Permit Application Status

PRCOM20130415


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130415
Building Permit - Commercial
Final Completion
ALLEGHENY PROPERTIES LLC
CHANGE OF TENANT
TENANT FINISH
03/18/2013
04/09/2013
11/27/2013
Locations
Contacts
HGK CONSTRUCTION MANAGEMENT INC, Address:11705 E 71ST CT, Phone:(816) 356-7555  
BRINTON ELECTRIC COMPANY INC, Address:10100 E 65TH ST STE B, Phone:(816) 356-0922  
ALLEGHENY PROPERTIES LLC, Address:7401 E 67TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 03/28/2013 03/26/2013
Mike Weisenborn
Fire Plan Review Approved with Conditions 03/28/2013 03/20/2013
Brian Austerman
Portable fire extinguishers - general
Corrective Action Required
03/20/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B:C extinguisher for every 3000 sq/ft
Misc
Corrective Action Required
03/20/2013

Recommend installing combination exit sign/emergency lighting over the exits
Licensed Contractors Approved 03/28/2013 03/18/2013
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $81.70 $81.70 Paid 03/26/2013
$81.70
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 4/10/2013 4/10/2013 at 12:00 AM 04/10/2013
Above Ceiling Inspection Failed 7/3/2013 7/3/2013 at 12:00 AM 07/03/2013
Misc
Corrective Action Required
07/03/2013
REMOVE ALL ABANDONED MATERIAL: - ABANDONED?? HVAC DUCT - TOP OF DEMOLISHED PARTITIONS, OR TO HEIGHT CERTIFIED BY A/E AS NOT REPRESENTING SAFETY HAZARD.
Misc
Corrective Action Required
07/03/2013
SMACNA / AIR DIFUSSION COUNCIL -- INSTALLATION OF HVAC FLEXIBLE DUCT: MANUFACTURER'S INSTRUCTIONS. SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL RE SUPPORT AT 5' MAX INTERVALS WITH 1-1/2" MIN WIDTH HANGERS. CLAMPS & TAPING MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS.
Misc
Corrective Action Required
07/03/2013
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]. NOTE THAT WIRE IS NOT A LISTED PRODUCT FOR THIS PURPOSE.
Misc
Corrective Action Required
07/03/2013
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; NOT TO BE LAID LOOSE ON CEILING GRID; DROP TO TERMINATIONS WHERE LOCATED. SUPPORT FROM STRUCTURE -- NOT FROM OTHER M/E/P SYSTEMS.
Misc
Corrective Action Required
07/03/2013
SEISMIC TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Above Ceiling Inspection Passed 7/29/2013 7/29/2013 at 12:00 AM 07/29/2013
Misc
Resolved
07/29/2013
REMOVE ALL ABANDONED MATERIAL: - ABANDONED?? HVAC DUCT - TOP OF DEMOLISHED PARTITIONS, OR TO HEIGHT CERTIFIED BY A/E AS NOT REPRESENTING SAFETY HAZARD.
Misc
Resolved
07/29/2013
SMACNA / AIR DIFUSSION COUNCIL -- INSTALLATION OF HVAC FLEXIBLE DUCT: MANUFACTURER'S INSTRUCTIONS. SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL RE SUPPORT AT 5' MAX INTERVALS WITH 1-1/2" MIN WIDTH HANGERS. CLAMPS & TAPING MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS.
Misc
Resolved
07/29/2013
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]. NOTE THAT WIRE IS NOT A LISTED PRODUCT FOR THIS PURPOSE.
Misc
Resolved
07/29/2013
PLACEMENT / SUPPORT / SECURING OF LOW VOLTAGE ELECTRICAL CABLE: ROUTE HIGH IN INTERSTITIAL SPACE >= 18" ABOVE CEILING GRID; NOT TO BE LAID LOOSE ON CEILING GRID; DROP TO TERMINATIONS WHERE LOCATED. SUPPORT FROM STRUCTURE -- NOT FROM OTHER M/E/P SYSTEMS.
Misc
Resolved
07/29/2013
SEISMIC TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Occupancy Inspection - Fire Passed 11/19/2013 at 12:00 AM 11/19/2013
Final Inspection - Commercial Passed 11/19/2013 at 12:00 AM 11/19/2013
Documents & Images
Date Uploaded File Type Document Name
03/26/2013 Letter Plan Review Conditions
03/26/2013 Letter Building Permit
04/10/2013 Letter Inspection Summary
06/27/2013 Letter Fire Building Plan Review
07/03/2013 Letter Inspection Summary
07/29/2013 Letter Inspection Summary
11/19/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home