Permit Application Status

PRCOM20140176


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140176
Building Permit - Commercial
Certificate of Occupancy
RED LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR CLOTHING STORE
02/12/2014
03/11/2014
08/18/2014
05/22/2014
Locations
Contacts
RED LEES SUMMIT EAST LLC, Address:1 E WASHINGTON ST STE 300  
NRGC, Address:21270 COUNTRY PLACE LANE, Phone:(913) 897-8221  
SET POINT MECHANICAL LLC, Address:6244 W 156TH ST, Phone:(913) 213-9465  
SJ ELECTRIC LLC, Address:PO BOX 1209, Phone:(913) 837-3549  
NORTHSIDE PLUMBING, Address:975 SWIFT, Phone:(816) 842-7900  
SARGENTI ARCHITECTS, Address:461 FROM RD, 2ND FLOOR  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/31/2014
Brian Austerman
Misc
Corrective Action Required
03/31/2014

Flow/control valves needs to be properly addressed at the panel for the address of the business
Misc
Corrective Action Required
03/31/2014

Control valves are to be marked for identification
Alarm Plan Review Released for Construction 03/18/2014
Brian Austerman
Misc
Corrective Action Required
03/18/2014

Horn strobes in restrooms to be switched to strobes only
Licensed Contractors Approved 03/14/2014 03/13/2014
Mike Weisenborn
Business License
Corrective Action Required
02/19/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
02/19/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Required Action: Licensed MEP Contractors must be listed on permit prior to approval. Provide names of MEP Contractors.
Building Plan Review Approved with Conditions 03/07/2014 03/07/2014
Mike Weisenborn
Plan Submittal 2012 Codes
Resolved
03/07/2014

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. 3/3/14 - resolved
Bldg - Accessibility - Drinking fountains 1109.5.1
Corrective Action Required
02/28/2014

2012 IBC 1109.5.1 – Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. (See code section for possible exceptions.) 3/3/14 - Water cooler will be available to public per drawings - verify at inspection
Misc
Resolved
03/07/2014

2012 IMC 717.5.4 Fire Partitions. Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing. (see code section for exceptions) 3/3/14 - wall will not be rated
Fire Plan Review Approved with Conditions 03/07/2014 03/03/2014
Brian Austerman
Address numbers required
Corrective Action Required
02/28/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE ADDRESSING ON ALL ENTRY DOORS, INCLUDING THE DOOR IN THE CORRIDOR. VERIFIED AT INSPECTION
Construction documents - Fire protection systems
Corrective Action Required
02/28/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE SPRINKLER PLANS FOR APPROVAL
Construction documents for fire alarm systems
Corrective Action Required
02/28/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ALARM PLANS FOR APPROVAL
Portable fire extinguishers - general
Corrective Action Required
02/28/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A 2A10B:C EXTINGUISHER FOR EVERY 3,000 SQ/FT
Misc
Corrective Action Required
02/28/2014

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. PROVIDE DUCT DETECTION FOR UNITS OVER 2,000 CFM
Misc
Corrective Action Required
02/28/2014

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. PROVIDE EXTERIOR EGRESS ILLUMINATION IF NOT ALREADY EXISTING
Misc
Corrective Action Required
03/03/2014

No additional FD comments 3/3/14
Building Plan Review Rejected 02/25/2014 02/19/2014
Joe Frogge
Plan Submittal 2012 Codes
Corrective Action Required
02/19/2014

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Required Action: Update code references on cover sheet to reflect correct code cycle.
Bldg - Accessibility - Drinking fountains 1109.5.1
Corrective Action Required
02/19/2014

2012 IBC 1109.5.1 – Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. (See code section for possible exceptions.) Required Action: Provide compliant drinking fountain(s) or submit letter from store owner stating that bottled water will be provided for patrons.
Misc
Corrective Action Required
02/19/2014

2012 IMC 717.5.4 Fire Partitions. Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing. (see code section for exceptions) Action Required: At corridor wall designated as a fire partition, install fire dampers at duct and transfer grilles (smoke dampers currently shown at duct penetrations and no protection designated at transfer grilles). Note: This wall is not required to be a fire partition per code, but if designated as such, it must be constructed as a fire partition including penetrations.
Fire Plan Review Approved with Conditions 02/25/2014 02/18/2014
Brian Austerman
Address numbers required
Corrective Action Required
02/18/2014

