Permit Application Status

PRCOM20140995


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140995
Building Permit - Commercial
Certificate of Occupancy
CROSS PROPERTIES LLC
NEW COMMERCIAL
NEW CAR WASH WITH ENTRY CANOPY AND KIOSK - GREEN LANTERN
05/05/2014
07/21/2014
11/10/2014
05/14/2015
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
TEAGUE ELECTRIC CONSTRUCTION LLC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
GASTINGER WALKER HARDEN ARCHITECTS, Address:817 WYANDOTTE  
CROSS PROPERTIES LLC, Address:1101 NW BLUE PKWY  
OLSSON , Address:7301 W 133RD ST STE 200, Phone:(913) 381-1170  
CWW ENTERPRISES LP, Address:500 GRAVES BLVD  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
CWW ENTERPRISES LLC, Address:500 GRAVES BLVD  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 11/10/2014 07/18/2014
Joe Frogge
Special Inspections Review Approved 07/18/2014
Joe Frogge
Licensed Contractors Approved 06/02/2014 07/18/2014
Joe Frogge
License contractors
Resolved
07/18/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of Mechanical contractor.
Building Plan Review Approved with Conditions 06/02/2014 05/28/2014
Joe Frogge
Misc
Resolved
05/28/2014

ICC A117.1-2009 Section 603.2.1 Turning Space. A turning space complying with Section 304 shall be provided within the room. The required turning space shall not be provided within a toilet compartment. Action required: Revise drawings to provide accessible turning space in restrooms that are not in toilet compartments. (note: turning radii configurations between floor plans and expanded plans do not match) 5/28/14 - drawings updated
Misc
Resolved
05/28/2014

2012 IBC 716.2 Fire-resistance-rated glazing assemblies. Fire-resistance=rated glazing tested as part of a fire-resistance=rated wall assembly in accordance with ASTM E 119 or UL 263 and labeled in accordance with Section 703.5 shall be permitted in fire doors and fire window assemblies where tested and installed in accordance with their listings and shall not otherwise be required to comply with this section. Action required: All windows in wall type 2 must be fire-resistance-rated 1hr. Correct the labels on section and on floor plan. 5/28/14 - drawings updated
Plumb - Minimum number of fixtures 403.1
Resolved
05/28/2014

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide accessible drinking fountain. (note: water cooler is shown on architectural sheets, but not the plumbing sheets) 5/28/14 - drawings updated
Engineered truss package
Corrective Action Required
05/23/2014

Copies of the engineered truss package were not provided at the time of permit application. Action required: This comment is for informational purposes. Truss package must be reviewed by engineer of record prior to submitting to City. Approved truss drawings must be on site for inspection. 5/28/14 - truss package deferred to construction.
Misc
Resolved
05/28/2014

Unable to identify plumbing materials. Action required: Provide plumbing material schedule. 5/28/14 - drawings updated
Fire Plan Review Approved with Conditions 06/02/2014 05/28/2014
Joe Frogge
Misc
Corrective Action Required
05/23/2014

PROVIDE EXTERIOR EMERGENCY EGRESS LIGHTING, AS REQUIRED IN BUILDINGS WITH 2 OR MORE EXITS. Acknowledged 5/28/14
Hazardous material identification
Corrective Action Required
05/23/2014

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. PROVIDE A NFPA 704 PLACARD ON DOORS LEADING TO ROOMS WITH HAZARDOUS MATERIALS. VERIFIED AT INSPECTION Acknowledged 5/28/14
Fire Plan Review Approved with Conditions 05/19/2014 05/15/2014
Mike Weisenborn
Misc
Corrective Action Required
05/08/2014

PROVIDE EXTERIOR EMERGENCY EGRESS LIGHTING, AS REQUIRED IN BUILDINGS WITH 2 OR MORE EXITS.
Hazardous material identification
Corrective Action Required
05/08/2014

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. PROVIDE A NFPA 704 PLACARD ON DOORS LEADING TO ROOMS WITH HAZARDOUS MATERIALS. VERIFIED AT INSPECTION
Building Plan Review Rejected 05/19/2014 05/14/2014
Joe Frogge
Misc
Corrective Action Required
05/14/2014

ICC A117.1-2009 Section 603.2.1 Turning Space. A turning space complying with Section 304 shall be provided within the room. The required turning space shall not be provided within a toilet compartment. Action required: Revise drawings to provide accessible turning space in restrooms that are not in toilet compartments. (note: turning radii configurations between floor plans and expanded plans do not match)
Misc
Corrective Action Required
05/14/2014

