Permit Application Status

PRCOM20122246


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20122246
Building Permit - Commercial
Certificate of Occupancy
JOHN CALVIN MANOR INC
ALTERATION COMMERCIAL
INTERIOR REMODEL
10/10/2012
12/09/2013
04/22/2013
12/18/2014
Locations
Contacts
4SIGHT GROUP LLC, Address:7920 WARD PKWY, Phone:(816) 802-8400  
JOHN CALVIN MANOR INC, Address:310 NW MURRAY  
4SIGHT GROUP LLC, Address:7920 WARD PKWY, Phone:(816) 802-8400  
PROSPERITY ELECTRIC LLC, Address:1601 E 18TH ST #205, Phone:(816) 318-6050  
LMG CONSTRUCTION, Address:3011 ROANOKE RD, Phone:(816) 474-0333  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 10/22/2012 12/09/2013
Mike Weisenborn
Business License
Resolved
10/25/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A minimum of a Class B license will be required.
License contractors
Resolved
12/09/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - I don't see where Allan's Electric or KC Plumbing have a current business license with the City of Lee's Summit. Current licenses will be required prior to permit issuance.
Misc
Resolved
12/09/2013

I have spoken with the building inspector for this project and he has requested that we issue separate permits for each building in the project. This will aid in inspection requests and project tracking. Action required - Please provide a separate project value for each building.
Licensed Contractors Approved 12/31/2013 12/09/2013
Mike Weisenborn
Internal Plan Review (Res) Rejected 10/22/2012 10/24/2012
Mike Weisenborn
True
Fire Plan Review Approved with Conditions 10/22/2012 10/24/2012
Jim Eden
Address numbers required
Corrective Action Required
10/24/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Maintain addressing on the buildings and numbering of the apartments on the interior doors and exterior doors of apartments on grade. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
10/24/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans and specifications for ugrades and alaterations to the alarm system.
Misc
Corrective Action Required
10/24/2012

