Permit Application Status

PRCOM20142793


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20142793
Building Permit - Commercial
Certificate of Occupancy
DKML LLC
ADDITION COMMERCIAL
ADDITION TO FACTORY BUILDING INCLUDING PLUMBING WORK BUT NOT ELECTRICAL OR MECHANICAL. ELECTRICAL: PRCOM20150917 MECHANICAL: PRCOM20150919
10/02/2014
05/26/2015
04/19/2015
01/28/2016
Locations
Contacts
MAR ENTERPRISES INC, Address:24408 E US 50 HWY, Phone:(816) 524-2398  
J & S PLUMBING PROS LLC, Address:116 S WESTGLEN DR, Phone:(816) 215-5306  
RUNDQUIST & ASSOCIATES, ARCHITECTS PC, Address:6635 EDGEVALE ROAD, Phone:(816) 472-6006  
DKML LLC, Address:1161 SE HAMBLEN RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/20/2015 08/20/2015
Joe Dir
Installation acceptance testing
Corrective Action Required
08/20/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Testing required for new installation of devices. To schedule a test contact Fire Department 816-969-1300.
Final Development Plan Review Approved 05/20/2015 05/18/2015
Joe Frogge
Licensed Contractors Approved 12/05/2014 05/18/2015
Joe Frogge
LC - MEP Subs
Resolved
05/18/2015

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Sprinkler Plan Review Released for Construction 03/23/2015
Brian Austerman
Installation acceptance testing
Corrective Action Required
03/23/2015

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call 816-969-1300 to schedule hydrostatic and flow testing
Fire Plan Review Approved with Conditions 12/12/2014 02/17/2015
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
02/17/2015

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ALARM PLANS FOR APPROVAL.
Hazardous material identification
Corrective Action Required
02/17/2015

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. PROVIDE INFORMATION ON OVENS AND PROVIDE A CURRENT LIST OF HAZARDOUS MATERIALS
Construction documents - Fire protection systems
Corrective Action Required
02/17/2015

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE SPRINKLER PLANS FOR APPROVAL. THE ADDITIONAL SPACE EXCEEDS 52,000 SQ/FT. PROVIDE ANOTHER RISER AND ALSO SHOW PROTECTION FOR THE OVENS
Portable fire extinguishers - general
Corrective Action Required
02/17/2015

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A 5LB ABC TYPE EXTINGUISHER FOR EVERY 3,000 SQ/FT OR ONE FOR EVERY 75' OF TRAVEL DISTANCE.
Misc
Corrective Action Required
02/17/2015

2-17-15 ADDITIONAL COMMENT The alternate bid to replace the flourescent lighting in the existing building does not call out emergency lighting. if the lighting fixtures are changed provide for emergency lighting
Building Plan Review Approved with Conditions 12/12/2014 12/18/2014
Joe Frogge
Final Development Plan
Resolved
04/29/2015

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes. received - 4/29/15
Misc
Resolved
12/12/2014

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility. 12/12/14 - letter provided
Bldg - Building height and area limitations 503.1
Resolved
12/12/2014

2012 IBC 503.1 – General. The building height and area shall not exceed the limitations specified in Table 503 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter. Each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building. Action required: Maximum area exceeded at listed Construction Type. Modify design or reclassify. If reclassified, written justification/qualification of existing and new structure from design professional will be required. 12/12/14 - reclassified as IIB which matches original construction
Miscellaneous Correction
Resolved
12/18/2014

Insufficient information to complete review. Action required: Provide the following information. - (resolved - 12/12/14) - (resolved - 12/12/14) - (resolved - 12/12/14) - (resolved - 12/12/14) - (resolved - 12/12/14) - (resolved - 12/18/14) - (resolved - 12/12/14)
Screening - Ground mounted equipment
Corrective Action Required
12/05/2014

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Modify documents to depict screening design. (contact Planning Department for approved methods and materials) 12/12/14 - shrubbery shown as screening - approval pending inspection by Planner.
Bldg - Landings at doors 1008.1.6
Resolved
12/12/2014

2012 IBC 1008.1.6 – Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Modify drawings. 12/12/14 - shown on drawings.
Bldg - Illumination required 1006.1
Resolved
12/12/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide illumination at all exterior doors. (note: architectural floor plans do not currently match electrical drawings) 12/12/14 - additional lighting provided
Misc
Resolved
12/12/2014

