Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
|
03/11/2013
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Control Valve in corridor shall be marked with proper suite number. Verified at inspection.
Call 969-1300 to schedule flow and alarm testing
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
02/08/2013
|
|
Brian Austerman
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule testing.
|
|
Misc
Corrective Action Required
Duct detectors shall be supervisory alarms only.
Verified at inspection.
|
|
|
Building Plan Review
|
Approved with Conditions
|
09/20/2012
|
01/24/2013
|
|
Mike Weisenborn
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - Provide the names of the licensed mechanical, electrical and plumbing subcontractors.
|
|
Business License
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required - Provide the name of the licensed general contractor. A minimum of a Class B license is required.
|
|
Plumb - Required public toilet facilities
Corrective Action Required
2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Action required - This comment is for information purposes.
|
|
Misc
Corrective Action Required
The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff.
Action required - This comment is for information purposes.
|
|
|
License Tax Codes
|
Approved
|
02/28/2013
|
01/24/2013
|
|
Mike Weisenborn
|
|
|
Internal Plan Review (Res)
|
Rejected
|
09/20/2012
|
09/19/2012
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved with Conditions
|
09/20/2012
|
09/11/2012
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits.
Action Required: Provide exterior egress lighting
|
|
Misc
Corrective Action Required
1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.
Exceptions:
1. On doors not required for egress in individual dwelling units or sleeping units.
2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf.
For information only. Egress doors shall have panic hardware or 1/4 turn thumb latch
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action Required: Provide construction documents for the sprinkler system modifications, can be a deferred submittal
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action Required: Provide construction documents for the fire alarm system modifications, can be a deferred submittal
|
|
Misc
Corrective Action Required
907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
For information only, activation of a duct detector shall shut down the unit and transmit a supervisory signal at the alarm panel
|
|
|
Zoning Review
|
Approved
|
09/20/2012
|
09/10/2012
|
|
Codes Admin
|
|
|