1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $554.72 $554.72 Paid 12/09/2013
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Passed 3/17/2014 at 12:00 AM 03/17/2014
All Rough Inspection - Commercial Partial 10/7/2014 10/7/2014 at 12:00 AM 10/07/2014
Misc
Partial Correction
10/07/2014
ALL-TRADES ROUGH-IN -- FRAMING + IN-WALL AND ABOVE-CEILING IN-WALL SYSTEMS APPROVED. OK TO COVER CEILINGS AND WALLS FOLLOWING SPACES: UNIT 521; 522; 523; 525; 527; 528; 529;
All Rough Inspection - Commercial Partial 10/17/2014 at 12:00 AM 10/17/2014
Misc
Partial Correction
10/07/2014
ALL-TRADES ROUGH-IN -- FRAMING + IN-WALL AND ABOVE-CEILING IN-WALL SYSTEMS APPROVED. OK TO COVER CEILINGS AND WALLS FOLLOWING SPACES: UNIT 521; 522; 523; 525; 527; 528; 529;[520; 524; 526;
All Rough Inspection - Commercial Partial 10/21/2014 10/22/2014 at 12:00 AM 10/22/2014
Misc
Partial Correction
10/17/2014
ALL-TRADES ROUGH-IN -- FRAMING + IN-WALL AND ABOVE-CEILING IN-WALL SYSTEMS APPROVED. OK TO COVER CEILINGS AND WALLS FOLLOWING SPACES: UNIT 520; 521; 522; 523; 524; 525; 526; 527; 528; 529; [500-509;
All Rough Inspection - Commercial Partial 10/30/2014 10/30/2014 at 12:00 AM 10/30/2014
Misc
Partial Correction
10/22/2014
ALL-TRADES ROUGH-IN -- FRAMING + IN-WALL AND ABOVE-CEILING IN-WALL SYSTEMS APPROVED. OK TO COVER CEILINGS AND WALLS FOLLOWING SPACES: UNIT 520; 521; 522; 523; 524; 525; 526; 527; 528; 529; [500-509; 530-539
All Rough Inspection - Commercial Partial 10/31/2014 10/31/2014 at 12:00 AM 10/31/2014
Misc
Partial Correction
10/30/2014
ALL-TRADES ROUGH-IN -- FRAMING + IN-WALL AND ABOVE-CEILING IN-WALL SYSTEMS APPROVED. OK TO COVER CEILINGS AND WALLS FOLLOWING SPACES: UNIT 500-509; 520; 521; 522; 523; 524; 525; 526; 527; 528; 529; 530-539; 510-519
Occupancy Inspection - Codes Commercial Temporary C of O 11/7/2014 11/7/2014 at 12:00 AM 11/07/2014
Misc
Partial Correction
11/07/2014
OK TO OCCUPY UNITS 520-529 AFTER ALL BALCONY GUARDS ARE COMPLETED INCLUDING TOP RAILS. SYSTEMS AT ATTIC YET TO BE INSPECTED.
Occupancy Inspection - Codes Commercial Partial 11/10/2014 at 12:00 AM 11/10/2014
Misc
Partial Correction
11/07/2014
OK TO OCCUPY UNITS 520-529 SYSTEMS AT ATTIC BASEMENT YET TO BE INSPECTED.
Alarm Test Passed 11/7/2014 at 12:00 AM 11/11/2014
Occupancy Inspection - Fire Temporary C of O 11/7/2014 at 12:00 AM 11/11/2014
Alarm Test Passed 11/17/2014 at 2:00 PM 11/17/2014
Misc
Corrective Action Required
11/17/2014
- post the numeric address of building "308" on all four sides of the building - remove all dust covers from the corridor smoke detectors - terminatethe old wiring form the old corridor smoke detectors - mount the fire extinguisher in the corridor accessable from a 75' travel distance
Occupancy Inspection - Fire Temporary C of O 11/17/2014 11/17/2014 at 12:00 AM 11/17/2014
Occupancy Inspection - Codes Commercial Temporary C of O 11/17/2014 11/17/2014 at 12:00 AM 11/17/2014
Misc
Partial Correction
11/17/2014
OK TO OCCUPY UNITS 520-529; [500-509; SYSTEMS AT ATTIC AND BASEMENT YET TO BE INSPECTED.
Alarm Test Passed 11/21/2014 at 12:00 AM 11/21/2014
Occupancy Inspection - Fire Not Ready 11/21/2014 11/21/2014 at 12:00 AM 11/21/2014
Misc
Corrective Action Required
11/21/2014
2nd floor west wing- keep all constuction debris, materials, related items off staiwys allowing for exiting from all corridors -remove dust covers from smoke detectors in the corridor remove all constrution related items from the corridors and exit ways -post the numeric address of 308 on all four sides of the building - west stairway egress lighting needs to illuminate on D/C power - don't corridor fire doors.
Occupancy Inspection - Codes Commercial Partial 11/21/2014 11/21/2014 at 12:00 AM 11/21/2014
Misc
Partial Correction
11/17/2014
OK TO OCCUPY UNITS 520-529; 500-509; UNITS 530-539 TO BE REINSPECTED BY FIRE DEPT AT 09:00 11/24. NO CODES ISSUES REMIANING AT CORRIDOR OR UNITS SYSTEMS AT ATTIC AND BASEMENT YET TO BE INSPECTED BY JB 12/1.
Occupancy Inspection - Fire Temporary C of O 11/24/2014 at 12:00 AM 11/24/2014
Occupancy Inspection - Codes Commercial Temporary C of O 11/26/2014 11/26/2014 at 12:00 AM 11/26/2014
Misc
Corrective Action Required
11/26/2014
-DECKS CONSTRUCTED WILL REQUIRE LAGS AT BEAM TO POST CONNECTIONS, AND JOIST HANGERS
Alarm Test Passed 11/24/2014 at 12:00 AM 11/26/2014
Alarm Test Passed 11/26/2014 at 12:00 AM 11/26/2014
Occupancy Inspection - Fire Temporary C of O 11/26/2014 at 12:00 AM 11/26/2014
Misc
Corrective Action Required
11/21/2014
2nd floor west wing- keep all constuction debris, materials, related items off staiwys allowing for exiting from all corridors -remove dust covers from smoke detectors in the corridor remove all constrution related items from the corridors and exit ways -post the numeric address of 308 on all four sides of the building - west stairway egress lighting needs to illuminate on D/C power - don't corridor fire doors.
Misc
Corrective Action Required
11/26/2014
Occupancy Inspection - Codes Commercial Partial 12/4/2014 at 12:00 AM 12/04/2014
Misc
Corrective Action Required
11/26/2014
PER DRAWINGS, DECKS REQUIRE JOIST HANGERS.
Misc
Corrective Action Required
12/04/2014
RESTORE DRAFT STOP WALL AT WEST SECTION. AT EAST SECTION REMOVE ANY BLOWN-IN INSULATION IN A/C UNIT AND CLOSE CABINET. PROVIDE PHOTOS.
All Rough Inspection - Commercial Passed 10/31/2014 at 12:00 AM 12/04/2014
Misc
Resolved
12/04/2014
ALL-TRADES ROUGH-IN -- FRAMING + IN-WALL AND ABOVE-CEILING IN-WALL SYSTEMS APPROVED. OK TO COVER CEILINGS AND WALLS FOLLOWING SPACES: UNIT 500-509; 520; 521; 522; 523; 524; 525; 526; 527; 528; 529; 530-539; 510-519
Alarm Test Passed 12/9/2014 at 12:00 AM 12/09/2014
Alarm Test Passed 12/18/2014 at 12:00 AM 12/18/2014
Occupancy Inspection - Codes Commercial Full C of O 12/19/2014 12/18/2014 at 12:00 AM 12/18/2014
Misc
Resolved
12/18/2014
PER DRAWINGS, DECKS REQUIRE JOIST HANGERS.
Misc
Resolved
12/18/2014
RESTORE DRAFT STOP WALL AT WEST SECTION. AT EAST SECTION REMOVE ANY BLOWN-IN INSULATION IN A/C UNIT AND CLOSE CABINET. PROVIDE PHOTOS.
Occupancy Inspection - Fire Passed 1/5/2015 at 12:00 AM 12/19/2014
Documents & Images
Date Uploaded File Type Document Name
10/24/2012 Letter Plan Review Conditions
05/02/2013 Letter EXTENSION
06/21/2013 Letter Fire Building Plan Review
12/09/2013 Letter Codes Plan Review Conditions
12/09/2013 Letter Codes Building Permit
10/07/2014 Letter Inspection Summary
10/17/2014 Letter Inspection Summary
10/22/2014 Letter Inspection Summary
10/30/2014 Letter Inspection Summary
10/31/2014 Letter Inspection Summary
11/07/2014 Letter Codes Temporary Certificate of Occupancy
11/17/2014 Letter Codes Temporary Certificate of Occupancy
11/21/2014 Letter Inspection Summary
11/26/2014 Letter Codes Temporary Certificate of Occupancy
12/04/2014 Letter Inspection Summary
12/18/2014 Letter Field Certificate of Occupancy
12/19/2014 Letter Codes Final Certificate of Occupancy
01/14/2017 Letter Fire Loss Reduction Form
01/14/2017 Letter Fire Loss Reduction Form
01/14/2017 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home