Permit Application Status

PRCOM20122034


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20122034
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR CLOTHING STORE
09/10/2012
01/28/2013
10/04/2014
04/11/2013
Locations
Contacts
HITT CONTRACTING INC, Address:2900 FAIRVIEW PARK DR, Phone:(703) 846-9000  
MD REPAIR, Address:7901 S PARRENT RD, Phone:(816) 690-7985  
WESTHUES ELECTRIC INC, Address:PO BOX 18220, Phone:(816) 356-5223  
TRITON PLUMBING, Address:P O BOX 380038, Phone:(816) 522-6865  
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
LINEAR!, Address:8600 FREEPORT PKWY, SUITE 310, Phone:(972) 929-9226  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/11/2013
Brian Austerman
Misc
Corrective Action Required
03/11/2013

Control Valve in corridor shall be marked with proper suite number. Verified at inspection. Call 969-1300 to schedule flow and alarm testing
Alarm Plan Review Released for Construction 02/08/2013
Brian Austerman
Installation acceptance testing
Corrective Action Required
09/10/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Misc
Corrective Action Required
09/10/2012

Duct detectors shall be supervisory alarms only. Verified at inspection.
Building Plan Review Approved with Conditions 09/20/2012 01/24/2013
Mike Weisenborn
License contractors
Corrective Action Required
09/18/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing subcontractors.
Business License
Corrective Action Required
09/18/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A minimum of a Class B license is required.
Plumb - Required public toilet facilities
Corrective Action Required
09/18/2012

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Misc
Corrective Action Required
09/18/2012

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes.
License Tax Codes Approved 02/28/2013 01/24/2013
Mike Weisenborn
Internal Plan Review (Res) Rejected 09/20/2012 09/19/2012
Mike Weisenborn
Fire Plan Review Approved with Conditions 09/20/2012 09/11/2012
Brian Austerman
Misc
Corrective Action Required
09/11/2012

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. Action Required: Provide exterior egress lighting
Misc
Corrective Action Required
09/11/2012

1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1. On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf. For information only. Egress doors shall have panic hardware or 1/4 turn thumb latch
Construction documents - Fire protection systems
Corrective Action Required
09/11/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide construction documents for the sprinkler system modifications, can be a deferred submittal
Construction documents for fire alarm systems
Corrective Action Required
09/11/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide construction documents for the fire alarm system modifications, can be a deferred submittal
Misc
Corrective Action Required
09/11/2012