2012 IBC 716.2 Fire-resistance-rated glazing assemblies. Fire-resistance=rated glazing tested as part of a fire-resistance=rated wall assembly in accordance with ASTM E 119 or UL 263 and labeled in accordance with Section 703.5 shall be permitted in fire doors and fire window assemblies where tested and installed in accordance with their listings and shall not otherwise be required to comply with this section. Action required: All windows in wall type 2 must be fire-resistance-rated 1hr. Correct the labels on section and on floor plan.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
05/14/2014

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide accessible drinking fountain. (note: water cooler is shown on architectural sheets, but not the plumbing sheets)
Engineered truss package
Corrective Action Required
05/14/2014

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide truss package or defer to construction. Truss package must be reviewed by engineer of record prior to submitting to City. Approved truss drawings must be on site for inspection.
Misc
Corrective Action Required
05/14/2014

Unable to identify plumbing materials. Action required: Provide plumbing material schedule.
Licensed Contractors Rejected 11/10/2014 05/14/2014
Joe Frogge
License contractors
Resolved
07/18/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of Mechanical contractor.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $6,028.70 $6,028.70 Paid 07/21/2014
$6,028.70
Right of Way Permit Fee $60.00 $60.00 Paid 07/21/2014
$60.00
8331507-Sewer Connection Fee $660.00 $660.00 Paid 07/21/2014
$660.00
Water Tap Fee $66,475.00 $66,475.00 Paid 07/21/2014
$66,475.00
Water Meter Fee $1,505.00 $1,505.00 Paid 07/21/2014
$1,505.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 7/29/2014 (11:00) 7/29/2014 at 12:00 AM 07/29/2014
Misc
Partial Correction
07/29/2014
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM AS FOLLOWS: A TO B TO C TO D TO E TO G (EXCEPT AT F) TO H (UFER GROUND CONNECTION IN PLACE);
Footing Inspection - Commercial Partial 7/29/2014 (1:45) 7/29/2014 at 12:00 AM 07/29/2014
Misc
Partial Correction
07/29/2014
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM AS FOLLOWS: A TO B TO C TO D TO E TO G (EXCEPT AT F) TO H (UFER GROUND CONNECTION IN PLACE); A TO U TO T TO S TO R TO Q TO P + RETURN;
Footing Inspection - Commercial Partial 8/1/2014 (8:00) 8/1/2014 at 12:00 AM 08/01/2014
Misc
Partial Correction
07/29/2014
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM AS FOLLOWS: A TO B TO C TO D TO E TO G (EXCEPT AT F) TO H (UFER GROUND CONNECTION IN PLACE); A TO U TO T TO S TO R TO Q TO P + RETURN; P TO O TO N TO M TO L TO K.4;
Misc
Partial Correction
08/01/2014
OK TO POUR WHEN READY BASE SLAB OF WASH TUNNEL FROM I.1 TO J.9;
Underslab Plumbing Inspection - Commercial Partial 8/5/2014 8/5/2014 at 12:00 AM 08/05/2014
Misc
Partial Correction
08/05/2014
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: SPACE 115 FROM WEST TO EAST AT (8/5); NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Footing Inspection - Commercial Partial 8/6/2014 at 12:00 AM 08/06/2014
Misc
Partial Correction
08/01/2014
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM AS FOLLOWS: A TO B TO C TO D TO E TO G (EXCEPT AT F) TO H (UFER GROUND CONNECTION IN PLACE); A TO U TO T TO S TO R TO Q TO P + RETURN; P TO O TO N TO M TO L TO K.4; FROM C TO T;
Misc
Partial Correction
08/01/2014
OK TO POUR WHEN READY BASE SLAB OF WASH TUNNEL FROM I.1 TO J.9;
Misc
Partial Correction
08/06/2014
OK TO POUR WHEN READY LINEAR FOOTING FROM E TO O;
Misc
Corrective Action Required
08/06/2014
OK TO POUR WHEN READY FOUR TYPE [4] ISOLATED FOOTINGS
Underslab Plumbing Inspection - Commercial Partial 8/6/2014 at 12:00 AM 08/06/2014
Misc
Partial Correction
08/06/2014