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE ADDRESSING ON ALL ENTRY DOORS, INCLUDING THE DOOR IN THE CORRIDOR. VERIFIED AT INSPECTION
Construction documents - Fire protection systems
Corrective Action Required
02/18/2014

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE SPRINKLER PLANS FOR APPROVAL
Construction documents for fire alarm systems
Corrective Action Required
02/18/2014

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE ALARM PLANS FOR APPROVAL
Portable fire extinguishers - general
Corrective Action Required
02/18/2014

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE A 2A10B:C EXTINGUISHER FOR EVERY 3,000 SQ/FT
Misc
Corrective Action Required
02/18/2014

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. PROVIDE DUCT DETECTION FOR UNITS OVER 2,000 CFM
Misc
Corrective Action Required
02/18/2014

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. PROVIDE EXTERIOR EGRESS ILLUMINATION IF NOT ALREADY EXISTING
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,230.88 $1,230.88 Paid 03/11/2014
$1,230.88
8331507-Sewer Connection Fee $150.00 $150.00 Paid 03/11/2014
$150.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 3/18/2014 3/18/2014 at 12:00 AM 03/18/2014
Misc
Corrective Action Required
03/18/2014
SOME UNDER-SLAB DWV PIPING NOT PER APPROVED DRAWING.
In-wall Inspection Partial 3/18/2014 at 12:00 AM 03/18/2014
Misc
Partial Correction
03/18/2014
OK TO COVER EHEN READY WALL FRAMING & IN-WALL SYSTEMS AT: DEMISING WALLS AT SOUTH & NORTH INTERIOR ELEVATIONS;
Underslab Plumbing Inspection - Commercial Passed 3/19/2014 3/19/2014 at 12:00 AM 03/19/2014
Misc
Resolved
03/19/2014
SOME UNDER-SLAB DWV PIPING NOT PER APPROVED DRAWING.
Underslab Electrical Inspection - Commercial Passed 3/21/2014 3/21/2014 at 12:00 AM 03/21/2014
Rated Assembly Inspection Not Ready 3/26/2014 3/26/2014 at 12:00 AM 03/26/2014
In-wall Inspection Passed 3/28/2014 3/28/2014 at 12:00 AM 03/28/2014
Misc
Resolved
03/28/2014
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT: DEMISING WALLS AT SOUTH & NORTH INTERIOR ELEVATIONS;
Electrical Service Inspection Failed 4/16/2014 4/16/2014 at 12:00 AM 04/16/2014
Misc
Corrective Action Required
04/16/2014
#6 ISOLATED GROUND CONDUCTOR FROM TRANSFORMER TO PANEL "B" PER NOTE [8] ON SHEET E-4 NOT FOUND INSTALLED. AFFIX PERMANENT LABEL "C" ON SERVICE METER ENCLOSURE.
Electrical Service Inspection Passed 4/29/2014 (8:00 to 5:00) 4/29/2014 at 12:00 AM 04/29/2014
Misc
Resolved
04/29/2014
#6 ISOLATED GROUND CONDUCTOR FROM TRANSFORMER TO PANEL "B" PER NOTE [8] ON SHEET E-4 NOT FOUND INSTALLED. AFFIX PERMANENT LABEL "C" ON SERVICE METER ENCLOSURE.
Gas Piping Inspection - Commercial Failed 5/5/2014 at 12:00 AM 05/05/2014
Misc
Corrective Action Required
05/05/2014
ROOFTOP GAS PIPING SUPPORT BLOCKS NOT PER DRAWING REQUIREMENT.
Misc
Corrective Action Required
05/05/2014
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Gas Service Inspection - Commercial Partial 5/5/2014 5/5/2014 at 12:00 AM 05/05/2014
Misc
Partial Correction
05/05/2014
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. RELEASE GAS SERVICE.
Misc
Corrective Action Required
05/05/2014
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Above Ceiling Inspection Not Ready 5/5/2014 5/5/2014 at 12:00 AM 05/05/2014
Misc
Corrective Action Required
05/05/2014
TEMPORARY ELECTRICAL WIRING NOT REMOVED FROM ABOVE CEILING SPACE.
Misc
