corrective Action Required
08/16/2016
COMPLETE FINISH SITEWORK; COMPLETE AND OBTAIN APPROVAL ON TRASH ENCLOSURE; RESOLVE ANY PLANNING ISSUES.
Misc
Resolved
08/24/2016
COMPLIANT HANDRAILS REQUIRED AT EXTERIOR STAIR AT SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Resolved
08/24/2016
COMPLIANT GUARDS AND HANDRAILS REQUIRED AT INTERIOR STAIR SW AND RAMP SW. TEMPORARY PROVISONS ARE ACCEPTABLE.
Misc
Resolved
08/24/2016
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBB-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE. SMOKE CAPTURE TEST TO BE CERTIFIED BY 3RD PARTY OR WITNESSED BY INSPECTOR BEFORE ANY USE IS APPROVED.
Occupancy Inspection - Codes Commercial Temporary C of O 9/8/2016 09/08/2016
Misc
Corrective Action Required
08/24/2016
COMPLETE FINISH SITEWORK; COMPLETE AND OBTAIN APPROVAL ON TRASH ENCLOSURE; RESOLVE ANY PLANNING ISSUES.
Occupancy Inspection - Planning Passed 9/22/2016 09/22/2016
Investigation Inspection Complete 9/22/2016 09/22/2016
Occupancy Inspection - Codes Commercial Full C of O 9/22/2016 09/22/2016
Misc
Resolved
09/22/2016
COMPLETE FINISH SITEWORK; COMPLETE AND OBTAIN APPROVAL ON TRASH ENCLOSURE; RESOLVE ANY PLANNING ISSUES.
Documents & Images
Date Uploaded File Type Document Name
01/08/2015 Letter Fire Building Plan Review
01/19/2015 Letter Codes P/R Corrections Document
02/02/2015 Letter Fire Building Plan Review
02/10/2015 Letter Codes Plan Review Conditions
02/10/2015 Letter Fire Building Plan Review
06/02/2015 Receipt Receipt for transaction: 2015-002075
06/02/2015 Letter Codes Plan Review Conditions
06/02/2015 Letter Codes Plan Review Conditions
06/02/2015 Letter Codes Building Permit
09/03/2015 Letter Inspection Summary
09/04/2015 Letter Inspection Summary
09/09/2015 Letter Inspection Summary
09/10/2015 Letter Inspection Summary
09/11/2015 Letter Inspection Summary
09/12/2015 Letter Inspection Summary
09/16/2015 Letter Inspection Summary
09/17/2015 Letter Inspection Summary
09/18/2015 Letter Fire Building Plan Review
09/22/2015 Letter Inspection Summary
09/28/2015 Letter Inspection Summary
09/29/2015 Letter Inspection Summary
10/07/2015 Letter Inspection Summary
10/19/2015 Letter Inspection Summary
10/21/2015 Letter Inspection Summary
10/23/2015 Letter Inspection Summary
10/29/2015 Letter Inspection Summary
11/02/2015 Letter Inspection Summary
11/19/2015 Letter Inspection Summary
12/22/2015 Letter Inspection Summary
01/11/2016 Letter Inspection Summary
02/02/2016 Letter Inspection Summary
02/12/2016 Letter Inspection Summary
02/16/2016 Letter DOC021616-002
02/22/2016 Letter Inspection Summary
02/25/2016 Letter Inspection Summary
03/02/2016 Letter Inspection Summary
03/03/2016 Letter Inspection Summary
03/04/2016 Letter Inspection Summary
03/09/2016 Letter Inspection Summary
03/17/2016 Letter Inspection Summary
03/24/2016 Letter Inspection Summary
03/29/2016 Letter Inspection Summary
03/31/2016 Letter Inspection Summary
04/05/2016 Letter Inspection Summary
04/05/2016 Letter Inspection Summary
04/11/2016 Letter Inspection Summary
04/12/2016 Letter Inspection Summary
04/18/2016 Porte Cochere Steel Fireproofing
04/19/2016 Letter Inspection Summary
04/20/2016 Letter Inspection Summary
04/22/2016 Letter Inspection Summary
04/26/2016 Letter Inspection Summary
04/27/2016 Letter Inspection Summary
04/29/2016 Letter Inspection Summary
05/05/2016 Letter Inspection Summary
05/06/2016 Letter Inspection Summary
05/11/2016 Letter Inspection Summary
05/25/2016 Letter Inspection Summary
06/01/2016 Letter Inspection Summary
06/06/2016 Letter Inspection Summary
06/09/2016 Letter Inspection Summary
06/10/2016 Letter Codes Temporary Certificate of Occupancy
06/10/2016 Letter Codes Temporary Certificate of Occupancy
06/15/2016 Letter Codes Temporary Certificate of Occupancy
06/17/2016 Letter Codes Temporary Certificate of Occupancy
07/11/2016 Letter Codes Temporary Certificate of Occupancy
07/13/2016 Letter DOC071316-002
07/13/2016 Letter DOC071316-003
08/24/2016 Letter Codes Temporary Certificate of Occupancy
09/08/2016 Letter Codes Temporary Certificate of Occupancy
09/22/2016 Letter Field Certificate of Occupancy
09/23/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home