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: SPACE 115 FROM WEST TO EAST AT (8/5); SPACES 109 THRU 114; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Partial 8/12/2014 8/12/2014 at 12:00 AM 08/12/2014
Misc
Partial Correction
08/06/2014
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: SPACE 115 FROM WEST TO EAST AT (8/5); SPACES 109 THRU 114; 4" SAN DRAIN FROM (W) TO (X) + LATERALS; 4" SAN DRAIN FROM (Y) TO (Z) + LATERALS; 6"-8" ST SEWER FROM (A') TO (B') + LATERALS; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Electrical Inspection - Commercial Not Ready 8/13/2014 8/13/2014 at 12:00 AM 08/13/2014
Underslab Electrical Inspection - Commercial Partial 8/14/2014 8/14/2014 at 12:00 AM 08/14/2014
Misc
Partial Correction
08/14/2014
NO ISSUES FOUND ON UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP. G.C. AND E.C. TO ENSURE LAYOUT IS CORRECT. OK TO COVER WHEN READY AT DETAIL AREA;
Underground Electrical Inspection - Commercial Partial 8/14/2014 8/14/2014 at 12:00 AM 08/14/2014
Misc
Partial Correction
08/14/2014
UNDERGROUND SECONDARY ELECTRICAL SERVICE CONDUIT APPROVED TO COVER BASED ON DRAWING SHEET E401 ON WHICH F1 CALLS FOR 5 SETS OF FOUR 400 MCM COPPER CONDUCTORS RUN IN 3-1/2" RNC-40 RACEWAY. 4" CONDUIT INSTALLED. NOTE APPARENT CONFLICT WITH NOTE P-3 ON SHEET C6.0 WHICH STIPULATES 1-5" CONSUIT. A/E TO CLARIFY.
Water Service Inspection Partial 8/19/2014 (10:00) 8/19/2014 at 12:00 AM 08/19/2014
Misc
Partial Correction
08/19/2014
WATER SERVICE PIPE ENTRY TO BLDG, STUB-UP, AND 5' O/S B/L INSPECTED BY LSPW PER G.C. -- NO ISSUES
Underground Electrical Inspection - Commercial Partial 8/21/2014 8/21/2014 at 12:00 AM 08/21/2014
Misc
Partial Correction
08/21/2014
OK TO COVER PER DRAWINGS & SPECS WHEN READY TWO 4" SCH 40 PVC DATACOMM CONDUITS PER NOTES <4> & <5> SHEET ME101
Underslab Plumbing Inspection - Commercial Partial 8/22/2014 at 12:00 AM 08/22/2014
Misc
Partial Correction
08/22/2014
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: SPACE 115 FROM WEST TO EAST AT (8/5); SPACES 109 THRU 114; 4" SAN DRAIN FROM (W) TO (X) + LATERALS; 4" SAN DRAIN FROM (Y) TO (Z) + LATERALS; 6"-8" ST SEWER FROM (A') TO (B') + LATERALS; 6" SCH 40 PVC CHASE FOR TIRE SHINE WEST TO EAST O/S EAST EXT WALL @ M231-A; 4" SCH 40 PVC SAN DRAIN FROM M221-Y EAST TO O/S EAST EXT WALL; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underground Electrical Inspection - Commercial Partial 8/22/2014 at 12:00 AM 08/22/2014
Misc
Partial Correction
08/14/2014
UNDERGROUND SECONDARY ELECTRICAL SERVICE CONDUIT APPROVED TO COVER BASED ON DRAWING SHEET E401 ON WHICH F1 CALLS FOR 5 SETS OF FOUR 400 MCM COPPER CONDUCTORS RUN IN 3-1/2" RNC-40 RACEWAY. 4" CONDUIT INSTALLED. NOTE APPARENT CONFLICT WITH NOTE P-3 ON SHEET C6.0 WHICH STIPULATES 1-5" CONDUIT. A/E TO CLARIFY.
Misc
Partial Correction
08/22/2014
OK TO COVER WHEN READY SIX 2" AND ONE 1-1/2" SCH 40 PVC CONDUITS FROM S WALL OF MAIN BUILDING TO KIOSK
Underslab Plumbing Inspection - Commercial Passed 8/22/2014 at 12:00 AM 08/22/2014
Underslab Electrical Inspection - Commercial Partial 8/25/2014 8/25/2014 at 12:00 AM 08/25/2014
Misc
Partial Correction
08/14/2014
NO ISSUES FOUND ON UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP. G.C. AND E.C. TO ENSURE LAYOUT IS CORRECT. OK TO COVER WHEN READY AT: DETAIL AREA; SOUTH 120' OF MECH 101;
Underslab Electrical Inspection - Commercial Partial 8/26/2014 8/26/2014 at 12:00 AM 08/26/2014
Misc
Partial Correction
08/25/2014
NO ISSUES FOUND ON UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP. G.C. AND E.C. TO ENSURE LAYOUT IS CORRECT. OK TO COVER WHEN READY AT: DETAIL AREA; MECH 101 COMPLETE;
Electrical Service Inspection Partial 9/18/2014 9/18/2014 at 12:00 AM 09/18/2014
Misc
Partial Correction
09/18/2014
RELEASE TEMPORARY ELECTRCIAL SERVICE AT BUILDING.
In-wall Inspection Partial 10/29/2014 at 12:00 AM 10/29/2014
Misc
Partial Correction
10/29/2014
OKAY TO COVER OFFICE AREA, EVERYTHING SOUTH OF COOLER. NOTE: INSTALL PLUMBING PROTECTION FOR PVC PIPING
