Permit Application Status

PRCOM20130947


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130947
Building Permit - Commercial
Voided
Summit Development Co
ADDITION COMMERCIAL
EXPAND BUILDING AND RENOVATE RESTROOMS Mike Weisenborn 12/10/2013 8:44 AM - CONTACTED THE APPLICANT AND THE INDICATED THAT THE PROJECT WAS NOT PROCEEDING AT THIS TIME.
05/17/2013
12/10/2013
12/10/2013
Locations
Contacts
KESSINGER HUNTER & CO LC, Address:2600 GRAND #700, Phone:(816) 842-2690  
  
  
  
KIRK BOND ARCHITECT, Address:12300 E 46TH TERRACE SOUTH, Phone:(816) 808-9952  
Summit Development Co, Address:700 W 47th St Ste 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 12/13/2013 12/10/2013
Mike Weisenborn
License contractors
Corrective Action Required
05/31/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Building Plan Review Rejected 06/17/2013 06/13/2013
Mike Weisenborn
Plumb - Water closet general clearance
Resolved
06/13/2013

2006 IPC 405.3.1 - Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition, vanity or other obstruction, or closer than 30 inches center-to-center between adjacent fixtures. There shall be at least a 21-inch clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches wide and 60 inches deep. Action required - The non-accessible water closet in the women's restroom is not 60 inches deep. Make needed corrections.
Misc
Corrective Action Required
06/10/2013

Plans and specifications for the mechanical, electrical and plumbing work have not been provided. Action required - Provide additional information.
Accessibility - Maneuvering Clearance at Doors.
Resolved
06/13/2013

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the push sides of the restroom doors. Make needed corrections.
Fire Plan Review Approved with Conditions 06/17/2013 06/11/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
06/10/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
06/10/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Building Plan Review Rejected 06/03/2013 05/31/2013
Mike Weisenborn
Plumb - Water closet general clearance
Corrective Action Required
05/31/2013

2006 IPC 405.3.1 - Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition, vanity or other obstruction, or closer than 30 inches center-to-center between adjacent fixtures. There shall be at least a 21-inch clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches wide and 60 inches deep. Action required - The non-accessible water closet in the women's restroom is not 60 inches deep. Make needed corrections.
Misc
Corrective Action Required
05/31/2013

Plans and specifications for the mechanical, electrical and plumbing work have not been provided. Action required - Provide additional information.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
05/31/2013

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the push sides of the restroom doors. Make needed corrections.
Final Development Plan Review Approved 06/03/2013 05/21/2013
Mike Weisenborn
PER HECTOR SOTO
Fire Plan Review Approved with Conditions 06/03/2013 05/20/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
05/20/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
05/20/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
05/31/2013 Letter Plan Review Conditions
06/13/2013 Letter Plan Review Conditions
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home