Permit Application Status

PRCOM20130108


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130108
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR NEW HAIR SALON
01/28/2013
02/27/2013
10/15/2014
04/30/2013
Locations
Contacts
SRKO LLC, Address:24 NW CHIPMAN RD, Phone:(816) 365-0100  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
WINDSOR ELECTRIC INC, Address:PO BOX 821, Phone:(913) 709-8893  
R & R PLUMBING INC, Address:2001 GASLIGHT DR, Phone:(816) 772-5431  
CRAIG A LUEBBERT, ARCHITECT, LLC, Address:396 SW WINTERGARDEN DR, Phone:(816) 536-3472  
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/26/2013
Brian Austerman
Installation acceptance testing
Corrective Action Required
03/26/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call 969-1300 to schedule flow test in conjunction with alarm test
Misc
Corrective Action Required
03/26/2013

Sprinkler control valve in corridor needs to be marked with the appropriate suite designation. Verified at inspection
Alarm Plan Review Released for Construction 03/20/2013
Brian Austerman
Misc
Corrective Action Required
03/20/2013

Verify suite designation, city permit records show this as unit J, but the plan shown unit N. Program accordingly, verified at testing
Licensed Contractors Approved 03/29/2013 02/25/2013
Mike Weisenborn
Business License
Corrective Action Required
02/06/2013

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A minimum of a Class B license is required. This information is required for permit approval.
License contractors
Corrective Action Required
02/06/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Building Plan Review Approved with Conditions 02/20/2013 02/14/2013
Mike Weisenborn
Bldg - Occupant load calculations - Areas without fixed seats
Resolved
02/14/2013

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - The standard way the Codes Administration Department calculates the occupant load for a salon is 2 people for each cutting/styling station, 2 people for each manicure/pedicure station, 2 people for the makeup station and one person for each chair in the waiting area. Using this methode we get an occupant load of 20 people for the space. Make needed corrections to the code analysis. Mike Weisenborn 02/14/2013 10:06 AM - Corrections have been made.
Plumb - Separate facilities
Resolved
02/14/2013

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - As the calculated occupant load is greater than 15, separate restroom facilities are required. Make needed corrections. Mike Weisenborn 02/14/2013 10:06 AM - Not required as the occupant load is 15.
Misc
Resolved
02/14/2013

2006 IMC - Table 403.3, footnote i - The required exhaust system shall capture the contaminat and odor at their source. Action required - This footnote is attached to the nail salon occupancy classification. It is our determination that exhaust openings in the ceiling do not meet the requirement. The exhaust openings shall be placed in the work area. Make needed corrections. Mike Weisenborn 02/14/2013 10:08 AM - Alterations have been made.
Misc
Resolved
02/14/2013

2006 IMC - 403.2.1.3 - Where mechanical exhaust is required by Note b in Table 403.3, recirculation of air from such spaces shall be prohibited. All air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3. Action required - It is the determination of the Codes Administration Department that any area having manicure or pedicure stations shall meet this requirement. Make needed corrections to the mechanical system.
Bldg - Toilet rooms - Walls
Resolved
02/14/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - The finish materials indicate that WC-1 is to extend 46 inches above the finished floor. Make needed corrections.
Bldg - Doors - Size of doors
Resolved
02/14/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The size of the doors is not provided on the door schedule. Provide additional information.
Misc
Resolved
02/14/2013

The plans don't provide information on the construction of the wall between the styling stations. Action required - Provide additional information.
Misc
Corrective Action Required
02/13/2013

I am unable to locate backflow protection for the water supplies on the pedicure and shampoo stations. Action required - To be verified on inspection.
Fire Plan Review Approved 02/20/2013 02/13/2013
Brian Austerman
Misc
Corrective Action Required
02/13/2013

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: Duct detection is shown, activation of which shall initiate a rtu shutdown and transmit a supervisory alarm to the panel. Verified at alarm testing
Construction documents - Fire protection systems
Corrective Action Required
02/13/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide sprinkler plans for approval for any modifications to the existing system
Misc
Corrective Action Required
02/13/2013

