Permit Application Status

PRCOM20143253


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20143253
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS
11/21/2014
01/06/2015
04/09/2015
Locations
Contacts
MCCOWN GORDON CONSTRUCTION LLC, Address:850 MAIN ST, Phone:(816) 960-1111  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
HEARTLAND ELECTRIC CORPORATION, Address:947 LOCUST HILL CIR, Phone:(816) 318-8500  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/16/2015
Brian Austerman
Misc
Corrective Action Required
03/16/2015

Released without comment
Licensed Contractors Approved 12/05/2014 12/31/2014
Joe Frogge
LC - General Contractor
Corrective Action Required
11/26/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/26/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 12/05/2014 12/04/2014
Mike Weisenborn
Construction documents for fire alarm systems
Corrective Action Required
11/24/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans if changes are required
Construction documents - Fire protection systems
Corrective Action Required
11/24/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans showing changes if required
Building Plan Review Approved with Conditions 12/05/2014 12/04/2014
Mike Weisenborn
License Tax Application
Corrective Action Required
11/26/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment for informational purposes.
Misc
Resolved
12/01/2014

2012 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: This building has been classified as Type IA. Cover sheet has been amended by hand.
NEC - Patient Care - Grounding of receptacles
Resolved
12/01/2014

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B).(A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118.(B) Insulated Equipment Grounding Conductor.(1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A).1. The grounding terminals of all receptacles.2. Metal Boxes and enclosures containing receptacles.3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts.(refer code for exceptions)(2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in exam rooms will have redundant ground system. Email or letter may be provided that can be attached to drawing set. 12/1/14 - clarified via email
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,319.60 $1,319.60 Paid 01/06/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 1/27/2015 1/27/2015 at 12:00 AM 01/27/2015
Misc
Corrective Action Required
01/27/2015
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. COLORADO JIMS DO NOT SECURE MC TO RESIST TUGGING. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
In-wall Inspection Partial 1/29/2015 1/29/2015 at 12:00 AM 01/29/2015
Misc
Resolved
01/29/2015
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. COLORADO JIMS DO NOT SECURE MC TO RESIST TUGGING. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
Misc
Partial Correction
01/29/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PHASE 1A SPACES/WALLS;
Above Ceiling Inspection Partial 2/27/2015 2/27/2015 at 12:00 AM 02/27/2015
Misc
Partial Correction
02/27/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 252; 256; 259; 260; 262; NOT APPROVED: 239 - WORK IN PROGRESS 246 - RESTORE FIRE-PROOFING AT WF BEAM 261 - RESTORE RETURN AIR DUCT INSULATION
Final Inspection - Commercial Partial 3/2/2015 3/2/2015 at 12:00 AM 03/02/2015
Misc
Partial Correction
03/02/2015
FOLLOWING NEW OR MODIFIED SPACES ARE OK TO SET UP FOR BUSINESS OPERATIONS: 2C205; 239; 246; 250; 252; 253; 254; 259; 260; 261; 262; ELECTRCIAL RECEPTACLES AT DEMOUNTABLE SYSTEM MODULES TO BE TESTED WHEN READY. FIRE DEPARTMENT APPROVAL FOR USE & OCCUPANCY YET TO BE OBTAINED.
Alarm Test Partial 3/3/2015 at 7:00 AM 03/03/2015
Final Inspection - Commercial Partial 3/5/2015 at 12:00 AM 03/05/2015
Misc
Partial Correction
03/02/2015
FOLLOWING NEW OR MODIFIED SPACES ARE OK TO SET UP FOR BUSINESS OPERATIONS: 2C205; 239; 246; 250; 252; 253; 254; 259; 260; 261; 262; SOME ELECTRCIAL RECEPTACLES AT DEMOUNTABLE SYSTEM MODULES ARE DEFECTIVE. TO BE RE-INSPECTED.
Final Inspection - Commercial Partial 3/6/2015 at 12:00 AM 03/06/2015
Misc
Partial Correction
03/05/2015
FOLLOWING NEW OR MODIFIED SPACES ARE OK USE AND OCCUPANCY: 2C205; 239; 246; 250; 252; 253; 254; 259; 260; 261; 262;
In-wall Inspection Partial 3/18/2015 3/18/2015 at 12:00 AM 03/18/2015
Misc
Partial Correction
01/29/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PHASE 1A SPACES/WALLS; PHASE 2 SPACES/WALLS EXCEPT 2C221;
In-wall Inspection Partial 3/19/2015 3/19/2015 at 12:00 AM 03/19/2015
Misc
Partial Correction
03/18/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PHASE 1A SPACES/WALLS; PHASE 2 SPACES/WALLS INCLUDING @ 2C221
Above Ceiling Inspection Passed 4/3/2015 4/3/2015 at 12:00 AM 04/03/2015
Misc
Resolved
04/03/2015
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PHASE 1 AREA; PHASE 2 AREA;
Alarm Test Passed 4/10/2015 at 12:00 AM 04/10/2015
Occupancy Inspection - Fire Passed 4/10/2015 at 12:00 AM 04/10/2015
Final Inspection - Commercial Passed 4/10/2015 4/10/2015 at 12:00 AM 04/10/2015
In-wall Inspection Passed 3/19/2015 at 12:00 AM 04/10/2015
Misc
Resolved
04/10/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PHASE 1A SPACES/WALLS; PHASE 2 SPACES/WALLS INCLUDING @ 2C221
Final Inspection - Commercial Passed 4/10/2015 at 12:00 AM 06/12/2015
Misc
Resolved
06/12/2015
FOLLOWING NEW OR MODIFIED SPACES ARE OK USE AND OCCUPANCY: 2C205; 239; 246; 250; 252; 253; 254; 259; 260; 261; 262;
Documents & Images
Date Uploaded File Type Document Name
11/24/2014 Letter Fire Building Plan Review
11/26/2014 Letter Codes P/R Corrections Document
12/01/2014 Letter Codes P/R Corrections Document
12/31/2014 Letter Codes Plan Review Conditions
01/06/2015 Letter Codes Building Permit
01/06/2015 Receipt Receipt for transaction: 2015-000013
01/27/2015 Letter Inspection Summary
01/29/2015 Letter Inspection Summary
02/27/2015 Letter Inspection Summary
03/02/2015 Letter Inspection Summary
03/06/2015 Letter Inspection Summary
03/16/2015 Letter Fire (Sprinkler) Plan Review
03/18/2015 Letter Inspection Summary
03/19/2015 Letter Inspection Summary
04/03/2015 Letter Inspection Summary
04/10/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home