Summary
PRCOM20130437
Building Permit - Commercial
Final Completion
MIDWEST DIVISION LSH LLC
ALTERATION COMMERCIAL
CONSTRUCT WALL TO SEPARATE CONFERENCE ROOM INTO TWO OFFICES
03/20/2013
04/01/2013
02/05/2016
Locations
Contacts
MID AMERICA CONTRACTORS INC / MICHAEL'S BASEMENT, Address:1101 N HWY 7, Phone:(816) 540-3040  
H & S ELECTRIC, Address:4901 ANTIOCH RD, Phone:(913) 206-1486  
MIDWEST DIVISION LSH LLC, Address:PO BOX 1504  
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 04/01/2013 04/01/2013
Mike Weisenborn
Misc
Corrective Action Required
04/01/2013

Alterations to the existing sprinkler system may be required based on required after installation of the new wall. To be determined on inspection.
Building Plan Review Approved 04/01/2013 03/26/2013
Mike Weisenborn
Licensed Contractors Approved 03/20/2013 03/20/2013
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 04/01/2013
$30.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Failed 4/4/2013 4/4/2013 at 12:00 AM 04/04/2013
Misc
Corrective Action Required
04/04/2013
ALL WIRING ON THE SAME BRANCH CIRCUIT AS A RECEPTACLE IN A PATIENT CARE AREA ARE REQUIERD TO HAVE A REDUNDANT GROUDING CONDUCTOR. THE LIGHTING AND WIRING ABOVE CEILING NO NOT HAVE REDUNDANT GROUNGING. OKAY TO COVER DIMISING WALL AS MC CABLE IN WALL IS OKAY.
Rough Electrical Inspection - Commercial Passed 4/10/2013 at 12:00 AM 04/10/2013
Misc
Resolved
04/10/2013
ALL WIRING ON THE SAME BRANCH CIRCUIT AS A RECEPTACLE IN A PATIENT CARE AREA ARE REQUIERD TO HAVE A REDUNDANT GROUDING CONDUCTOR. THE LIGHTING AND WIRING ABOVE CEILING NO NOT HAVE REDUNDANT GROUNGING. OKAY TO COVER DIMISING WALL AS MC CABLE IN WALL IS OKAY.
Occupancy Inspection - Fire Passed 12/31/2015
Investigation Inspection Complete 02/05/2016
Final Electrical Inspection - Commercial Passed 02/05/2016
Underslab Electrical Inspection - Commercial Not Complete 01/09/2018
Underground Electrical Inspection - Commercial Not Complete 01/09/2018
All Rough Inspection - Commercial Not Complete 01/09/2018
In-wall Inspection Not Complete 01/09/2018
Occupancy Inspection - Codes Commercial Not Complete 01/09/2018
Documents & Images
Date Uploaded File Type Document Name
04/01/2013 Letter Plan Review Conditions
04/01/2013 Letter Building Permit
04/04/2013 Letter Inspection Summary
04/10/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home