Design and capacity of sand/oil separator. Action required: Provide letter from design engineer of record stating that the existing sand/oil separator is adequately sized for newly added load as well and is appropriately designed for pressurized input from new ejector pump. 12/12/14 - resolved via engineer's calculation shown on drawings
Fire Plan Review Approved with Conditions 12/12/2014 12/12/2014
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
12/05/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ALARM PLANS FOR APPROVAL.
Hazardous material identification
Corrective Action Required
12/05/2014

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. PROVIDE INFORMATION ON OVENS AND PROVIDE A CURRENT LIST OF HAZARDOUS MATERIALS
Construction documents - Fire protection systems
Corrective Action Required
12/05/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE SPRINKLER PLANS FOR APPROVAL. THE ADDITIONAL SPACE EXCEEDS 52,000 SQ/FT. PROVIDE ANOTHER RISER AND ALSO SHOW PROTECTION FOR THE OVENS
Portable fire extinguishers - general
Corrective Action Required
12/05/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A 5LB ABC TYPE EXTINGUISHER FOR EVERY 3,000 SQ/FT OR ONE FOR EVERY 75' OF TRAVEL DISTANCE.
Building Plan Review Rejected 10/16/2014 10/10/2014
Joe Frogge
Final Development Plan
Corrective Action Required
10/10/2014

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment for informational purposes.
Misc
Corrective Action Required
10/10/2014

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility.
Bldg - Building height and area limitations 503.1
Corrective Action Required
10/10/2014

2012 IBC 503.1 – General. The building height and area shall not exceed the limitations specified in Table 503 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter. Each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building. Action required: Maximum area exceeded at listed Construction Type. Modify design or reclassify. If reclassified, written justification/qualification of existing and new structure from design professional will be required.
Miscellaneous Correction
Corrective Action Required
10/10/2014

Insufficient information to complete review. Action required: Provide the following information. - Detailed interior floor plan. - Resolve exterior floor plan discrepancies between architectural plans and MEP plans. - Complete the labelling of interior and exterior column pads. - Provide detailed plans of superstructure. (these may be deferred upon written request) - Document building envelope insulation methods & materials. - Detailed design of trenches intended for use as electrical raceways. - Detailed design of new overhead buss bar system.
Screening - Ground mounted equipment
Corrective Action Required
10/10/2014

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Modify documents to depict screening design. (contact Planning Department for approved methods and materials)
Bldg - Landings at doors 1008.1.6
Corrective Action Required
10/10/2014

2012 IBC 1008.1.6 – Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Modify drawings.
Bldg - Illumination required 1006.1
Corrective Action Required
10/10/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide illumination at all exterior doors. (note: architectural floor plans do not currently match electrical drawings)
Misc
Corrective Action Required
10/10/2014

Design and capacity of sand/oil separator. Action required: Provide letter from design engineer of record stating that the existing sand/oil separator is adequately sized for newly added load as well and is appropriately designed for pressurized input from new ejector pump.
Licensed Contractors Rejected 10/16/2014 10/10/2014
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/10/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 10/16/2014 10/06/2014
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
10/06/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ALARM PLANS FOR APPROVAL.
Hazardous material identification
Corrective Action Required
10/06/2014

