Permit Application Status

PRCOM20132019


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20132019
Building Permit - Commercial
Final Completion
SARAH PEPPER ENTERPRISES LLC
NEW OTHER (COMMERCIAL)
200 AMP FESTIVAL SERVICE
09/12/2013
09/12/2013
09/24/2013
Locations
Contacts
JASON WRIGHT ELECTRIC, Address:PO BOX 218, Phone:(816) 246-5826  
SARAH PEPPER ENTERPRISES LLC, Address:5925 WALNUT  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Deferred 09/24/2013 09/12/2013
Codes Admin
Licensed Contractors Approved 09/12/2013 09/12/2013
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 09/12/2013
$30.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 9/20/2013 at 12:00 AM 09/20/2013
Misc
Corrective Action Required
09/20/2013
NEC 250.92B; IRC E3510.1. BONDING OF SERVICE ENCLOSURES & EQUIPMENT: NIPPLES ENTERING THROUGH REMAINING KNOCKOUTS REQUIRE BONDING BUSHINGS WITH BONDING JUMPERS TERMINATED AT ENCLOSURE HOUSINGS. LOCKNUT NOT SUFFICIENT FOR BONDING.
Misc
Corrective Action Required
09/20/2013
ELECTRICAL SERVICE ADDRESS IDENTIFICATION: NOT FOUND AFFIXED AT METER / DISCONNECT
Electrical Service Inspection Passed 9/23/2013 9/23/2013 at 12:00 AM 09/23/2013
Misc
Resolved
09/23/2013
NEC 250.92B; IRC E3510.1. BONDING OF SERVICE ENCLOSURES & EQUIPMENT: NIPPLES ENTERING THROUGH REMAINING KNOCKOUTS REQUIRE BONDING BUSHINGS WITH BONDING JUMPERS TERMINATED AT ENCLOSURE HOUSINGS. LOCKNUT NOT SUFFICIENT FOR BONDING.
Misc
Resolved
09/23/2013
ELECTRICAL SERVICE ADDRESS IDENTIFICATION: NOT FOUND AFFIXED AT METER / DISCONNECT
Final Electrical Inspection - Commercial Passed 9/23/2013 at 12:00 AM 09/23/2013
Documents & Images
Date Uploaded File Type Document Name
09/12/2013 Letter Codes Building Permit
09/20/2013 Letter Inspection Summary
09/23/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home