Above Ceiling Inspection Partial 10/29/2014 at 12:00 AM 10/29/2014
Misc
Partial Correction
10/29/2014
FRAMING AND ELECTRICAL FOR KIASK APPROVED TO APPLY FINISH MATERIAL (PLY THEN GYP)
Underground Plumbing Inspection - Commercial Partial 11/5/2014 11/5/2014 at 12:00 AM 11/05/2014
Misc
Partial Correction
11/05/2014
PRIVATE DEDUCT METER FOR THE IRRIGATION SYSTEM OBSERVED WITHIN METER PIT. METER PIT AND PIPING FROM VAULT TO METER PIT BACKFILLED PRIOR TO INSPECTION; NOT INSPECTED.
In-wall Inspection Partial 11/14/2014 11/14/2014 at 12:00 AM 11/14/2014
Misc
Partial Correction
10/29/2014
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: OFFICE AREA, EVERYTHING SOUTH OF COOLER; SPACES 109; 111; 112; 113;
Above Ceiling Inspection Partial 11/14/2014 11/14/2014 at 12:00 AM 11/14/2014
Misc
Partial Correction
11/14/2014
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO EXTERIOR CEILINGS AT S/SW;
Gas Service Inspection - Commercial Not Ready 11/14/2014 11/14/2014 at 12:00 AM 11/14/2014
Gas Piping Inspection - Commercial Not Ready 11/14/2014 at 12:00 AM 11/14/2014
Electrical Service Inspection Passed 11/18/2014 11/18/2014 at 12:00 AM 11/18/2014
Misc
Resolved
11/18/2014
RELEASE TEMPORARY ELECTRCIAL SERVICE AT BUILDING.
Gas Service Inspection - Commercial Passed 11/19/2014 11/19/2014 at 12:00 AM 11/19/2014
Gas Piping Inspection - Commercial Partial 11/19/2014 at 12:00 AM 11/19/2014
Misc
Corrective Action Required
11/19/2014
MAIN FEED AND ROOFTOP PIPING ONLY PRESSURE-TESTED. REMAINDER OF PIPING TO BE TESTED WHEN READY.
Misc
Corrective Action Required
11/19/2014
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Misc
Corrective Action Required
11/19/2014
SUPPORT AND STRAPPING OF ROOFTOP PIPING TO BE FINAL-CHECKED WHEN COMPLETED.
Underground Electrical Inspection - Commercial Partial 11/24/2014 11/24/2014 at 12:00 AM 11/24/2014
Misc
Partial Correction
11/24/2014
POLE BASES APPROVED TO POUR. DETAIL SHOWS ROD WITH CAD WELD. THIS HASN'T BEEN INSPECTED. GAVE OPTION FOR DESIGN PROFESSIONAL TO SUBMIT NEW DETAIL FOR APPROVED CLAMP.
Above Ceiling Inspection Partial 12/16/2014 12/16/2014 at 12:00 AM 12/16/2014
Misc
Partial Correction
11/14/2014
FRAMING AND ELECTRICAL FOR KIASK APPROVED TO APPLY FINISH MATERIAL (PLY THEN GYP)
Misc
Partial Correction
12/16/2014
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 103; 104; 105; 106 EXCEPT CLOSET; 108; 109; 111; 112;
Above Ceiling Inspection Partial 12/19/2014 12/19/2014 at 12:00 AM 12/19/2014
Misc
Resolved
12/19/2014
FRAMING AND ELECTRICAL FOR KIASK APPROVED TO APPLY FINISH MATERIAL (PLY THEN GYP)
Misc
Partial Correction
12/16/2014
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 103; 104; 105; 106 EXCEPT CLOSET; 108; 109; 111; 112; 103; 107; 110N KIOSK NOT READY
Occupancy Inspection - Codes Commercial Not Ready 12/19/2014 at 12:00 AM 12/19/2014
Misc
Corrective Action Required
12/19/2014
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 2) NEC 210.63 ELECTRICAL RECEPTACLE OUTLETS REQUIRED WITHIN 25 FEET OF HVAC AND/OR REFRIG EQPMT. 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Above Ceiling Inspection Passed 12/30/2014 12/30/2014 at 12:00 AM 12/30/2014
Misc
Resolved
12/30/2014
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 103; 104; 105; 106 EXCEPT CLOSET; 108; 109; 111; 112; 103; 107; 110N KIOSK NOT READY
Occupancy Inspection - Planning Temporary C of O 12/31/2014
Corrective Action Required
12/31/2014
LANDSCAPING. Landscaping shall be completed per the approved plan.
Occupancy Inspection - Codes Commercial Failed 12/31/2014 12/31/2014 at 12:00 AM 12/31/2014
Misc
Corrective Action Required
12/19/2014
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 2) NEC 210.63 ELECTRICAL RECEPTACLE OUTLETS REQUIRED WITHIN 25 FEET OF HVAC AND/OR REFRIG EQPMT. MUST BE HOTFOR TEST. 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Misc
