Permit Application Status

PRCOM20140598


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140598
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
MEDICAL OFFICE EXPANSION
04/09/2014
06/05/2014
10/21/2014
10/27/2014
Locations
Contacts
TURNER CONSTRUCTION COMPANY, Address:1220 WASHINGTON STE 1000, Phone:(816) 283-0555  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
CAPITAL ELECTRIC CONSTRUCTION INC, Address:PO BOX 410079, Phone:(913) 335-1214  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
PULSE DESIGN GROUP, Address:8207 MELROSE DRIVE  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/01/2014
Brian Austerman
Misc
Corrective Action Required
07/01/2014

No Fire Dept. comments
Building Plan Review Approved 04/29/2014 06/27/2014
Mike Weisenborn
Misc
Resolved
04/23/2014

2012 IBC Chapter 7 Fire And Smoke Protection Features. Action required: Provide UL# and construction details for 2 hour fire/smoke barrier. 4/23/14 - drawing updated
Misc
Resolved
04/24/2014

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locates specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or protable lighitng equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. 4/23/14 - directed to general note on drawings that covers this issue.
Misc
Resolved
04/24/2014

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in exam rooms will have redundant ground system. 4/23/14 - directed to general note on drawings that covers this issue.
Licensed Contractors Approved 05/29/2014 06/03/2014
Joe Frogge
Business License
Corrective Action Required
04/22/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
04/22/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 04/29/2014 04/24/2014
Joe Frogge
Construction documents - Fire protection systems
Corrective Action Required
04/22/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if work is required
Construction documents for fire alarm systems
Corrective Action Required
04/22/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any modifications to the system
Building Plan Review Rejected 04/21/2014 04/17/2014
Joe Frogge
Misc
Corrective Action Required
04/17/2014

2012 IBC Chapter 7 Fire And Smoke Protection Features. Action required: Provide UL# and construction details for 2 hour fire/smoke barrier.
Misc
Corrective Action Required
04/17/2014

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locates specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or protable lighitng equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Misc
Corrective Action Required
04/17/2014

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles. 2. Metal Boxes and enclosures containing receptacles. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in exam rooms will have redundant ground system.
Licensed Contractors Rejected 04/21/2014 04/17/2014
Joe Frogge
Business License
Corrective Action Required
04/17/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
04/17/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 04/21/2014 04/17/2014
Joe Frogge
Construction documents - Fire protection systems
Corrective Action Required
04/10/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if work is required
Construction documents for fire alarm systems
Corrective Action Required
04/10/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any modifications to the system
Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $60.00 $60.00 Paid 06/05/2014
$60.00
9110078-Valuation Fee for Alteration to Commercial $511.26 $511.26 Paid 06/05/2014
$511.26
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 8/20/2014 8/20/2014 at 12:00 AM 08/20/2014
Above Ceiling Inspection Passed 9/11/2014 9/11/2014 at 12:00 AM 09/11/2014
Alarm Test Passed 10/2/2014 at 12:00 AM 10/02/2014
Occupancy Inspection - Codes Commercial Not Ready 10/13/2014 10/10/2014 at 12:00 AM 10/10/2014
Misc
Resolved
10/13/2014
EXCESSIVE BOX SETBACK AT RECEPTACLES REQUIRES INSTALLATION OF SPARK RINGS: - D293 NURSE STATION UNDER WEST COUNTER - D286 WORK AREA UNDER EAST COUNTER - D298 BREAK ROOM AT EAST WALL TALL CABINET
Misc
Corrective Action Required
10/10/2014
ELECTRICAL RECEPTACLE FOR ICEMAKER MUST BE GFCI-PROTECTED OR BE SINGLE PLUG
Misc
Corrective Action Required
10/10/2014
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Miscellaneous Inspection Passed 10/10/2014 at 12:00 AM 10/10/2014
Occupancy Inspection - Fire Temporary C of O 10/13/2014 10/13/2014 at 12:00 AM 10/13/2014
Misc
Corrective Action Required
10/13/2014
-test emergency lighting and exit lights with generator, circuits -post the suite number in the corridor
Occupancy Inspection - Codes Commercial Partial 10/14/2014 at 12:00 AM 10/14/2014
Misc
Corrective Action Required
10/10/2014
EXCESSIVE BOX SETBACK AT RECEPTACLES REQUIRES INSTALLATION OF SPARK RINGS: - D293 NURSE STATION UNDER WEST COUNTER - D286 WORK AREA UNDER EAST COUNTER - D298 BREAK ROOM AT EAST WALL TALL CABINET
Misc
Corrective Action Required
10/10/2014
ELECTRICAL RECEPTACLE FOR ICEMAKER MUST BE GFCI-PROTECTED OR BE SINGLE PLUG
Misc
Corrective Action Required
10/10/2014
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Occupancy Inspection - Codes Commercial Not Ready 10/16/2014 10/16/2014 at 12:00 AM 10/16/2014
Misc
Resolved
10/14/2014
EXCESSIVE BOX SETBACK AT RECEPTACLES REQUIRES INSTALLATION OF SPARK RINGS: - D293 NURSE STATION UNDER WEST COUNTER - D286 WORK AREA UNDER EAST COUNTER - D298 BREAK ROOM AT EAST WALL TALL CABINET
Misc
Resolved
10/16/2014
ELECTRICAL RECEPTACLE FOR ICEMAKER MUST BE GFCI-PROTECTED OR BE SINGLE PLUG
Misc
Corrective Action Required
10/14/2014
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Misc
Corrective Action Required
10/16/2014
NOT READY FOR FIRE DEPT FINAL. ELECTRICAL CONTRACTOR NOT PREPARED TO PROVIDE EMERGENCY SYSTEM TEST WITH FIRE DEPARTMENT.
Occupancy Inspection - Codes Commercial Failed 10/21/2014 10/21/2014 at 12:00 AM 10/21/2014
Misc
Resolved
10/21/2014
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Misc
Corrective Action Required
10/16/2014
NOT READY FOR FIRE DEPT FINAL. ELECTRICAL CONTRACTOR NOT PREPARED TO PROVIDE EMERGENCY SYSTEM TEST WITH FIRE DEPARTMENT.
Occupancy Inspection - Fire Passed 10/27/2014 at 12:00 AM 10/27/2014
Misc
Corrective Action Required
10/13/2014
-test emergency lighting and exit lights with generator, circuits -post the suite number in the corridor
Occupancy Inspection - Codes Commercial Full C of O 10/27/2014 at 12:00 AM 10/27/2014
Misc
Resolved
10/27/2014
NOT READY FOR FIRE DEPT FINAL. ELECTRICAL CONTRACTOR NOT PREPARED TO PROVIDE EMERGENCY SYSTEM TEST WITH FIRE DEPARTMENT.
Documents & Images
Date Uploaded File Type Document Name
04/10/2014 Letter Fire Building Plan Review
04/17/2014 Letter Codes P/R Corrections Document
04/24/2014 Letter Codes P/R Corrections Document
06/03/2014 Letter Codes Plan Review Conditions
06/05/2014 Letter Codes Building Permit
07/14/2014 Letter Fire (Sprinkler) Plan Review
08/20/2014 Letter Inspection Summary
09/11/2014 Letter Inspection Summary
10/14/2014 Letter Inspection Summary
10/16/2014 Letter Inspection Summary
10/27/2014 Letter Field Certificate of Occupancy
10/28/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home