Permit Application Status

PRCOM20132665


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20132665
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
KITCHEN/DINING EXPANSION - TEMP KITCHEN
12/16/2013
12/19/2013
02/20/2014
Locations
Contacts
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
US ENGINEERING COMPANY, Address:3433 ROANOKE RD, Phone:(816) 753-6969  
R F FISHER ELECTRIC COMPANY LLC, Address:5299 DTC BLVD STE 600, Phone:(913) 384-1500  
US ENGINEERING COMPANY, Address:3433 ROANOKE RD, Phone:(816) 753-6969  
ACI BOLAND, Address:11229 NALL SUITE 140  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 01/21/2014 01/17/2014
Mike Weisenborn
Misc
Informational
01/14/2014

2006 IPC - Section 608.16.10 - Coffee machines and noncarbonated beverage dispensers. The water supply connection to coffee machines and noncarbonated beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022 or by an air gap. Action required - This comment is for information purposes and compliance will be verified on inspection.
Fire Plan Review Approved with Conditions 01/21/2014 01/16/2014
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
01/14/2014

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if alterations are made to the sprinkler system
Construction documents for fire alarm systems
Corrective Action Required
01/14/2014

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for any alterations to the alarm system
Building Plan Review Approved with Conditions 12/20/2013 12/17/2013
Mike Weisenborn
Misc
Informational
12/17/2013

2006 IPC - Section 608.16.10 - Coffee machines and noncarbonated beverage dispensers. The water supply connection to coffee machines and noncarbonated beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022 or by an air gap. Action required - This comment is for information purposes and compliance will be verified on inspection.
Fire Plan Review Approved with Conditions 12/30/2013 12/17/2013
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
12/17/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans if alterations are made to the sprinkler system
Construction documents for fire alarm systems
Corrective Action Required
12/17/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for any alterations to the alarm system
Licensed Contractors Approved 12/16/2013 12/16/2013
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $247.43 $247.43 Paid 12/18/2013
$247.43
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Partial 1/14/2014 at 12:00 AM 01/14/2014
Misc
Partial Correction
01/14/2014
1ST FLR TEMP KITCHEN GRAB-N-GO AREA OK FOR INTERIM USE
In-wall Inspection Partial 1/28/2014 at 12:00 AM 01/28/2014
Misc
Partial Correction
01/28/2014
OK TO COVER WHEN READY WALL FAMING AND IN-WALL SYSTEMS AT: FLOOR-TO-DECK FACE OF WALL AT TEMPORARY KITCHEN NE -- FRAMING ONLY;
In-wall Inspection Partial 1/31/2014 1/31/2014 at 12:00 AM 01/31/2014
Misc
Partial Correction
01/28/2014
OK TO COVER WHEN READY WALL FAMING AND IN-WALL SYSTEMS AT: FLOOR-TO-DECK FACE OF WALL AT TEMPORARY KITCHEN NE -- FRAMING ONLY; FRAMING AND CONCEALED SYSTEMS AT ALL TEMPORARY KITCHEN WALLS
Above Ceiling Inspection Partial 2/12/2014 2/12/2014 at 12:00 AM 02/12/2014
Misc
Partial Correction
02/12/2014
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS ON TEMPORARY BASIS AT TEMPORARY KITCHEN NORTH 25'. SOME NON-CRITICAL ISSUES ACCEPTED UNTIL PERMANENT RENOVATION PROCEEDS.
Miscellaneous Inspection Partial 2/14/2014 at 12:00 AM 02/14/2014
Misc
Partial Correction
01/14/2014
1ST FLR TEMP KITCHEN GRAB-N-GO AREA OK FOR INTERIM USE
Above Ceiling Inspection Passed 2/12/2014 at 12:00 AM 02/20/2014
Misc
Resolved
02/20/2014
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS ON TEMPORARY BASIS AT TEMPORARY KITCHEN NORTH 25'. SOME NON-CRITICAL ISSUES ACCEPTED UNTIL PERMANENT RENOVATION PROCEEDS.
In-wall Inspection Passed 1/31/2014 at 12:00 AM 02/20/2014
Misc
Resolved
02/20/2014
OK TO COVER WHEN READY WALL FAMING AND IN-WALL SYSTEMS AT: FLOOR-TO-DECK FACE OF WALL AT TEMPORARY KITCHEN NE -- FRAMING ONLY; FRAMING AND CONCEALED SYSTEMS AT ALL TEMPORARY KITCHEN WALLS
Miscellaneous Inspection Passed 2/20/2014 at 12:00 AM 02/20/2014
Misc
Resolved
02/20/2014
1ST FLR TEMP KITCHEN GRAB-N-GO AREA OK FOR INTERIM USE
Final Inspection - Commercial Passed 2/20/2014 at 12:00 AM 02/20/2014
Documents & Images
Date Uploaded File Type Document Name
12/17/2013 Letter Fire Building Plan Review
12/17/2013 Letter Codes Plan Review Conditions
12/18/2013 Letter Codes Building Permit
01/14/2014 Letter Inspection Summary
01/15/2014 Letter DOC011514-002.pdf
01/16/2014 Letter Fire Building Plan Review
01/28/2014 Letter Inspection Summary
01/31/2014 Letter Inspection Summary
02/12/2014 Letter Inspection Summary
02/20/2014 Letter Inspection Summary
02/21/2014 Letter DOC022114.pdf
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home