Permit Application Status

PRCOM20130547


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130547
Building Permit - Commercial
Certificate of Occupancy
RAINTREE VILLAGE SHOPPING CENTER LLC
CHANGE OF TENANT
DRY CLEANING DROP OFF BUSINESS - PERMIT IS FOR A CHANGE OF USE ONLY. NO WORK TO BE DONE IN THE SPACE. ONLY AN OCCUPANCY INSPECTION REQUIRED
04/03/2013
04/15/2013
08/07/2015
Locations
Contacts
WIL-KLEEN INC, Address:480 4 S NOLAND RD, Phone:(816) 554-1040  
RAINTREE VILLAGE SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 400  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 04/15/2013 04/15/2013
Codes Admin
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
04/15/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - An accessible counter shall be provided.This will be verified on inspection.
Plumb - Required public toilet facilities
Corrective Action Required
04/15/2013

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - A clear path shall be provided from the front of the store to the restrooms. This comment is for information purposes and will be verified on inspection.
Misc
Corrective Action Required
04/15/2013

This permit is to establish an occupancy and does not cover any alterations to the structure or the mechanical, electrical or plumbing systems.
Licensed Contractors Approved 04/15/2013 04/15/2013
Mike Weisenborn
Fire Plan Review Approved with Conditions 04/15/2013 04/04/2013
Brian Austerman
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
04/04/2013

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing sprinkler system shall have a current certification inspection at time of final. To be verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
04/04/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for any sprinkler head modifications or relocations if any is required
Construction documents for fire alarm systems
Corrective Action Required
04/04/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for any notification device relocations or additions. Storbes are required in bathrooms and horn/strobes are required in the open area
Address numbers required
Corrective Action Required
04/04/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All exterior doors leading to the space shall be addressed the same, verified at inspection
Hazardous material identification
Corrective Action Required
04/04/2013

2006 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. If there will be cleaning chemicals or other hazardous materials stored provide a hazardous materials inventory statement and management plan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 04/15/2013
$30.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Commercial Passed 08/07/2015
Occupancy Inspection - Codes Commercial Full C of O 08/07/2015
Occupancy Inspection - Fire Passed 12/31/2015
Documents & Images
Date Uploaded File Type Document Name
04/15/2013 Letter Plan Review Conditions
04/15/2013 Letter Building Permit
06/27/2013 Letter Fire Building Plan Review
08/07/2015 Letter Inspection Summary
08/26/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home