The waterflow valve needs to be labeled N109, verified at final inspection
Construction documents for fire alarm systems
Corrective Action Required
02/13/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide alarm plans for approval for any alarm system modifications
Portable fire extinguishers - general
Corrective Action Required
02/13/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: A 10 lb extinguisher is shown on plans, one 5lb (2A10B:C) is required for every 3000 sq/ft. Verified at inspection
Building Plan Review Rejected 02/07/2013 02/07/2013
Mike Weisenborn
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
02/07/2013

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - The standard way the Codes Administration Department calculates the occupant load for a salon is 2 people for each cutting/styling station, 2 people for each manicure/pedicure station, 2 people for the makeup station and one person for each chair in the waiting area. Using this methode we get an occupant load of 20 people for the space. Make needed corrections to the code analysis.
Plumb - Separate facilities
Corrective Action Required
02/07/2013

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - As the calculated occupant load is greater than 15, separate restroom facilities are required. Make needed corrections.
Misc
Corrective Action Required
02/07/2013

2006 IMC - Table 403.3, footnote i - The required exhaust system shall capture the contaminat and odor at their source. Action required - This footnote is attached to the nail salon occupancy classification. It is our determination that exhaust openings in the ceiling do not meet the requirement. The exhaust openings shall be placed in the work area. Make needed corrections.
Misc
Corrective Action Required
02/07/2013

2006 IMC - 403.2.1.3 - Where mechanical exhaust is required by Note b in Table 403.3, recirculation of air from such spaces shall be prohibited. All air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3. Action required - It is the determination of the Codes Administration Department that any area having manicure or pedicure stations shall meet this requirement. Make needed corrections to the mechanical system.
Bldg - Toilet rooms - Walls
Corrective Action Required
02/07/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - The finish materials indicate that WC-1 is to extend 46 inches above the finished floor. Make needed corrections.
Bldg - Doors - Size of doors
Corrective Action Required
02/07/2013

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The size of the doors is not provided on the door schedule. Provide additional information.
Misc
Corrective Action Required
02/07/2013

The plans don't provide information on the construction of the wall between the styling stations. Action required - Provide additional information.
Misc
Corrective Action Required
02/07/2013

I am unable to locate backflow protection for the water supplies on the pedicure and shampoo stations. Action required - Provide additional information.
Fire Plan Review Approved with Conditions 02/07/2013 01/29/2013
Brian Austerman
Misc
Corrective Action Required
01/29/2013

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: Duct detection is shown, activation of which shall initiate a rtu shutdown and transmit a supervisory alarm to the panel. Verified at alarm testing
Construction documents - Fire protection systems
Corrective Action Required
01/29/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide sprinkler plans for approval for any modifications to the existing system
Misc
Corrective Action Required
01/29/2013

