Permit Application Status

PRCOM20142967


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20142967
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
INTERIOR RENOVATIONS TO ACCOMMODATE NEW X-RAY EQUIPMENT
10/23/2014
12/02/2014
02/13/2015
Locations
Contacts
MCCOWN GORDON CONSTRUCTION LLC, Address:850 MAIN ST, Phone:(816) 960-1111  
MMC CONTRACTORS NATIONAL INC, Address:13800 WYANDOTTE, Phone:(816) 941-5300  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
MMC CONTRACTORS NATIONAL INC, Address:13800 WYANDOTTE, Phone:(816) 941-5300  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/31/2014
Joe Dir
Licensed Contractors Approved 11/04/2014 11/24/2014
Joe Frogge
LC - General Contractor
Corrective Action Required
10/27/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
10/27/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Approved with Conditions 11/04/2014 10/30/2014
Mike Weisenborn
Fire Plan Review Approved with Conditions 11/04/2014 10/30/2014
Mike Weisenborn
Construction documents for fire alarm systems
Corrective Action Required
10/27/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If alterations are required submit plans for approval
Construction documents - Fire protection systems
Corrective Action Required
10/27/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If alterations are required submit plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $131.96 $131.96 Paid 12/02/2014
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 12/12/2014 12/12/2014 at 12:00 AM 12/12/2014
Misc
Partial Correction
12/12/2014
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 2E69;
Above Ceiling Inspection Partial 12/30/2014 at 12:00 AM 12/30/2014
Misc
Partial Correction
12/30/2014
REMOVE TWO ABANDONED STRAP HANGERS; CLAMP MC CABLE WITHIN 12" OF ENTRY TO BOX ONE LOCATION. THEN OK TO COVER WHEN READY.
Occupancy Inspection - Fire Temporary C of O 1/7/2015 1/7/2015 at 12:00 AM 01/07/2015
Misc
Corrective Action Required
01/07/2015
phase-1 of 2 - comfirmation from alarm installer that the new(added) smoke detection in room 2E69 has been installed, programed and tested.
Final Inspection - Commercial Partial 1/7/2015 1/7/2015 at 12:00 AM 01/07/2015
Misc
Partial Correction
01/07/2015
FOLLOWING SPACES OK FOR USE AND OCCUPANCY: 2E57 & 69 (DOCUMENTATION OF TEST OF NEW SMOKE DETECTOR @ 69 TO BE PROVIDED TO CPT DIR @ LSFD);
Alarm Test Passed 1/14/2015 at 12:00 AM 01/14/2015
Occupancy Inspection - Fire Passed 1/14/2015 at 12:00 AM 01/22/2015
Misc
Corrective Action Required
01/14/2015
phase-1 of 2 - comfirmation from alarm installer that the new(added) smoke detection in room 2E69 has been installed, programed and tested.
In-wall Inspection Partial 1/29/2015 1/29/2015 at 12:00 AM 01/29/2015
Misc
Partial Correction
12/12/2014
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 2E69; X-RAY 2E81 AFTER ONE NOTCHED STUD IS REINFORCED AND DOOR FRAME ANCHORAGE IS IMPROVED;
Above Ceiling Inspection Partial 2/9/2015 2/9/2015 at 12:00 AM 02/09/2015
Misc
Partial Correction
12/30/2014
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT SPACES: 2E57; 69; 81;
Occupancy Inspection - Fire Passed 2/17/2015 at 12:00 AM 02/17/2015
Final Inspection - Commercial Passed 2/17/2015 at 12:00 AM 02/17/2015
Misc
Resolved
02/17/2015
FOLLOWING SPACES OK FOR USE AND OCCUPANCY: 2E57 & 69 (DOCUMENTATION OF TEST OF NEW SMOKE DETECTOR @ 69 TO BE PROVIDED TO CPT DIR @ LSFD);
Documents & Images
Date Uploaded File Type Document Name
10/27/2014 Letter Fire Building Plan Review
10/27/2014 Letter Codes P/R Corrections Document
12/02/2014 Receipt Receipt for transaction: 2014-002262
12/02/2014 Letter Codes Plan Review Conditions
12/02/2014 Letter Codes Building Permit
12/12/2014 Letter Inspection Summary
12/30/2014 Letter Inspection Summary
01/07/2015 Letter Inspection Summary
01/29/2015 Letter Inspection Summary
02/09/2015 Letter Inspection Summary
02/17/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home