Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Plan Review
|
Approved with Conditions
|
11/24/2014
|
11/17/2014
|
|
Joe Frogge
|
|
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.)
Comment - If paint is used for restroom finish material around waterclosets and similar, it must be epoxy type.
|
|
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Comment - I wasn't able to locate the mop sink/utility sink.
|
|
Misc
Corrective Action Required
Comment - 5 handicap parking stalls required. I only see 4, but also see that there is probably one intended to be shown near the entry at vestibule 10-152?
|
|
Misc
Corrective Action Required
Comment - Recommend ensuring during design process that mechanical platform labelled "Mezzanine" continues to meet definition of "equipment platform." If not, an egress stair will be required.
|
|
Misc
Corrective Action Required
Electrical drawings will need to show methods and materials in Class 1 Div 1 areas in and around fueling.
|
|
Miscellaneous Correction
Corrective Action Required
Final design to include provisions for maintaining minimum egress requirements out of meeting room with divider partition. Minimum egress to be maintained while divider partition is in place and when stored.
|
|
Miscellaneous Correction
Corrective Action Required
Two exits with panic hardware is required out of electrical equipment room when electrical equipment is rated at 1200 amps or more. For a single egress, space design must meet specific exception requirements per 2011 NEC Article 110.26.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
11/24/2014
|
11/17/2014
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
A hazardous materials permit will be required for the fuel storage. Also may include lubricants and waste oil. Call (816) 969-1300 for application
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Submit alarm plans for approval
|
|
Hazardous material identification
Corrective Action Required
2006 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5.
Provide information on chemical storage ( if applicable)
|
|
Knox box required
Corrective Action Required
2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Call (816) 969-1300 to obtain a knox box application. If the entracne will be gated a knox lock will also be required
|
|
Fire protection equipment identification
Corrective Action Required
2012 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Label door to riser room
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Submit sprinkler plans for approval
|
|
Misc
Corrective Action Required
|
|
Misc
Corrective Action Required
Fuel tanks shall be listed to UL 2085 and have impact bollards
|
|
Misc
Corrective Action Required
Alarm plans shall show CO detection for garage area
|
|
|