Corrective Action Required
12/31/2014
SOME EXTERIOR ELECT RECEPTS NOT HOT FOR TEST. ALL AT WET LOCATIONS REQUIRE IN-USE COVERS.
Misc
Corrective Action Required
12/31/2014
KIOSK TO BE INSPECTED WHEN READY
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY WATER DEPARTMENT ISSUES.
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY PUBLIC WORKS ISSUES.
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY PLANNING DEPT ISSUES.
Misc
Corrective Action Required
12/31/2014
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
12/31/2014
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
12/31/2014
SINK AT 109 NOT YET PLUMBED
Misc
Corrective Action Required
12/31/2014
ELECT RECEPT AT 109 EAST WALL MUST BE GFI- PROTECTED (WITHIN 6' OF EDGE OF SINK).
Misc
Corrective Action Required
12/31/2014
NEC 370-20 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT HARD TILE WALLS AT 110 COFFEE NOOK, MEN'S 111, WOMEN'S 112
Misc
Corrective Action Required
12/31/2014
HEIGHT OF 18" SIDEWALL GRAB BARS @ MEN'S 111 & WOMEN'S 112: ANSI ALLOWABLE RANGE 39" - 41"
Misc
Corrective Action Required
12/31/2014
HOSE BIBS @ 114 NOT SECURED SOLID
Misc
Corrective Action Required
12/31/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC PRIOR TO APPROVAL. LICENSE TAX MUST BE PAID BEFORE TCO OR COFO.
Occupancy Inspection - Codes Commercial Not Ready 1/9/2015 at 12:00 AM 01/09/2015
Misc
Corrective Action Required
12/31/2014
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 2) NEC 210.63 ELECTRICAL RECEPTACLE OUTLETS REQUIRED WITHIN 25 FEET OF HVAC AND/OR REFRIG EQPMT. MUST BE HOTFOR TEST. 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Misc
Resolved
01/09/2015
SOME EXTERIOR ELECT RECEPTS NOT HOT FOR TEST. ALL AT WET LOCATIONS REQUIRE IN-USE COVERS.
Misc
Corrective Action Required
12/31/2014
KIOSK TO BE INSPECTED WHEN READY
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY WATER DEPARTMENT ISSUES.
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY PUBLIC WORKS ISSUES.
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
12/31/2014
RESOLVE ANY PLANNING DEPT ISSUES.
Misc
Corrective Action Required
12/31/2014
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
12/31/2014
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Resolved
01/09/2015
SINK AT 109 NOT YET PLUMBED
Misc
Resolved
01/09/2015
ELECT RECEPT AT 109 EAST WALL MUST BE GFI- PROTECTED (WITHIN 6' OF EDGE OF SINK).
Misc
Resolved
01/09/2015
NEC 370-20 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT HARD TILE WALLS AT 110 COFFEE NOOK, MEN'S 111, WOMEN'S 112
Misc
Resolved
01/09/2015
HEIGHT OF 18" SIDEWALL GRAB BARS @ MEN'S 111 & WOMEN'S 112: ANSI ALLOWABLE RANGE 39" - 41"
Misc
Resolved
01/09/2015
HOSE BIBS @ 114 NOT SECURED SOLID
Misc
Corrective Action Required
12/31/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Water Service Inspection Passed 8/19/2014 at 12:00 AM 01/15/2015
Misc
Partial Correction
08/19/2014
WATER SERVICE PIPE ENTRY TO BLDG, STUB-UP, AND 5' O/S B/L INSPECTED BY LSPW PER G.C. -- NO ISSUES
Underslab Electrical Inspection - Commercial Passed 8/26/2014 at 12:00 AM 01/15/2015
Misc
Resolved
01/15/2015
NO ISSUES FOUND ON UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP. G.C. AND E.C. TO ENSURE LAYOUT IS CORRECT. OK TO COVER WHEN READY AT: DETAIL AREA; MECH 101 COMPLETE;
Underground Plumbing Inspection - Commercial Passed 11/5/2014 at 12:00 AM 01/15/2015
Misc
Resolved
01/15/2015
PRIVATE DEDUCT METER FOR THE IRRIGATION SYSTEM OBSERVED WITHIN METER PIT. METER PIT AND PIPING FROM VAULT TO METER PIT BACKFILLED PRIOR TO INSPECTION; NOT INSPECTED.
Underground Electrical Inspection - Commercial Passed 11/24/2014 at 12:00 AM 01/15/2015
Misc
Resolved
01/15/2015
POLE BASES APPROVED TO POUR. DETAIL SHOWS ROD WITH CAD WELD. THIS HASN'T BEEN INSPECTED. GAVE OPTION FOR DESIGN PROFESSIONAL TO SUBMIT NEW DETAIL FOR APPROVED CLAMP.