The waterflow valve needs to be labeled N109, verified at final inspection
Construction documents for fire alarm systems
Corrective Action Required
01/29/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide alarm plans for approval for any alarm system modifications
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $329.70 $329.70 Paid 02/27/2013
8331507-Sewer Connection Fee $300.00 $300.00 Paid 02/27/2013
$300.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 3/7/2013 3/7/2013 at 12:00 AM 03/07/2013
Underslab Plumbing Inspection - Commercial Passed 3/7/2013 3/7/2013 at 12:00 AM 03/07/2013
In-wall Inspection Passed 3/15/2013 3/19/2013 at 12:00 AM 03/19/2013
Misc
Resolved
03/19/2013
IPC 308.5 MAXIMUM SPACING OF SUPPORTS FOR VERTICAL PLUMBING PIPING: 10' MAX FOR PVC & COPPER; + MID-STORY GUIDE FOR PVC PIPE <= 2";
Misc
Resolved
03/19/2013
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS. CHECK ALL.
Electrical Service Inspection Failed 3/19/2013 at 12:00 AM 03/19/2013
Misc
Corrective Action Required
03/19/2013
GROUND JUMPER FROM LOAD SIDE DISONNECT TO TROUGH ABOVE: CONDUIT CONNECTION TO DISCONNECT ENCLOSURE NOT TIGHTENED.
Misc
Corrective Action Required
03/19/2013
MARK SUITE ADDRESS ON SERVICE METER ENCLOSURE -- EITHER TEMPORARY (MARKER OK FOR TEMPORARY) OR PERMANENT (STICKER OR PLACARD) BEFORE SERVICE IS RELEASED. ADDRESS ON CARDBOARD BLANK-OFF WILL NOT REMAIN AFTER METER IS SET.
Electrical Service Inspection Passed 3/20/2013 3/20/2013 at 12:00 AM 03/20/2013
Misc
Resolved
03/20/2013
GROUND JUMPER FROM LOAD SIDE DISONNECT TO TROUGH ABOVE: CONDUIT CONNECTION TO DISCONNECT ENCLOSURE NOT TIGHTENED.
Misc
Resolved
03/20/2013
MARK SUITE ADDRESS ON SERVICE METER ENCLOSURE -- EITHER TEMPORARY (MARKER OK FOR TEMPORARY) OR PERMANENT (STICKER OR PLACARD) BEFORE SERVICE IS RELEASED. ADDRESS ON CARDBOARD BLANK-OFF WILL NOT REMAIN AFTER METER IS SET.
Gas Piping Inspection - Commercial Partial 4/1/2013 at 12:00 AM 04/01/2013
Misc
Corrective Action Required
04/01/2013
IFGC 404.8: EXPOSED METALLIC PIPING MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Misc
Corrective Action Required
04/01/2013
SOME ROOFTOP GAS PIPING SUPPORT POINTS YET TO BE STRAPPED.
Gas Service Inspection - Commercial Passed 4/1/2013 4/1/2013 at 12:00 AM 04/01/2013
Above Ceiling Inspection Partial 4/10/2013 4/10/2013 at 12:00 AM 04/10/2013
Misc
Partial Correction
04/10/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT @ SPACE 104 IPC - PROTECTION OF COPPER PIPING ADJACENT TO STEEL FRAMING MEMBERS: ISOLATE COPPER FROM DISSIMILAR METAL WITH NON-CONDUCTIVE MATERIAL -- SEE ABOVE SPACE 104
Sprinkler - Flow Test Passed 4/25/2013 at 9:00 AM 04/25/2013
Alarm Test Passed 4/25/2013 at 9:00 AM 04/25/2013
Occupancy Inspection - Fire Passed 4/25/2013 at 12:00 AM 04/25/2013
Gas Piping Inspection - Commercial Passed 4/25/2013 at 12:00 AM 04/25/2013
Misc
Resolved
04/25/2013
IFGC 404.8: EXPOSED METALLIC PIPING MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Misc
Resolved
04/25/2013
SOME ROOFTOP GAS PIPING SUPPORT POINTS YET TO BE STRAPPED.
Above Ceiling Inspection Passed 4/25/2013 at 12:00 AM 04/25/2013
Misc
Resolved
04/25/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT @ SPACE 104 IPC - PROTECTION OF COPPER PIPING ADJACENT TO STEEL FRAMING MEMBERS: ISOLATE COPPER FROM DISSIMILAR METAL WITH NON-CONDUCTIVE MATERIAL -- SEE ABOVE SPACE 104
