Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
|
05/31/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Provide plans showing the actual scope of work, including what is existing, what has been moved and what was added. Also show where the flow valve, supply line and branch lines are located.
|
|
Misc
Corrective Action Required
Supplemental information received on 5/30/2013. Released for construction 5/31/2013
|
|
|
Sprinkler Plan Review
|
Rejected
|
|
05/22/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Provide plans showing the actual scope of work, including what is existing, what has been moved and what was added. Also show where the flow valve, supply line and branch lines are located.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
04/29/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Second set of alarm plans received, replaces the original plan submittal
|
|
Misc
Corrective Action Required
Call (816) 969-1300 to schedule alarm testing
|
|
|
Fire Plan Review
|
Approved
|
04/01/2013
|
04/23/2013
|
|
Brian Austerman
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
04/15/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Call (816) 969-1300 to schedule alarm testing
|
|
|
Licensed Contractors
|
Approved
|
09/16/2013
|
04/09/2013
|
|
Mike Weisenborn
|
|
Business License
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required - Provide the name of the licensed general contractor. A minimum of a Class B license is required. This information is required for permit approval.
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - Provide the name of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
|
|
|
Building Plan Review
|
Approved with Conditions
|
04/01/2013
|
04/01/2013
|
|
Mike Weisenborn
|
|
Bldg - Glazing - Human impact loads
2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Action required - Required glazing is not indicated on the plans. Glazing in the doors, glazing adjacent to doors, storefront glazing within 18 inches of the floor and the mirrors shall meet this requirement. Make needed corrections.
|
|
Plumb - Required public toilet facilities
Corrective Action Required
2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Action required - This comment is for information purposes and will be verified on inspection.
|
|
Misc
Door hardware Type indicates "keyed lock with closer". The City of Lee's Summit does not allow locks which are keyed from the inside. If it is a deadbolt a quarter turn thumb latch is required.
Action required - Make needed corrections.
|
|
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.)
Action required - The installation of the instantaneous water heater shall not conflict with this requirement. To be verified on inspection.
|
|
|
Fire Plan Review
|
Approved
|
04/01/2013
|
03/26/2013
|
|
Brian Austerman
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans for approval if modifying the existing system
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide alarm plans for approval if modifying the existing system
|
|
Misc
Corrective Action Required
1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Provide exterior emergency lighting if not already existing.
RESOLVED IN RESUBMITTAL
|
|
Misc
Corrective Action Required
The sprinkler control valve in the corridor shall be marked with the correct suite number, verified at inspection
|
|
|
Building Plan Review
|
Rejected
|
03/21/2013
|
03/20/2013
|
|
Mike Weisenborn
|
|
Bldg - Glazing - Human impact loads
Corrective Action Required
2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Action required - Required glazing is not indicated on the plans. Glazing in the doors, glazing adjacent to doors, storefront glazing within 18 inches of the floor and the mirrors shall meet this requirement. Make needed corrections.
|
|
Plumb - Required public toilet facilities
Corrective Action Required
2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Action required - This comment is for information purposes and will be verified on inspection.
|
|
Misc
Corrective Action Required
Door hardware Type indicates "keyed lock with closer". The City of Lee's Summit does not allow locks which are keyed from the inside. If it is a deadbolt a quarter turn thumb latch is required.
Action required - Make needed corrections.
|
|
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.)
Action required - The installation of the instantaneous water heater shall not conflict with this requirement. To be verified on inspection.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/21/2013
|
03/14/2013
|
|
Brian Austerman
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans for approval if modifying the existing system
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide alarm plans for approval if modifying the existing system
|
|
Misc
Corrective Action Required
1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Provide exterior emergency lighting if not already existing
|
|
Misc
Corrective Action Required
The sprinkler contorl valve in the corridor shall be marked with the correct suite number, verified at inspection
|
|
|