Corrective Action Required
05/05/2014
SEVERAL ELECTRICAL JUNCTION BOXES NOT CLOSED.
Misc
Corrective Action Required
05/05/2014
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; NOT TO BE LAID LOOSE ON CEILING GRID; DROP TO TERMINATIONS WHERE LOCATED. SUPPORT FROM STRUCTURE -- NOT FROM OTHER M/E/P SYSTEMS.
Misc
Corrective Action Required
05/05/2014
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Above Ceiling Inspection Failed 5/7/2014 5/7/2014 at 12:00 AM 05/07/2014
Misc
Resolved
05/07/2014
TEMPORARY ELECTRICAL WIRING NOT REMOVED FROM ABOVE CEILING SPACE.
Misc
Resolved
05/07/2014
SEVERAL ELECTRICAL JUNCTION BOXES NOT CLOSED.
Misc
Corrective Action Required
05/05/2014
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; SUPPORT FROM STRUCTURE -- NOT FROM CEILING SUPPORT WIRES OR OTHER M/E/P SYSTEMS. CHECK ALL.
Misc
Resolved
05/07/2014
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER.
Misc
Corrective Action Required
05/07/2014
INSTALL CEILING SUPPORT WIRES STRAIGHT FROM STRUCTURE ABOVE TO MAIN TEES; DO NOT BEND AROUND HVAC DUCT OR OTHER SYSTEMS.
Above Ceiling Inspection Passed 5/8/2014 at 12:00 AM 05/08/2014
Misc
Resolved
05/08/2014
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; SUPPORT FROM STRUCTURE -- NOT FROM CEILING SUPPORT WIRES OR OTHER M/E/P SYSTEMS. CHECK ALL.
Misc
Resolved
05/08/2014
INSTALL CEILING SUPPORT WIRES STRAIGHT FROM STRUCTURE ABOVE TO MAIN TEES; DO NOT BEND AROUND HVAC DUCT OR OTHER SYSTEMS.
Gas Service Inspection - Commercial Passed 5/12/2014 at 12:00 AM 05/12/2014
Misc
Resolved
05/12/2014
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. RELEASE GAS SERVICE.
Misc
Resolved
05/12/2014
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Occupancy Inspection - Codes Commercial Failed 5/12/2014 5/12/2014 at 12:00 AM 05/12/2014
Misc
Corrective Action Required
05/12/2014
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600.3, IF INTERNALLY LIGHTED MUST BE SHOP-LABELED. INSTALL NO NON-LISTED SIGN.
Misc
Corrective Action Required
05/12/2014
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Corrective Action Required
05/12/2014
NEC 406.8; E3902.8: IN-USE WEATHERPROOF COVER REQUIRED ON ELECTRICAL RECEPTACLES AT WET LOCATIONS. SEE AT RTU.
Misc
Corrective Action Required
05/12/2014
GFI ELECT RECEPT AT RTU NO TRIPPING ON TEST
Misc
Corrective Action Required
05/12/2014
GFI ELECT RECEPTS AT RESTROOMS NOT TRIPPING; SIMILAR AT STOCK ROOM.
Misc
Corrective Action Required
05/12/2014
LOOSE ELECT RECEPTS: [100] N.E. & S.E.
Misc
Corrective Action Required
05/12/2014
FLOOR SINK IN "MENS' NOT SEALED AT PERIMETER
Misc
Corrective Action Required
05/12/2014
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF.
Misc
Corrective Action Required
05/12/2014
ENSURE ELECT PANEL SCHEDULES ARE COMPLETE, CORRECT, CLEAR AND LEGIBLE. ALSO LABEL PANEL FRONTS.
Misc
Corrective Action Required
05/12/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Alarm Test Passed 5/12/2014 at 12:00 AM 05/12/2014
Sprinkler - Flow Test Passed 5/12/2014 at 12:00 AM 05/12/2014
Occupancy Inspection - Fire Temporary C of O 5/12/2014 5/12/2014 at 12:00 AM 05/12/2014
Misc
Corrective Action Required
05/12/2014
label the sprinkler sys isolation valves 880 C (north) 880 C (south0 readable from the ground replace all painted sprinkler heads and install eschutions throughout remove all dust covers from the smoke detectors remoce the constrction covers fromant sprinkler heads install outlet cover plates and switch plates as needed install the main elec panel covers mount fire extgs in locations as discussed