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. For information only, activation of a duct detector shall shut down the unit and transmit a supervisory signal at the alarm panel
Zoning Review Approved 09/20/2012 09/10/2012
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,120.98 $1,120.98 Paid 01/28/2013
8331507-Sewer Connection Fee $180.00 $180.00 Paid 01/28/2013
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 2/11/2013 2/11/2013 at 12:00 AM 02/11/2013
Misc
Partial Correction
02/11/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES;
In-wall Inspection Partial 2/14/2013 2/14/2013 at 12:00 AM 02/14/2013
Misc
Partial Correction
02/11/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES; N-S WALL AT REAR PASSAGEWAY WHERE ELECTRICAL PANELS ARE TO BE MOUNTED;
Underslab Plumbing Inspection - Commercial Passed 2/15/2013 2/15/2013 at 12:00 AM 02/15/2013
Underslab Electrical Inspection - Commercial Passed 2/20/2013 2/19/2013 at 12:00 AM 02/19/2013
In-wall Inspection Partial 2/20/2013 2/19/2013 at 12:00 AM 02/19/2013
Misc
Partial Correction
02/14/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES; N-S WALL AT REAR PASSAGEWAY WHERE ELECTRICAL PANELS ARE TO BE MOUNTED; SALES AREA AND ALL REMAINING EXCEPT REAR (EAST) SPACES;
Rated Assembly Inspection Passed 2/25/2013 2/25/2013 at 12:00 AM 02/25/2013
In-wall Inspection Partial 2/25/2013 2/25/2013 at 12:00 AM 02/25/2013
Misc
Partial Correction
02/19/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES; N-S WALL AT REAR PASSAGEWAY WHERE ELECTRICAL PANELS ARE TO BE MOUNTED; SALES AREA AND ALL REMAINING EXCEPT REAR (EAST) SPACES; FITTING ROOM AREA;
Electrical Service Inspection Passed 3/1/2013 3/1/2013 at 12:00 AM 03/01/2013
Above Ceiling Inspection Partial 3/4/2013 3/4/2013 at 12:00 AM 03/04/2013
Misc
Partial Correction
03/04/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: OFFICE; 4'x55' CEILING AT FRONT(WEST) OF STORE;
In-wall Inspection Partial 3/5/2013 3/5/2013 at 12:00 AM 03/05/2013
Misc
Partial Correction
02/25/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES; N-S WALL AT REAR PASSAGEWAY WHERE ELECTRICAL PANELS ARE TO BE MOUNTED; SALES AREA AND ALL REMAINING EXCEPT REAR (EAST) SPACES; FITTING ROOM AREA;
Misc
Corrective Action Required
03/05/2013
RESTROOM WALLS: IPC - PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL
Above Ceiling Inspection Partial 3/5/2013 3/5/2013 at 12:00 AM 03/05/2013
Misc
Partial Correction
03/04/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: OFFICE; 4'x55' CEILING AT FRONT(WEST) OF STORE;
Misc
Corrective Action Required
03/05/2013
DWV PIPING ABOVE RESTROOMS NOT COMPLETED.
Above Ceiling Inspection Partial 03/05/2013
Misc
Partial Correction
03/05/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: OFFICE; 4'x55' CEILING AT FRONT(WEST) OF STORE;
Misc
Corrective Action Required
03/05/2013
DWV PIPING ABOVE RESTROOMS NOT COMPLETED.
In-wall Inspection Passed 3/6/2013 3/6/2013 at 12:00 AM 03/06/2013
Misc
Resolved
03/06/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES; N-S WALL AT REAR PASSAGEWAY WHERE ELECTRICAL PANELS ARE TO BE MOUNTED; SALES AREA AND ALL REMAINING EXCEPT REAR (EAST) SPACES; FITTING ROOM AREA; RESTROOMS
Misc
Resolved
03/06/2013
RESTROOM WALLS: IPC - PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL
Above Ceiling Inspection Passed 3/7/2013 3/7/2013 at 12:00 AM 03/07/2013
Misc
Resolved
03/07/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: OFFICE; 4'x55' CEILING AT FRONT(WEST) OF STORE;
Misc
Resolved
03/07/2013
DWV PIPING ABOVE RESTROOMS NOT COMPLETED.
Gas Piping Inspection - Commercial Partial 3/8/2013 at 12:00 AM 03/08/2013
Misc
Corrective Action Required
03/08/2013
IFGC 404.8: EXPOSED METALLIC PIPING MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Gas Service Inspection - Commercial Passed 3/8/2013 3/8/2013 at 12:00 AM 03/08/2013
Alarm Test Passed 3/28/2013 at 9:00 AM 03/28/2013
Sprinkler - Flow Test Passed 3/28/2013 at 12:00 AM 03/28/2013
Gas Piping Inspection - Commercial Passed 4/1/2013 at 12:00 AM 04/01/2013
Misc
Resolved
04/01/2013
IFGC 404.8: EXPOSED METALLIC PIPING MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Occupancy Inspection - Codes Commercial Not Ready 4/1/2013 4/1/2013 at 12:00 AM 04/01/2013
Misc
Corrective Action Required
04/01/2013
COURTESY PRE-FINAL WALK-THROUGH OBSERVATIONS: - RESTROOM MIRRORS 1/2" HIGH - MEN'S RR W.C. 3-1/2" TOO FAR FROM WALL - ELECT RECEPT COVER PLATES TO BE PLACED - ONE ELECT RECEPT MIS-WIRED - STICK ELECT C.B. LABELS TO PANEL FRONTS - PLACE ELECT PANEL SCHEDULES - EXTERIOR LIGHTED SIGN SUBJECT TO APPROVAL - AFFIX "NO SMOKING" STICKER AT PUBLIC ENT DOOR FINAL INSPECTION WILL INCLUDE, BUT WILL NOT BE LIMITED TO, THE ABOVE ISSUES.
In-wall Inspection Passed 4/1/2013 at 12:00 AM 04/01/2013
Misc
Resolved
04/01/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: PERIMETER WALLS AFTER SPRINKLER F.P. PIPE @ EAST WALL IS PROPERLY SECURED; SHOE STORAGE BOTH FACES; WING WALL PER ELEVATION 5/A-4.1 BOTH FACES; N-S WALL AT REAR PASSAGEWAY WHERE ELECTRICAL PANELS ARE TO BE MOUNTED; SALES AREA AND ALL REMAINING EXCEPT REAR (EAST) SPACES; FITTING ROOM AREA; RESTROOMS
Occupancy Inspection - Fire Passed 4/11/2013 at 12:00 AM 04/11/2013
Misc
Corrective Action Required
04/11/2013
OK to occupy once cleared through codes administration
Occupancy Inspection - Codes Commercial Full C of O 4/11/2013 4/11/2013 at 12:00 AM 04/11/2013
Misc
Resolved
04/11/2013
COURTESY PRE-FINAL WALK-THROUGH OBSERVATIONS: - RESTROOM MIRRORS 1/2" HIGH - MEN'S RR W.C. 3-1/2" TOO FAR FROM WALL - ELECT RECEPT COVER PLATES TO BE PLACED - ONE ELECT RECEPT MIS-WIRED - STICK ELECT C.B. LABELS TO PANEL FRONTS - PLACE ELECT PANEL SCHEDULES - EXTERIOR LIGHTED SIGN SUBJECT TO APPROVAL - AFFIX "NO SMOKING" STICKER AT PUBLIC ENT DOOR FINAL INSPECTION WILL INCLUDE, BUT WILL NOT BE LIMITED TO, THE ABOVE ISSUES.
Documents & Images
Date Uploaded File Type Document Name
09/19/2012 Letter Plan Review Conditions
01/24/2013 Letter Plan Review Conditions
01/28/2013 Letter Building Permit
02/11/2013 Letter Inspection Summary
02/14/2013 Letter Inspection Summary
02/15/2013 Letter Inspection Summary
02/19/2013 Letter Inspection Summary
02/25/2013 Letter Inspection Summary
03/01/2013 Letter Inspection Summary
03/04/2013 Letter Inspection Summary
03/05/2013 Letter Inspection Summary
03/06/2013 Letter Inspection Summary
03/07/2013 Letter Inspection Summary
03/08/2013 Letter Inspection Summary
04/01/2013 Letter Inspection Summary
04/11/2013 Letter Fire Loss Reduction Form
04/11/2013 Letter Field Certificate of Occupancy
04/12/2013 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
06/27/2013 Letter Fire (Sprinkler) Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home