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. PROVIDE INFORMATION ON OVENS AND PROVIDE A CURRENT LIST OF HAZARDOUS MATERIALS
Construction documents - Fire protection systems
Corrective Action Required
10/06/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE SPRINKLER PLANS FOR APPROVAL. THE ADDITIONAL SPACE EXCEEDS 52,000 SQ/FT. PROVIDE ANOTHER RISER AND ALSO SHOW PROTECTION FOR THE OVENS
Portable fire extinguishers - general
Corrective Action Required
10/06/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A 5LB ABC TYPE EXTINGUISHER FOR EVERY 3,000 SQ/FT OR ONE FOR EVERY 75' OF TRAVEL DISTANCE.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Addition to Commercial $3,113.22 $3,113.22 Paid 05/26/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Hydrostatic Test Passed 7/22/2015 at 12:00 AM 07/27/2015
Alarm Test Passed 10/1/2015 at 12:00 AM 10/01/2015
Footing Inspection - Commercial Passed 10/02/2015
Occupancy Inspection - Codes Commercial Not Ready 10/2/2015 at 12:00 AM 10/02/2015
Misc
Corrective Action Required
10/02/2015
***NOT AN OFFICAL OCCUPANCY INSPECTION*** -LICENSE TAX FOR THE ADDITION HAS NOT BEEN PAID. -GENERAL CONTRACTOR NEEDS TO SUBMIT ALL SPECIAL INSPECTIONS PERFORMED ON THE BUILDING. -NEED TO SUBMIT MANUFACTURER INSTRUCTIONS ON ALL OVERHEAD DOORS STATING THE DOORS ARE SUITABLE FOR WIND LOADS UP TO 90 M.P.H. -PLAN REVIEW COMMENT, REQUIRED TO SCREEN ALL MECHANICAL EQUIPMENT. NONE OF THE UNITS ARE SCREENED. OBTAIN PLANNING AND DEVELOPMENT APPROVAL/GUIDANCE FOR MEETING THIS ORDINANCE REQUIREMENT. GIVEN APPROVAL TO SET UP EQUIPMENT IN THE ADDITION SO HE CAN COMPLETE THE WIRING.
Occupancy Inspection - Codes Commercial Temporary C of O 12/9/2015 12/9/2015 at 12:00 AM 12/09/2015
Misc
Corrective Action Required
10/02/2015
OVERHEAD DOOR -PLAN REVIEW COMMENT, REQUIRED TO SCREEN ALL MECHANICAL EQUIPMENT. NONE OF THE UNITS ARE SCREENED. OBTAIN PLANNING AND DEVELOPMENT APPROVAL/GUIDANCE FOR MEETING THIS ORDINANCE REQUIREMENT. -OBTAIN APPROVAL FROM PUBLIC WORKS REGARDING DETENTION BASIN.
Occupancy Inspection - Codes Commercial Temporary C of O 12/10/2015
Misc
Corrective Action Required
12/09/2015
OVERHEAD DOOR -PLAN REVIEW COMMENT, REQUIRED TO SCREEN ALL MECHANICAL EQUIPMENT. NONE OF THE UNITS ARE SCREENED. OBTAIN PLANNING AND DEVELOPMENT APPROVAL/GUIDANCE FOR MEETING THIS ORDINANCE REQUIREMENT. -OBTAIN APPROVAL FROM PUBLIC WORKS REGARDING DETENTION BASIN.
Occupancy Inspection - Fire Passed 12/9/2015 at 12:00 AM 12/10/2015
Occupancy Inspection - Planning Temporary C of O 12/15/2015
Corrective Action Required
12/15/2015
The 3 ground-mounted mechanical units on the south side of the property must be screened. A vinyl panel placed on the east side of each of the units will satisfy ordinance requirements. The vinyl panels must screen the units from the view of the neighboring building east of the JCI property.
Occupancy Inspection - Planning Passed 01/27/2016
Occupancy Inspection - Codes Commercial Full C of O 01/28/2016
Misc
Resolved
01/28/2016
OVERHEAD DOOR -PLAN REVIEW COMMENT, REQUIRED TO SCREEN ALL MECHANICAL EQUIPMENT. NONE OF THE UNITS ARE SCREENED. OBTAIN PLANNING AND DEVELOPMENT APPROVAL/GUIDANCE FOR MEETING THIS ORDINANCE REQUIREMENT. -OBTAIN APPROVAL FROM PUBLIC WORKS REGARDING DETENTION BASIN.
Documents & Images
Date Uploaded File Type Document Name
10/06/2014 Letter Fire Building Plan Review
10/10/2014 Letter Codes P/R Corrections Document
12/12/2014 Letter Codes P/R Corrections Document
12/12/2014 Letter Codes P/R Corrections Document
02/17/2015 Letter Fire Building Plan Review
03/23/2015 Letter Fire (Sprinkler) Plan Review
05/26/2015 Receipt Receipt for transaction: 2015-001671
05/26/2015 Letter Codes Building Permit
05/26/2015 Letter Codes Plan Review Conditions
08/20/2015 Letter Fire (Alarm) Plan Review Notice
10/02/2015 Letter Inspection Summary
12/09/2015 Letter Codes Temporary Certificate of Occupancy
12/10/2015 Letter Codes Temporary Certificate of Occupancy
12/15/2015 Letter Planning Inspection Summary
01/15/2016 CMR 20142793
01/27/2016 Letter Planning Inspection Summary
01/28/2016 Letter Field Certificate of Occupancy
01/29/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home