Permit Application Status

PRCOM20131124


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20131124
Building Permit - Commercial
Voided
BBJV LLC
PARTIAL COMMERCIAL
FOUNDATION Mike Weisenborn 07/17/2013 8:59 AM - VOIDED THE APPLICATION AS WE WERE ABLE TO ISSUE THE FULL BUILDING PERMIT
06/06/2013
07/17/2013
Locations
Contacts
MEYER BROTHERS BUILDING COMPANY, Address:800 E 101ST TER STE 120, Phone:(816) 246-4800  
  
ELECTRICAL ASSOCIATES LLC, Address:308 W ELM ST, Phone:(913) 825-2537  
FIVE STAR MECHANICAL CONTRACT INC, Address:P O BOX 11964, Phone:(816) 358-4444  
BBJV LLC, Address:3200 S OUTER RD  
GIDDY UP LLC, Address:29304 PINK HILL RD NE  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Rejected 06/20/2013 06/10/2013
Brian Austerman
Misc
Corrective Action Required
06/10/2013

Provide civil plans, including fire department access roads, fire hydrants and the FDC on the building. The FDC is to be located no more than 100' from a fire hydrant
Misc
Corrective Action Required
06/10/2013

Provide complete MEP's showing emergency lighting, exiting and details on HVAC units
Misc
Corrective Action Required
06/10/2013

Provide information on waste oil furnace and tank in order to evaluate for the need of a hazardous materials permit for storage and use
Construction documents - Fire protection systems
Corrective Action Required
06/10/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
06/10/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Knox box required
Corrective Action Required
06/10/2013

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Portable fire extinguishers - general
Corrective Action Required
06/10/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide one 2A10B:C extinguisher for every 3,000 sq/ft, verified at inspection
Licensed Contractors Approved 06/06/2013 06/06/2013
Mike Weisenborn
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
06/21/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home