Permit Application Status

PRCOM20132712


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20132712
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
CHANGE OF TENANT
TENANT FINISH FOR MEDICAL OFFICE. SPACE WAS PREVIOUSLY PART OF UNIFORM SOURCE.
12/23/2013
02/20/2014
08/18/2014
04/24/2014
Locations
Contacts
FMS, Address:5721 THEDEN, Phone:(913) 260-8216  
FMS, Address:5721 THEDEN, Phone:(913) 260-8216  
FMS, Address:5721 THEDEN, Phone:(913) 260-8216  
COOTER'S PLUMBING, Address:P O BOX 683, Phone:(816) 419-5574  
SCHARHAG ARCHITECTS, Address:310 ARMOUR RD #202, Phone:(816) 221-9297  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 02/26/2014 02/20/2014
Mike Weisenborn
Accessibility - Refrigerator/Freezer - General requirements
Informational
02/19/2014

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for informational purposes.
NEC - Receptacles - Grounding
Corrective Action Required
02/19/2014

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - This comment applies to electrical in the treatment rooms. Add additional information on the plans. Mike Weisenborn 01/14/2014 11:07 AM - Notes have been added to the plans.
Mech - Dryer exhaust - Manufacturer's instructions 504.6.4.2
Informational
02/20/2014

2012 IMC 504.6.4.2 – Manufacturer’s instructions. The maximum length of the exhaust duct shall be determined by the dryer manufacturer’s installation instructions. The code official shall be provided with a copy of the installation instructions for the make and model of the dryer. Where the exhaust duct is to be concealed, the installation instructions shall be provided to the code official prior to the concealment inspection. In the absence of fitting equivalent length calculations from the clothes dryer manufacturer, Table 504.6.1 shall be used. Action required - This comment is for information purposes.
Fire Plan Review Approved with Conditions 02/26/2014 02/20/2014
Mike Weisenborn
Portable fire extinguishers - general
Corrective Action Required
02/19/2014

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two 2A:10B:C fire extinguishers at a conspicuous location in a normal pathway, with not more than a 75 foot travel distance. Verified at inspection.
Misc
Corrective Action Required
02/19/2014

1014.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. 1.Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high-hazard occupancy and provide a discernible path of egress travel to an exit. Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group. 2. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through stockrooms in Group M occupancies when all of the following are met: 2.1. The stock is of the same hazard classification as that found in the main retail area; 2.2. Not more than 50 percent of the exit access is through the stockroom; 2.3.The stockroom is not subject to locking from the egress side; and 2.4. There is a demarcated, minimum 44-inch-wide (1118 mm) aisle defined by full or partial height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. 3. An exit access shall not pass through a room that can be locked to prevent egress. 4. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. Verified at inspection.
Address numbers required
Corrective Action Required
02/19/2014

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The front and rear doors shall be posted with the correct address. Verified at inspection.
Misc
Corrective Action Required
02/19/2014

All exit and emergency lighting shall be maintained. Verified at inspection.
Misc
Corrective Action Required
02/19/2014

1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Forces shall be applied to the latch side. The rear door shall swing outward with the proper door hardware. Verified at inspection. CORRECTED 2/20/14
Licensed Contractors Approved 07/06/2014 02/19/2014
Mike Weisenborn
Business License
Resolved
02/20/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - A minimum of a Class B license is required. Provide the name of the licensed general contractor prior to permit approval.
License contractors
Resolved
02/20/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Fire Plan Review Approved with Conditions 01/15/2014 01/14/2014
Mike Weisenborn
Portable fire extinguishers - general
Corrective Action Required
01/09/2014

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two 2A:10B:C fire extinguishers at a conspicuous location in a normal pathway, with not more than a 75 foot travel distance. Verified at inspection.
Misc
Corrective Action Required
01/09/2014

1014.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. 1.Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high-hazard occupancy and provide a discernible path of egress travel to an exit. Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group. 2. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through stockrooms in Group M occupancies when all of the following are met: 2.1. The stock is of the same hazard classification as that found in the main retail area; 2.2. Not more than 50 percent of the exit access is through the stockroom; 2.3.The stockroom is not subject to locking from the egress side; and 2.4. There is a demarcated, minimum 44-inch-wide (1118 mm) aisle defined by full or partial height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. 3. An exit access shall not pass through a room that can be locked to prevent egress. 4. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. Verified at inspection.
Address numbers required
Corrective Action Required
01/09/2014

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The front and rear doors shall be posted with the correct address. Verified at inspection.
Misc
Corrective Action Required
01/09/2014

All exit and emergency lighting shall be maintained. Verified at inspection.
Misc
Corrective Action Required
01/09/2014

1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Forces shall be applied to the latch side. The rear door shall swing outward with the proper door hardware. Verified at inspection.
Building Plan Review Approved with Conditions 01/15/2014 01/14/2014
Mike Weisenborn
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
01/14/2014