Occupancy Inspection - Codes Commercial Failed 4/25/2013 4/25/2013 at 12:00 AM 04/25/2013
Misc
Corrective Action Required
04/25/2013
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Corrective Action Required
04/25/2013
FINISH ELECTRICAL AT FRONT COUNTER SUBJECT TO APPROVAL WHEN COMPLETED
Misc
Corrective Action Required
04/25/2013
IBC 1210.1: SURFACE OF RESTROOM FLOOR MUST BE NON-ABSORBENT, SMOOTH. PROVIDE MANUFACTURER'S LITERATURE FOR VERIFICATION.
Misc
Corrective Action Required
04/25/2013
NEC 210-8; E3802.2: GFCI PROTECTION OF ELECTRICAL RECEPTACLES: DUPLEX ELECTRICAL RECEPTACLE AT CLOTHES WASHER NOT GFCI PROTECTED. IF NOT PROTECTED AND DESIGNATED AS "DEDICATED" FOR WASHER RECEPTACLE MUST BE SINGLE PLUG.
Misc
Corrective Action Required
04/25/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE CORRECTLY NUMBERED. ALSO CHECK CORRESPONDENCE WITH PANEL SCHEDULE.
Misc
Corrective Action Required
04/25/2013
IDENTIFICATION OF ELECTRICAL SERVICE PANELS: AFFIX PERMANENT LABELS @ FACE OF PANEL FRONT PER DRAWINGS OR OCCUPANT PREFERENCE.
Misc
Corrective Action Required
04/25/2013
ROOFTOP INSPECTION: 1) NO SUITE # FOUND AT RTU 2) RTU ELECT RECEPT COVER NOT IN-USE TYPE 3) GAS PIPING SUPPORT BLOCKS a) ADD 1 AT ONE N-S BRANCH b) STACKED BLOCKS NOT ATTACHED 4) WIP ON PLUMBING VENT 6) CLEAR ALL DEBRIS OFF ROOF SURFACE AT SUITE FOOTPRINT
Misc
Corrective Action Required
04/25/2013
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Occupancy Inspection - Codes Commercial Full C of O 4/30/2013 4/30/2013 at 12:00 AM 04/30/2013
Misc
Resolved
04/30/2013
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Resolved
04/30/2013
FINISH ELECTRICAL AT FRONT COUNTER SUBJECT TO APPROVAL WHEN COMPLETED
Misc
Resolved
04/30/2013
IBC 1210.1: SURFACE OF RESTROOM FLOOR MUST BE NON-ABSORBENT, SMOOTH. PROVIDE MANUFACTURER'S LITERATURE FOR VERIFICATION.
Misc
Resolved
04/30/2013
NEC 210-8; E3802.2: GFCI PROTECTION OF ELECTRICAL RECEPTACLES: DUPLEX ELECTRICAL RECEPTACLE AT CLOTHES WASHER NOT GFCI PROTECTED. IF NOT PROTECTED AND DESIGNATED AS "DEDICATED" FOR WASHER RECEPTACLE MUST BE SINGLE PLUG.
Misc
Resolved
04/30/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE CORRECTLY NUMBERED. ALSO CHECK CORRESPONDENCE WITH PANEL SCHEDULE.
Misc
Resolved
04/30/2013
IDENTIFICATION OF ELECTRICAL SERVICE PANELS: AFFIX PERMANENT LABELS @ FACE OF PANEL FRONT PER DRAWINGS OR OCCUPANT PREFERENCE.
Misc
Resolved
04/30/2013
ROOFTOP INSPECTION: 1) NO SUITE # FOUND AT RTU 2) RTU ELECT RECEPT COVER NOT IN-USE TYPE 3) GAS PIPING SUPPORT BLOCKS a) ADD 1 AT ONE N-S BRANCH b) STACKED BLOCKS NOT ATTACHED 4) WIP ON PLUMBING VENT 6) CLEAR ALL DEBRIS OFF ROOF SURFACE AT SUITE FOOTPRINT
Misc
Resolved
04/30/2013
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Documents & Images
Date Uploaded File Type Document Name
02/07/2013 Letter Plan Review Conditions
02/14/2013 Letter Plan Review Conditions
02/27/2013 Letter Building Permit
03/07/2013 Letter Inspection Summary
03/15/2013 Letter Inspection Summary
03/19/2013 Letter Inspection Summary
03/20/2013 Letter Inspection Summary
04/01/2013 Letter Inspection Summary
04/10/2013 Letter Inspection Summary
04/25/2013 Letter Inspection Summary
04/30/2013 Letter Field Certificate of Occupancy
05/01/2013 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire (Alarm) Plan Review Notice
06/26/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home