Occupancy Inspection - Fire Passed 5/13/2014 at 12:00 AM 05/13/2014
Misc
Corrective Action Required
05/12/2014
label the sprinkler sys isolation valves 880 C (north) 880 C (south0 readable from the ground replace all painted sprinkler heads and install eschutions throughout remove all dust covers from the smoke detectors remoce the constrction covers fromant sprinkler heads install outlet cover plates and switch plates as needed install the main elec panel covers mount fire extgs in locations as discussed
Occupancy Inspection - Codes Commercial Temporary C of O 5/19/2014 5/19/2014 at 12:00 AM 05/19/2014
Misc
Resolved
05/19/2014
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600.3, IF INTERNALLY LIGHTED MUST BE SHOP-LABELED. INSTALL NO NON-LISTED SIGN.
Misc
Resolved
05/19/2014
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Resolved
05/19/2014
NEC 406.8; E3902.8: IN-USE WEATHERPROOF COVER REQUIRED ON ELECTRICAL RECEPTACLES AT WET LOCATIONS. SEE AT RTU.
Misc
Resolved
05/19/2014
GFI ELECT RECEPT AT RTU NO TRIPPING ON TEST
Misc
Resolved
05/19/2014
GFI ELECT RECEPTS AT RESTROOMS NOT TRIPPING; SIMILAR AT STOCK ROOM.
Misc
Corrective Action Required
05/12/2014
LOOSE ELECT RECEPTS: [100] N.E.
Misc
Resolved
05/19/2014
FLOOR SINK IN "MENS' NOT SEALED AT PERIMETER
Misc
Resolved
05/19/2014
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF.
Misc
Corrective Action Required
05/12/2014
DESIGNATE ELECTRICAL PANELS AT PANEL FRONTS. 24 POSTION ELECT PANEL HAS 42 POSTION PANEL SCHEDULE.
Misc
Resolved
05/19/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Codes Commercial Partial 5/20/2014 5/20/2014 at 12:00 AM 05/20/2014
Misc
Corrective Action Required
05/19/2014
LOOSE ELECT RECEPTS: [100] N.E.
Misc
Resolved
05/20/2014
DESIGNATE ELECTRICAL PANELS AT PANEL FRONTS. 24 POSTION ELECT PANEL HAS 42 POSTION PANEL SCHEDULE.
Occupancy Inspection - Codes Commercial Full C of O 5/22/2014 5/22/2014 at 12:00 AM 05/22/2014
Misc
Resolved
05/22/2014
LOOSE ELECT RECEPTS: [100] N.E.
Gas Piping Inspection - Commercial Passed 5/12/2014 at 12:00 AM 06/03/2014
Misc
Resolved
06/03/2014
ROOFTOP GAS PIPING SUPPORT BLOCKS NOT PER DRAWING REQUIREMENT.
Misc
Resolved
06/03/2014
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Rated Assembly Inspection Passed 3/26/2014 at 12:00 AM 06/03/2014
Documents & Images
Date Uploaded File Type Document Name
02/18/2014 Letter Fire Building Plan Review
02/19/2014 Letter Codes P/R Corrections Document
03/03/2014 Letter Fire Building Plan Review
03/11/2014 Letter Codes Building Permit
03/11/2014 Letter Codes Plan Review Conditions
03/18/2014 Letter Inspection Summary
03/18/2014 Letter Fire (Alarm) Plan Review Notice
03/19/2014 Letter Inspection Summary
03/21/2014 Letter Inspection Summary
03/28/2014 Letter Inspection Summary
03/31/2014 Letter Fire (Sprinkler) Plan Review
04/16/2014 Letter Inspection Summary
04/29/2014 Letter Inspection Summary
05/05/2014 Letter Inspection Summary
05/07/2014 Letter Inspection Summary
05/08/2014 Letter Inspection Summary
05/12/2014 Letter Inspection Summary
05/19/2014 Letter Codes Temporary Certificate of Occupancy
05/22/2014 Letter Field Certificate of Occupancy
05/23/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home