Permit Application Status

PRCOM20143152


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20143152
Building Permit - Commercial
Voided
THE CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW WATER UTILITIES DEPARTMENT FACILITY
11/10/2014
05/16/2015
03/11/2016
Locations
Contacts
HDR ENGINEERING, INC, Address:P O BOX 80600, Phone:(317) 596-3260  
THE CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 11/24/2014 11/17/2014
Joe Frogge
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
11/10/2014

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Comment - If paint is used for restroom finish material around waterclosets and similar, it must be epoxy type.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
11/10/2014

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Comment - I wasn't able to locate the mop sink/utility sink.
Misc
Corrective Action Required
11/10/2014

Comment - 5 handicap parking stalls required. I only see 4, but also see that there is probably one intended to be shown near the entry at vestibule 10-152?
Misc
Corrective Action Required
11/10/2014

Comment - Recommend ensuring during design process that mechanical platform labelled "Mezzanine" continues to meet definition of "equipment platform." If not, an egress stair will be required.
Misc
Corrective Action Required
11/17/2014

Electrical drawings will need to show methods and materials in Class 1 Div 1 areas in and around fueling.
Miscellaneous Correction
Corrective Action Required
11/17/2014

Final design to include provisions for maintaining minimum egress requirements out of meeting room with divider partition. Minimum egress to be maintained while divider partition is in place and when stored.
Miscellaneous Correction
Corrective Action Required
11/17/2014

Two exits with panic hardware is required out of electrical equipment room when electrical equipment is rated at 1200 amps or more. For a single egress, space design must meet specific exception requirements per 2011 NEC Article 110.26.
Fire Plan Review Approved with Conditions 11/24/2014 11/17/2014
Brian Austerman
Misc
Corrective Action Required
11/17/2014

A hazardous materials permit will be required for the fuel storage. Also may include lubricants and waste oil. Call (816) 969-1300 for application
Construction documents for fire alarm systems
Corrective Action Required
11/17/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit alarm plans for approval
Hazardous material identification
Corrective Action Required
11/17/2014

2006 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. Provide information on chemical storage ( if applicable)
Knox box required
Corrective Action Required
11/17/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. If the entracne will be gated a knox lock will also be required
Fire protection equipment identification
Corrective Action Required
11/17/2014

2012 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Label door to riser room
Construction documents - Fire protection systems
Corrective Action Required
11/17/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit sprinkler plans for approval
Misc
Corrective Action Required
11/17/2014

Misc
Corrective Action Required
11/17/2014

Fuel tanks shall be listed to UL 2085 and have impact bollards
Misc
Corrective Action Required
11/17/2014

Alarm plans shall show CO detection for garage area
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
11/17/2014 Letter Codes P/R Corrections Document
11/17/2014 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home