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met at the reception counter. Mike Weisenborn 01/14/2014 11:06 AM - Notes have been added to the plans.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Resolved
01/14/2014

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Show compliance at the breakroom sink. Mike Weisenborn 01/14/2014 11:07 AM - Notes have been added to the plans.
Accessibility - Refrigerator/Freezer - General requirements
Informational
01/09/2014

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for informational purposes.
NEC - Receptacles - Grounding
Corrective Action Required
01/09/2014

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - This comment applies to electrical in the treatment rooms. Add additional information on the plans. Mike Weisenborn 01/14/2014 11:07 AM - Notes have been added to the plans.
Building Plan Review Rejected 01/07/2014 01/07/2014
Mike Weisenborn
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
01/07/2014

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met at the reception counter.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
01/07/2014

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Show compliance at the breakroom sink.
Accessibility - Refrigerator/Freezer - General requirements
Informational
01/07/2014

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for informational purposes.
NEC - Receptacles - Grounding
Corrective Action Required
01/07/2014

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - This comment applies to electrical in the treatment rooms. Add additional information on the plans.
Fire Plan Review Approved with Conditions 01/07/2014 12/26/2013
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
12/26/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two 2A:10B:C fire extinguishers at a conspicuous location in a normal pathway, with not more than a 75 foot travel distance. Verified at inspection.
Misc
Corrective Action Required
12/26/2013

1014.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. 1.Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high-hazard occupancy and provide a discernible path of egress travel to an exit. Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group. 2. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through stockrooms in Group M occupancies when all of the following are met: 2.1. The stock is of the same hazard classification as that found in the main retail area; 2.2. Not more than 50 percent of the exit access is through the stockroom; 2.3.The stockroom is not subject to locking from the egress side; and 2.4. There is a demarcated, minimum 44-inch-wide (1118 mm) aisle defined by full or partial height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. 3. An exit access shall not pass through a room that can be locked to prevent egress. 4. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. Verified at inspection.
Address numbers required
Corrective Action Required
12/26/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The front and rear doors shall be posted with the correct address. Verified at inspection.
Misc
Corrective Action Required
12/26/2013

All exit and emergency lighting shall be maintained. Verified at inspection.
Misc
Corrective Action Required
12/26/2013