Gas Piping Inspection - Commercial Passed 11/19/2014 at 12:00 AM 01/15/2015
Misc
Resolved
01/15/2015
MAIN FEED AND ROOFTOP PIPING ONLY PRESSURE-TESTED. REMAINDER OF PIPING TO BE TESTED WHEN READY.
Misc
Resolved
01/15/2015
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Misc
Resolved
01/15/2015
SUPPORT AND STRAPPING OF ROOFTOP PIPING TO BE FINAL-CHECKED WHEN COMPLETED.
In-wall Inspection Passed 11/14/2014 at 12:00 AM 01/15/2015
Misc
Resolved
01/15/2015
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: OFFICE AREA, EVERYTHING SOUTH OF COOLER; SPACES 109; 111; 112; 113;
Occupancy Inspection - Codes Commercial Not Ready 1/15/2015 at 12:00 AM 01/15/2015
Misc
Corrective Action Required
01/09/2015
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Misc
Corrective Action Required
01/09/2015
PANEL SCHEDULE LABELING AT KIOSK TO BE COMPLETED.
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY WATER DEPARTMENT ISSUES.
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY PUBLIC WORKS ISSUES. SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY PLANNING DEPT ISSUES.
Misc
Corrective Action Required
01/09/2015
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/09/2015
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/09/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Corrective Action Required
01/15/2015
PRIVATE DEDUCT METER FOR THE IRRIGATION SYSTEM OBSERVED WITHIN METER PIT. METER PIT AND PIPING FROM VAULT TO METER PIT BACKFILLED PRIOR TO INSPECTION; NOT INSPECTED.
Misc
Corrective Action Required
01/15/2015
ELECTRICAL CONDUIT OUTSIDE KIOSK WALLS NOT FOUND TO BE >=18" DEEP NOR PROTECTED BY A CONCRETE SLAB.
Occupancy Inspection - Codes Commercial Not Ready 1/9/2015 at 12:00 AM 01/16/2015
Misc
Corrective Action Required
01/09/2015
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 2) NEC 210.63 ELECTRICAL RECEPTACLE OUTLETS REQUIRED WITHIN 25 FEET OF HVAC AND/OR REFRIG EQPMT. MUST BE HOTFOR TEST. 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Misc
Corrective Action Required
01/09/2015
SOME EXTERIOR ELECT RECEPTS NOT HOT FOR TEST. ALL AT WET LOCATIONS REQUIRE IN-USE COVERS.
Misc
Corrective Action Required
01/09/2015
KIOSK TO BE INSPECTED WHEN READY
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY WATER DEPARTMENT ISSUES.
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY PUBLIC WORKS ISSUES.
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
01/09/2015
RESOLVE ANY PLANNING DEPT ISSUES.
Misc
Corrective Action Required
01/09/2015
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/09/2015
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/09/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Not Ready 1/16/2015 at 12:00 AM 01/16/2015
Misc
Corrective Action Required
01/15/2015
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Misc
Corrective Action Required
01/15/2015
PANEL SCHEDULE LABELING AT KIOSK TO BE COMPLETED.
Misc
Corrective Action Required
01/15/2015
RESOLVE ANY WATER DEPARTMENT ISSUES.
Misc
Corrective Action Required
01/15/2015
RESOLVE ANY PUBLIC WORKS ISSUES. SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
01/15/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES.
Misc
Corrective Action Required
01/15/2015
RESOLVE ANY PLANNING DEPT ISSUES.
Misc
Corrective Action Required
01/15/2015
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/15/2015
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/15/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Corrective Action Required
01/15/2015
PRIVATE DEDUCT METER FOR THE IRRIGATION SYSTEM OBSERVED WITHIN METER PIT. METER PIT AND PIPING FROM VAULT TO METER PIT BACKFILLED PRIOR TO INSPECTION; NOT INSPECTED.
Misc
Corrective Action Required
01/15/2015
ELECTRICAL CONDUIT OUTSIDE KIOSK WALLS NOT FOUND TO BE >=18" DEEP NOR PROTECTED BY A CONCRETE SLAB.
Occupancy Inspection - Codes Commercial Not Ready 1/16/2015 at 12:00 AM 01/16/2015
Misc
