Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved
|
04/02/2013
|
08/27/2013
|
|
Brian Austerman
|
|
|
Fire Plan Review
|
Approved
|
05/23/2013
|
08/06/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
As per prior agreement, no occupancy of the 5th floor shall be allowed until the requirements for high rise and fire control room have been met
|
|
Misc
Corrective Action Required
3006.4 Medical gas systems.
Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter.
Provide med gas system certification
|
|
Misc
Corrective Action Required
Chemotherapy hoods shall be approved by codes administration, for information only
|
|
Misc
Corrective Action Required
907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Duct detectors shall transmit a supervisory signal to the panel and shut down unit, for information only
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Verified at inspection
|
|
Misc
Corrective Action Required
2306.6.1 Access doors.
Where building access is required by Table 2306.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder.
Doors equipped with card readers or other access controlls shall unlock upon the activation of the fire alarm, verified at inspection
|
|
Misc
Corrective Action Required
8/6/13 Resub reviesed for changes to the infusion walls. No additional fire department comments
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
|
06/19/2013
|
|
Brian Austerman
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule hydrostatic testing
|
|
|
Building Plan Review
|
Approved
|
05/23/2013
|
05/21/2013
|
|
Mike Weisenborn
|
|
Suite address
This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located.
Action required - Provide the suite number for this tenant finish.
|
|
Misc
I am unable to locate the finished area covered under this permit.
Action required - Provide the area of the finished space covered under this permit application.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
05/23/2013
|
05/16/2013
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
As per prior agreement, no occupancy of the 5th floor shall be allowed until the requirements for high rise and fire control room have been met
|
|
Misc
Corrective Action Required
3006.4 Medical gas systems.
Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter.
Provide med gas system certification
|
|
Misc
Corrective Action Required
Chemotherapy hoods shall be approved by codes administration, for information only
|
|
Misc
Corrective Action Required
907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Duct detectors shall transmit a supervisory signal to the panel and shut down unit, for information only
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Verified at inspection
|
|
Misc
Corrective Action Required
2306.6.1 Access doors.
Where building access is required by Table 2306.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder.
Doors equipped with card readers or other access controlls shall unlock upon the activation of the fire alarm, verified at inspection
|
|
|
Building Plan Review
|
Rejected
|
04/02/2013
|
04/02/2013
|
|
Mike Weisenborn
|
|
Suite address
Corrective Action Required
This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located.
Action required - Provide the suite number for this tenant finish.
|
|
Misc
Corrective Action Required
I am unable to locate the finished area covered under this permit.
Action required - Provide the area of the finished space covered under this permit application.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
04/02/2013
|
03/22/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
As per prior agreement, no occupancy of the 5th floor shall be allowed until the requirements for high rise and fire control room have been met
|
|
Misc
Corrective Action Required
3006.4 Medical gas systems.
Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter.
Provide med gas system certification
|
|
Misc
Corrective Action Required
Chemotherapy hoods shall be approved by codes administration, for information only
|
|
Misc
Corrective Action Required
907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Duct detectors shall transmit a supervisory signal to the panel and shut down unit, for information only
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Verified at inspection
|
|
Misc
Corrective Action Required
2306.6.1 Access doors.
Where building access is required by Table 2306.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder.
Doors equipped with card readers or other access controlls shall unlock upon the activation of the fire alarm, verified at inspection
|
|
|
Licensed Contractors
|
Approved
|
03/21/2013
|
03/21/2013
|
|
Codes Admin
|
|
|