1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Forces shall be applied to the latch side. The rear door shall swing outward with the proper door hardware. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $306.38 $306.38 Paid 02/20/2014
$306.38
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 2/21/2014 at 12:00 AM 02/21/2014
Misc
Partial Correction
02/21/2014
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: SPACES #3-7 AFTER CRIPPLE STUDS ABOVE DOORS ARE FULLY SCREWED AT CONNECTIONS;
Underslab Plumbing Inspection - Commercial Not Ready 3/5/2014 3/5/2014 at 12:00 AM 03/05/2014
Misc
Corrective Action Required
03/05/2014
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Underslab Plumbing Inspection - Commercial Passed 3/6/2014 3/6/2014 at 12:00 AM 03/06/2014
Misc
Resolved
03/06/2014
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Above Ceiling Inspection Not Ready 3/11/2014 3/11/2014 at 12:00 AM 03/11/2014
Misc
Corrective Action Required
03/11/2014
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE. CALL-AHEAD MADE ONE HOUR IN ADVANCE -- AS REQUESTED.
In-wall Inspection Partial 3/13/2014 at 12:00 AM 03/13/2014
Misc
Partial Correction
02/21/2014
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: SPACES #3-7; SPACE 10 OK TO ONE-SIDE ONLY IN-WALL SYSTEMS AT SPACES 8,9,10 TO BE REQUESTED FOR FULL IN-WALL INSPECTION AFTER ALL WORK INCLUDING REMOVAL OF ABANDONED CONCEALED ELECTRICAL WIRING IS COMPLETED. PLUMBING ONLY IS PRESENTLY APPROVED.
In-wall Inspection Passed 3/14/2014 3/14/2014 at 12:00 AM 03/14/2014
Misc
Resolved
03/14/2014
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: SPACES #3-7; SPACE 10 OK TO ONE-SIDE ONLY IN-WALL SYSTEMS AT SPACES 8,9,10 TO BE REQUESTED FOR FULL IN-WALL INSPECTION AFTER ALL WORK INCLUDING REMOVAL OF ABANDONED CONCEALED ELECTRICAL WIRING IS COMPLETED. PLUMBING ONLY IS PRESENTLY APPROVED.
Above Ceiling Inspection Partial 4/3/2014 4/3/2014 at 12:00 AM 04/03/2014
Misc
Corrective Action Required
03/11/2014
1.APPROVED:OPEN AREA, 5 OFFICES ON THE SOUTH APPROVED FOR CEILING TILE- 2. BATHROOM-KIT-REAR HALL-NOT READY-
Occupancy Inspection - Codes Commercial Not Ready 4/4/2014 4/4/2014 at 12:00 AM 04/04/2014
Misc
Corrective Action Required
04/04/2014
THIS IS NOT READY FOR INSPECTION: OPEN BOXES THROUGHOUT, INCLUDING IN AREAS ABOVE CEILING THAT HAVE YET TO BE APPROVED. CONTRACTOR WAS INFORMED THAT A GROUNDNING ELECTRODE CONDUCTOR WOULD NEED TO BE INSTALLED FROM THE MAIN DISCONNECT TO BUILDING STEEL. SUB-PANEL NEEDS BONDING JUMPERS REMOVED AND GROUNDED CONDUCTORS ISOLATED FROM THE PANEL. METALLIC TUBING IS UTILIZED AS THE EQUIPMENT GROUND FOR THE SUB-PANEL. BONDING JUMPER WILL NEED TO BE INSTALLED AT THE 90* FITTING ABOVE THE BACK DOOR TO ENSURE CONTINUITY.
Occupancy Inspection - Fire Not Ready 4/4/2014 4/4/2014 at 12:00 AM 04/07/2014
Above Ceiling Inspection Passed 4/10/2014 at 12:00 AM 04/10/2014
Misc
Resolved
04/10/2014
1.APPROVED:OPEN AREA, 5 OFFICES ON THE SOUTH APPROVED FOR CEILING TILE- 2. BATHROOM-KIT-REAR HALL-NOT READY-
Occupancy Inspection - Fire Passed 4/10/2014 at 12:00 AM 04/10/2014
Occupancy Inspection - Codes Commercial Temporary C of O 4/10/2014 4/10/2014 at 12:00 AM 04/10/2014
Misc
Resolved
04/10/2014
THIS IS NOT READY FOR INSPECTION: OPEN BOXES THROUGHOUT, INCLUDING IN AREAS ABOVE CEILING THAT HAVE YET TO BE APPROVED. CONTRACTOR WAS INFORMED THAT A GROUNDNING ELECTRODE CONDUCTOR WOULD NEED TO BE INSTALLED FROM THE MAIN DISCONNECT TO BUILDING STEEL. SUB-PANEL NEEDS BONDING JUMPERS REMOVED AND GROUNDED CONDUCTORS ISOLATED FROM THE PANEL. METALLIC TUBING IS UTILIZED AS THE EQUIPMENT GROUND FOR THE SUB-PANEL. BONDING JUMPER WILL NEED TO BE INSTALLED AT THE 90* FITTING ABOVE THE BACK DOOR TO ENSURE CONTINUITY.
Occupancy Inspection - Codes Commercial Partial 4/10/2014 at 12:00 AM 04/10/2014
Misc
Corrective Action Required
04/10/2014
Call for inspection when rear corridor floor is uniformly leveled to comply with ANSI maximum elevation changes. Also, at 210 back room finish floor channel pour-back level with existing floor surface + use non-protruding plug at cleanout.
Occupancy Inspection - Codes Commercial Partial 4/16/2014 at 12:00 AM 04/16/2014
Misc
Corrective Action Required
04/10/2014
Call for inspection when rear corridor floor is uniformly leveled to comply with ANSI maximum elevation changes. Also, at 210 back room finish floor channel pour-back level with existing floor surface + use non-protruding plug at cleanout.
Occupancy Inspection - Codes Commercial Full C of O 4/24/2014 at 12:00 AM 04/24/2014
Misc
Resolved
04/24/2014
Call for inspection when rear corridor floor is uniformly leveled to comply with ANSI maximum elevation changes. Also, at 210 back room finish floor channel pour-back level with existing floor surface + use non-protruding plug at cleanout.
Documents & Images
Date Uploaded File Type Document Name
12/31/2013 Letter Fire Building Plan Review
01/07/2014 Letter Codes Plan Review Conditions
01/13/2014 Letter Fire Building Plan Review
02/20/2014 Letter Codes Plan Review Conditions
02/20/2014 Letter Codes Building Permit
02/20/2014 Letter Fire Building Plan Review
02/21/2014 Letter Inspection Summary
03/05/2014 Letter Inspection Summary
03/06/2014 Letter Inspection Summary
03/11/2014 Letter Inspection Summary
03/13/2014 Letter Inspection Summary
03/14/2014 Letter Inspection Summary
04/03/2014 Letter Inspection Summary
04/04/2014 Letter Inspection Summary
04/10/2014 Letter Codes Temporary Certificate of Occupancy
04/24/2014 Letter Field Certificate of Occupancy
04/25/2014 Letter Codes Final Certificate of Occupancy
08/18/2014 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home