Corrective Action Required
01/16/2015
ROOFTOP: 1) SECURE GAS PIPE TO MANUFACTURED BLOCKS AS SHOWN ON BLOCK MANUFACURER'S INSTALLATION INSTRUCTIONS. http://www.rooftopblock.com 3) DESIGNATION OF ROOFTOP HVAC UNITS: AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & RTU # 4) DEBRIS LEFT ON ROOF SURFACE: REMOVE ALL DEBRIS AND UNUSED MATERIALS WHICH MAY DAMAGE MEMBRANE OR OBSTRUCT ROOF DRAINS.
Misc
Corrective Action Required
01/16/2015
PANEL SCHEDULE LABELING AT KIOSK TO BE COMPLETED.
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY WATER DEPARTMENT ISSUES. BEN HASKAMP @ 816-969-1930
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES. CPT JOE DIR @ 816-969-1713
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Misc
Corrective Action Required
01/16/2015
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/16/2015
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/16/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Corrective Action Required
01/16/2015
PRIVATE DEDUCT METER FOR THE IRRIGATION SYSTEM OBSERVED WITHIN METER PIT. METER PIT AND PIPING FROM VAULT TO METER PIT BACKFILLED PRIOR TO INSPECTION; NOT INSPECTED.
Occupancy Inspection - Codes Commercial Not Ready 1/22/2015 at 12:00 AM 01/22/2015
Misc
Corrective Action Required
01/16/2015
ROOFTOP: - RECENTLY-INSTALLED REFRIGERATION EQUIPMENT: CARDBOARD SLIPSHEETS UNDER 4x4 SUPPORTS ARE NOT CONSIDERED PERMANENT. USE SCRAP ROOFING MEMBRANE OR OTHER APPROVED, ROOF MEMBRANE-COMPATIBLE SLIP SHEET APPLIED TO BOTTOMS AND SCREWED TO SIDES OF 4x4s. - ENSURE ALL ROOFTOP HVAC UNITS HAVE PERMANENT DESIGNATION LABELS AFFIXED, WITH DESIGNATION REFLECTED AT ELECTRICAL PANEL. - ENSURE NO DEBRIS OR UNUSED MATERIALS WHICH MAY DAMAGE ROOF MEMBRANE OR OBSTRUCT ROOF DRAINS REMAIN ON ROOF SURFACE.
Misc
Corrective Action Required
01/16/2015
PANEL SCHEDULE LABELING AT KIOSK TO BE COMPLETED.
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY WATER DEPARTMENT ISSUES. BEN HASKAMP @ 816-969-1930
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES. CPT JOE DIR @ 816-969-1713
Misc
Corrective Action Required
01/16/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Misc
Corrective Action Required
01/16/2015
100A/B/C NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/16/2015
101/102 NOT READY FOR FINAL INSPECTION. AFTER EQUIPMENT AND SYSTEMS ARE COMPLETED 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/16/2015
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Underground Electrical Inspection - Commercial Partial 8/22/2014 at 12:00 AM 01/22/2015
Misc
Partial Correction
08/22/2014
UNDERGROUND SECONDARY ELECTRICAL SERVICE CONDUIT APPROVED TO COVER BASED ON DRAWING SHEET E401 ON WHICH F1 CALLS FOR 5 SETS OF FOUR 400 MCM COPPER CONDUCTORS RUN IN 3-1/2" RNC-40 RACEWAY. 4" CONDUIT INSTALLED. NOTE APPARENT CONFLICT WITH NOTE P-3 ON SHEET C6.0 WHICH STIPULATES 1-5" CONDUIT. A/E TO CLARIFY.
Miscellaneous Inspection Passed 1/22/2015 at 12:00 AM 01/22/2015
Occupancy Inspection - Codes Commercial Temporary C of O 1/28/2015 at 12:00 AM 01/28/2015
Misc
Corrective Action Required
01/22/2015
ROOFTOP: - RECENTLY-INSTALLED REFRIGERATION EQUIPMENT: ROOF MEMBRANE-COMPATIBLE SLIP SHEET APPLIED TO BOTTOMS AND SCREWED TO SIDES OF 4x4s. - ENSURE NO DEBRIS OR UNUSED MATERIALS WHICH MAY DAMAGE ROOF MEMBRANE OR OBSTRUCT ROOF DRAINS REMAIN ON ROOF SURFACE.
Misc
Resolved
01/28/2015
PANEL SCHEDULE LABELING AT KIOSK TO BE COMPLETED.
Misc
Corrective Action Required
01/22/2015
RESOLVE ANY WATER DEPARTMENT ISSUES. BEN HASKAMP @ 816-969-1930
Misc
Corrective Action Required
01/22/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
01/22/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES. CPT JOE DIR @ 816-969-1713
Misc
Corrective Action Required
01/22/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Misc
Corrective Action Required
01/22/2015
100A/B/C SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/22/2015
