Summary
PRCOM20141908
Building Permit - Commercial
Closed
JOHN KNOX VILLAGE
REPAIR REPLACE UPGRADE
REPLACE EXISTING FIRE SUPPRESSION SYSTEM
07/09/2014
01/08/2016
Locations
Contacts
  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 11/06/2014
Brian Austerman
Misc
Corrective Action Required
11/06/2014

Provide label on FDC clearly stating which building it serves
Installation acceptance testing
Corrective Action Required
11/06/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow testing
Misc
Corrective Action Required
11/06/2014

Mark interior riser room doors
Misc
Corrective Action Required
11/06/2014

Main drain needs to be routed to the exterior or to a drain capable of handling the flow
Sprinkler Plan Review Released for Construction 07/10/2014
Brian Austerman
Installation acceptance testing
Corrective Action Required
07/10/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow testing
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Hydrostatic Test Passed 3/10/2015 at 10:00 AM 03/10/2015
Alarm Test Passed 4/10/2015 at 12:00 AM 04/10/2015
Sprinkler - Flow Test Failed 4/10/2015 at 12:00 AM 04/10/2015
Sprinkler - Flow Test Passed 4/14/2015 04/14/2015
Documents & Images
Date Uploaded File Type Document Name
07/10/2014 Letter Fire (Sprinkler) Plan Review
11/06/2014 Letter Fire (Sprinkler) Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home