Permit Application Status

PRCOM20121747


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20121747
Building Permit - Commercial
Final Completion
CP DEER BROOK PLAZA LLC
ALTERATION COMMERCIAL
WHITE BOX FINISH
08/02/2012
08/21/2012
02/06/2013
08/30/2012
Locations
Contacts
CMG CONSTRUCTION , Address:8336 NIEMAN RD, Phone:(913) 384-2284  
CP DEER BROOK PLAZA LLC, Address:3400 COLLEGE BLVD STE 195  
SECO INC, Address:7007 COLLEGE BLVD STE 265, Phone:(913) 428-3550  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/22/2012 08/20/2012
Mike Weisenborn
True
Building Plan Review Approved 08/22/2012 08/20/2012
Mike Weisenborn
License contractors
Resolved
08/20/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Our records show that Quality Plumbing has not renewed their business license for the 2012-2013 fiscal year. Their business license needs to be renewed prior to permit issuance. Mike Weisenborn 08/20/2012 4:06 PM - There will be no plumbing work on this permit.
Misc
Resolved
08/20/2012

The door shown in the corridor to the storage area does not meet accessible egress requirements from the pull side. Action required - Per conversations with the contractor the door is to be removed from the project. Mike Weisenborn 08/20/2012 4:07 PM - The door has been removed.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
08/15/2012

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - This will be verified on inspection.
Bldg - Toilet rooms - Walls
Corrective Action Required
08/15/2012

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This will be verified on inspection.
Misc
Resolved
08/20/2012

The plans show a mop sink being added in the men's restroom that wil interfer with required clear spaces for accessibility. Action required - The mop sink needs to be relocated. Mike Weisenborn 08/20/2012 4:08 PM - The mop sink is existing.
Misc
Resolved
08/20/2012

The plans do not provide any information for the construction and bracing of the new wall separating the main area and the storage area. Action required - Provide additional information.
Misc
Corrective Action Required
08/15/2012

This permit is for the construction of a "white box" space only and does not allow for the occupancy of the space. A separate permit will be required for the future tenant to verify that they meet all occupancy type requirements. Action required - This comment is for information purposes.
Fire Plan Review Approved 08/22/2012 08/15/2012
Codes Admin
Internal Plan Review (Res) Rejected 08/13/2012 08/10/2012
Mike Weisenborn
Building Plan Review Rejected 08/13/2012 08/10/2012
Mike Weisenborn
License contractors
Corrective Action Required
08/10/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Our records show that Quality Plumbing has not renewed their business license for the 2012-2013 fiscal year. Their business license needs to be renewed prior to permit issuance.
Misc
Corrective Action Required
08/10/2012

The door shown in the corridor to the storage area does not meet accessible egress requirements from the pull side. Action required - Per conversations with the contractor the door is to be removed from the project.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
08/10/2012

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - This will be verified on inspection.
Bldg - Toilet rooms - Walls
Corrective Action Required
08/10/2012

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This will be verified on inspection.
Misc
Corrective Action Required
08/10/2012

The plans show a mop sink being added in the men's restroom that wil interfer with required clear spaces for accessibility. Action required - The mop sink needs to be relocated.
Misc
Corrective Action Required
08/10/2012

The plans do not provide any information for the construction and bracing of the new wall separating the main area and the storage area. Action required - Provide additional information.
Misc
Corrective Action Required
08/10/2012

This permit is for the construction of a "white box" space only and does not allow for the occupancy of the space. A separate permit will be required for the future tenant to verify that they meet all occupancy type requirements. Action required - This comment is for information purposes.
Fire Plan Review Approved 08/13/2012 08/07/2012
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
08/07/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide plans for approval for any sprinkler modifications
Construction documents for fire alarm systems
Corrective Action Required
08/07/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide plans for approval for any alarm system modifications
Portable fire extinguishers - general
Corrective Action Required
08/07/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide a minimum size of 2A10B:C extinguishers. Verified at inspection
Address numbers required
Corrective Action Required
08/07/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Address all exterior doors leading into the space, verified at inspection
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/07/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action Required: Sprinkler system must have current ceritfication at time of final
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $36.29 $36.29 Paid 08/21/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 8/22/2012 8/22/2012 at 12:00 AM 08/22/2012
Above Ceiling Inspection Partial 8/22/2012 8/22/2012 at 12:00 AM 08/22/2012
Misc
Partial Correction
08/22/2012
OK TO PLACE ACT BORDERS (2' MAXIMUM) AT MAIN AREA (STORAGE ROOM NOT READY)
Misc
Corrective Action Required
08/22/2012
REMOVE ABANDONED ROD & STRAP HANGERS
Misc
Corrective Action Required
08/22/2012
COMPLETE HVAC SUPPLY & RETURN SYSTEM PER SMACNA. CONNECT FLEX CONNECTORS WITH INNNER LAYER SECURED AND OUTER LAYER SECURED. ELIMINATE EXCESS CONNECTOR LENGHT. SEAL ALL ABANDONED OPENINGS. SET AND CONNECT ALL DIFFUSERS AND GRILLES. ELIMINATE ABANDONED EXHAUST PATH(S) TO ATMOSPHERE.
Misc
Corrective Action Required
08/22/2012
ADJUST FIRE PROTECTION SPRINKLER DROPS TO GRID ELEVATION.
Above Ceiling Inspection Passed 8/27/2012 8/27/2012 at 12:00 AM 08/27/2012
Misc
Resolved
08/27/2012
OK TO PLACE ACT BORDERS (2' MAXIMUM) AT MAIN AREA (STORAGE ROOM NOT READY)
Misc
Resolved
08/27/2012
REMOVE ABANDONED ROD & STRAP HANGERS
Misc
Resolved
08/27/2012
COMPLETE HVAC SUPPLY & RETURN SYSTEM PER SMACNA. CONNECT FLEX CONNECTORS WITH INNNER LAYER SECURED AND OUTER LAYER SECURED. ELIMINATE EXCESS CONNECTOR LENGHT. SEAL ALL ABANDONED OPENINGS. SET AND CONNECT ALL DIFFUSERS AND GRILLES. ELIMINATE ABANDONED EXHAUST PATH(S) TO ATMOSPHERE.
Misc
Resolved
08/27/2012
ADJUST FIRE PROTECTION SPRINKLER DROPS TO GRID ELEVATION.
Final Inspection - Commercial Passed 8/30/2012 8/30/2012 at 12:00 AM 08/30/2012
Occupancy Inspection - Fire Passed 8/30/2012 at 12:00 AM 08/30/2012
Documents & Images
Date Uploaded File Type Document Name
08/10/2012 Letter Plan Review Conditions
08/21/2012 Letter Building Permit
08/21/2012 Letter Plan Review Conditions
08/22/2012 Letter Inspection Summary
08/27/2012 Letter Inspection Summary
08/30/2012 Letter Inspection Summary
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home