101/102 SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/28/2015
BOILER INSTALLATION REQUIRES APPROVAL OF STATE BOILER INSPECTOR PRIOR TO USE.
Occupancy Inspection - Fire Temporary C of O 1/28/2015 at 12:00 AM 01/28/2015
Misc
Corrective Action Required
01/28/2015
-close upall elec run boxes in the mexchanical room, and detail bays - fire caulk all wall penatrations in wall between mechanical room and wash bay - have the state approve the boiler for operation - post the NFPA 704 placards on doors leading into mechanical room wirh proper msds hazard ratings - supply a msds list of chemicals to remain in the building
Occupancy Inspection - Codes Commercial Partial 2/3/2015 2/3/2015 at 12:00 AM 02/03/2015
Misc
Resolved
02/03/2015
ROOFTOP: - RECENTLY-INSTALLED REFRIGERATION EQUIPMENT: ROOF MEMBRANE-COMPATIBLE SLIP SHEET APPLIED TO BOTTOMS AND SCREWED TO SIDES OF 4x4s. - ENSURE NO DEBRIS OR UNUSED MATERIALS WHICH MAY DAMAGE ROOF MEMBRANE OR OBSTRUCT ROOF DRAINS REMAIN ON ROOF SURFACE.
Misc
Corrective Action Required
01/28/2015
RESOLVE ANY WATER DEPARTMENT ISSUES. BEN HASKAMP @ 816-969-1930
Misc
Corrective Action Required
01/28/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
01/28/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES. CPT JOE DIR @ 816-969-1713
Misc
Corrective Action Required
01/28/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Misc
Corrective Action Required
01/28/2015
100A/B/C SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
01/28/2015
101/102 SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Occupancy Inspection - Codes Commercial Partial 2/5/2015 at 12:00 AM 02/05/2015
Misc
Resolved
02/05/2015
RESOLVE ANY WATER DEPARTMENT ISSUES. BEN HASKAMP @ 816-969-1930
Misc
Corrective Action Required
02/03/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Corrective Action Required
02/03/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES. CPT JOE DIR @ 816-969-1713
Misc
Corrective Action Required
02/03/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Misc
Partial Correction
02/05/2015
100A/B/C SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Partial Correction
02/05/2015
101/102 SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Corrective Action Required
02/05/2015
DRAWING REVISION REQUIRED FOR ELIMINATION OF BOILERS AND REPLACEMENT WITH WATER HEATER.
Occupancy Inspection - Fire Passed 2/9/2015 at 12:00 AM 02/09/2015
Misc
Corrective Action Required
02/09/2015
-close upall elec run boxes in the mexchanical room, and detail bays - fire caulk all wall penatrations in wall between mechanical room and wash bay - have the state approve the boiler for operation - post the NFPA 704 placards on doors leading into mechanical room wirh proper msds hazard ratings - supply a msds list of chemicals to remain in the building
Occupancy Inspection - Codes Commercial Temporary C of O 2/12/2015 at 12:00 AM 02/12/2015
Misc
Corrective Action Required
02/05/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Resolved
02/12/2015
RESOLVE ANY FIRE DEPARTMENT ISSUES. CPT JOE DIR @ 816-969-1713
Misc
Corrective Action Required
02/05/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Misc
Resolved
02/12/2015
100A/B/C SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Misc
Resolved
02/12/2015
101/102 SET-UP AND FINAL INSPECTION REMAIN IN PROGRESS. 1HR FIRE WALLS ARE SUBJECT TO APPROVAL.
Occupancy Inspection - Water Utilities Passed 1/28/2015 at 12:00 AM 03/26/2015
Occupancy Inspection - Codes Commercial Full C of O 5/14/2015 at 12:00 AM 05/14/2015
Misc
Resolved
05/14/2015
RESOLVE ANY PUBLIC WORKS ISSUES. BOB BURNS @ 816-969-1838 SEE PW "PUNCH LIST" DATED 1/14/15
Misc
Resolved
05/14/2015
RESOLVE ANY PLANNING DEPT ISSUES. JENNIFER THOMPSON @ 816-969-1606
Occupancy Inspection - Planning Passed 1/28/2015 at 12:00 AM 05/15/2015
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit