Permit Application Status

PRCOM20121257


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20121257
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
TENANT FINISH FOR INTENSIVE CARE UNIT
06/06/2012
08/06/2012
10/15/2014
09/06/2013
Locations
Contacts
TURNER CONSTRUCTION COMPANY, Address:1220 WASHINGTON STE 1000, Phone:(816) 283-0555  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
ACI-BOLAND, INC, Address:11229 Nall, Ste. 140  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 12/12/2012 12/12/2012
Mike Weisenborn
Fire Plan Review Approved 12/12/2012 12/12/2012
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
12/10/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Installation acceptance testing
Corrective Action Required
12/10/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Misc
Corrective Action Required
12/10/2012

Access controlled doors to the floor shall release with the activation of the fire alarm. Verified at inspection.
Misc
Corrective Action Required
12/10/2012

3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Action required: Provide documentation of pipe testing. All piping and valves shall be labeled in accordance with NFPA 99. Verified at inspection.
Misc
Corrective Action Required
12/10/2012

Elevators shall be inspected by the State of Missouri. Adjust sprinkler and fire alarm coverage ass needed and provide as built drawings.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
12/10/2012

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Verified at inspection.
Building Plan Review Approved with Conditions 09/19/2012 12/10/2012
Mike Weisenborn
Fire Plan Review Approved with Conditions 09/20/2012 09/19/2012
Jim Eden
Construction documents - Fire protection systems
Resolved
09/19/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Call (816) 969-1300 to schedule testing. Provide shop drawing for review and approval
Construction documents for fire alarm systems
Corrective Action Required
09/13/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Installation acceptance testing
Corrective Action Required
09/13/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Misc
Corrective Action Required
09/13/2012

Access controlled doors to the floor shall release with the activation of the fire alarm. Verified at inspection.
Misc
Corrective Action Required
09/13/2012

3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Action required: Provide documentation of pipe testing. All piping and valves shall be labeled in accordance with NFPA 99. Verified at inspection.
Misc
Corrective Action Required
09/13/2012

Elevators shall be inspected by the State of Missouri. Adjust sprinkler and fire alarm coverage ass needed and provide as built drawings.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
09/19/2012

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Verified at inspection.
Building Plan Review Approved 08/30/2012 08/30/2012
Mike Weisenborn
Fire Plan Review Approved with Conditions 08/30/2012 08/29/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
08/23/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Call (816) 969-1300 to schedule testing. Provide shop drawing for review and approval
Construction documents for fire alarm systems
Corrective Action Required
08/23/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Installation acceptance testing
Corrective Action Required
08/23/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Misc
Corrective Action Required
08/23/2012

Access controlled doors to the floor shall release with the activation of the fire alarm. Verified at inspection.
Misc
Corrective Action Required
08/23/2012

3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Action required: Provide documentation of pipe testing. All piping and valves shall be labeled in accordance with NFPA 99. Verified at inspection.
Misc
Corrective Action Required
08/29/2012

Elevators shall be inspected by the State of Missouri. Adjust sprinkler and fire alarm coverage ass needed and provide as built drawings.
Internal Plan Review (Res) Approved 07/25/2012 07/24/2012
Mike Weisenborn
True
Building Plan Review Approved 07/25/2012 07/24/2012
Mike Weisenborn
Misc
Resolved
07/24/2012

A third party review of the electrical system shall be provided. Action required - Provide documentation of approval. Mike Weisenborn 07/24/2012 3:46 PM - Documentation and corrections have been provided.
Misc
Resolved
07/24/2012

2006 IBC Section 3004.1 - Vents required. Hoistways of elevators and dumbwaiters penetrating more than three stories shall be provided with a means for venting smoke and hot gases to the outer air in case of fire. Action required - Show how this requirement will be met for the freight elevator.
Fire Plan Review Approved 07/25/2012 07/24/2012
Jim Eden
Misc
Resolved
07/24/2012

905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved by the fire code official. 2. On each side of the wall adjacent to the exit opening of a horizontal exit. Exception: Where floor areas adjacent to a horizontal exit are reachable from exit stairway hose connections by a 30-foot (9144 mm) hose stream from a nozzle attached to 100 feet (30480 mm) of hose, a hose connection shall not be required at the horizontal exit. 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Action required: Provide a fire hose cabinet with a 2 1/2 in hose valve along the new wall by door 4F021. Extend from the existing stairwell system. This condition shall apply to all floors that have had the second access from the existing stairwell to the new building removed.
Construction documents - Fire protection systems
Corrective Action Required
07/18/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
07/18/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Misc
Resolved
07/24/2012

905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 6.Where the most remote portion of a nonsprinklered floor or story is more than 150 feet (45 720 mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet (60 960 mm) from a hose connection, the fire code official is authorized to require that additional hose connections be provided in approved locations. Action required:Provide a hose valve in corridor 4F034 to meet this requirement, preferably on the wall adjacent to the Stair 4F011.
Installation acceptance testing
Corrective Action Required
07/18/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule testing.
Misc
Corrective Action Required
07/18/2012

Access controlled doors to the floor shall release with the activation of the fire alarm. Verified at inspection.
Misc
Corrective Action Required
07/18/2012

3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Action required: Provide documentation of pipe testing. All piping and valves shall be labeled in accordance with NFPA 99. Verified at inspection.
Sprinkler Plan Review Released for Construction 06/18/2012 07/23/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/23/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Revised plans received July 20, 2012.
Installation acceptance testing
Corrective Action Required
07/23/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Misc
Resolved
07/23/2012

Provide a Class 1, 2 1/2 inch hose valve and cabinet in the corridor outside of ICU #10.
Misc
Resolved
07/23/2012

Extend a Class 1, 2 1/2 inch hose valve from the north stair (A410) into the corridor (4F021) from the hospital stair riser.
Sprinkler Plan Review Rejected 07/09/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/09/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received June 19, 2012.
Installation acceptance testing
Corrective Action Required
07/09/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Misc
Corrective Action Required
07/09/2012

Provide a Class 1, 2 1/2 inch hose valve and cabinet in the corridor outside of ICU #10.
Misc
Corrective Action Required
07/09/2012

Extend a Class 1, 2 1/2 inch hose valve from the north stair (A410) into the corridor (4F021) from the hospital stair riser.
Internal Plan Review (Res) Rejected 06/18/2012 06/20/2012
Mike Weisenborn
Fire Plan Review Rejected 06/18/2012 06/19/2012
Jim Eden
Misc
Corrective Action Required
06/19/2012

905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved by the fire code official. 2. On each side of the wall adjacent to the exit opening of a horizontal exit. Exception: Where floor areas adjacent to a horizontal exit are reachable from exit stairway hose connections by a 30-foot (9144 mm) hose stream from a nozzle attached to 100 feet (30480 mm) of hose, a hose connection shall not be required at the horizontal exit. 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Action required: Provide a fire hose cabinet with a 2 1/2 in hose valve along the new wall by door 4F021. Extend from the existing stairwell system. This condition shall apply to all floors that have had the second access from the existing stairwell to the new building removed.
Construction documents - Fire protection systems
Corrective Action Required
06/19/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
06/19/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Misc
Corrective Action Required
06/19/2012

905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 6.Where the most remote portion of a nonsprinklered floor or story is more than 150 feet (45 720 mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet (60 960 mm) from a hose connection, the fire code official is authorized to require that additional hose connections be provided in approved locations. Action required:Provide a hose valve in corridor 4F034 to meet this requirement, preferably on the wall adjacent to the Stair 4F011.
Installation acceptance testing
Corrective Action Required
06/19/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule testing.
Misc
Corrective Action Required
06/19/2012

Access controlled doors to the floor shall release with the activation of the fire alarm. Verified at inspection.
Misc
Corrective Action Required
06/19/2012

3006.4 Medical gas systems. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Action required: Provide documentation of pipe testing. All piping and valves shall be labeled in accordance with NFPA 99. Verified at inspection.
Building Plan Review Rejected 06/18/2012 06/18/2012
Mike Weisenborn
Misc
Corrective Action Required
06/18/2012

A third party review of the electrical system shall be provided. Action required - Provide documentation of approval.
Misc
Corrective Action Required
06/18/2012

2006 IBC Section 3004.1 - Vents required. Hoistways of elevators and dumbwaiters penetrating more than three stories shall be provided with a means for venting smoke and hot gases to the outer air in case of fire. Action required - Show how this requirement will be met for the freight elevator.
Misc
Resolved
06/19/2012

The allowable egress travel for a sprinkled I2 is 200 feet. I measured both egress paths and one is compliant and the other measures 205 feet. I discussed this with Mark Dunning and we believe it meets the intent of the code.
Bldg - Exit access - Common path of egress travel
Resolved
06/19/2012

2006 IBC 1014.3 - Common path of egress travel. In occupancies other than Groups H-1, H-2 and H-3, the common path of egress travel shall not exceed 75 feet. In Group H-1, H-2 and H-3 occupancies, the common path of egress travel shall not exceed 25 feet. For common path of egress travel in Group A occupancies having fixed seating, see Section 1025.8. (See code for possible exceptions.) Common path of travel is not allowed to converge back together once it is separated. In this design, the common path separates as soon as you enter the common corridors and then comes back to within 25 feet of each other. I have discussed this with Mark Dunning and we feel that this meets the intent of the code as it does not meet back up and the elevation of protection in this buidling.
License Tax Codes Approved 06/18/2012 06/15/2012
Mike Weisenborn
Zoning Review Approved 08/29/2013 06/07/2012
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $21,980.00 $21,980.00 Paid 08/06/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 8/13/2012 at 12:00 AM 08/13/2012
Misc
Partial Correction
08/13/2012
OK TO COVER WHEN READY WALL TOP-OUT AT FOLLOWING LOCATIONS: FROM D.1/5.7 TO H.6/5.7 TO H.6/6; H.2/6.5 TO F.9/6.6 TO H.6/6.8 TO H.9/6.7;
Rated Assembly Inspection Partial 8/13/2012 at 12:00 AM 08/13/2012
Misc
Partial Correction
08/13/2012
OK TO TAPE, MUD AND FIRE-SEAL WHEN READY 5/8" TYPE X GWB WALL TOP-OUT AT FOLLOWING LOCATIONS: CORRIDOR FACE FROM D.1/5.7 TO H.6/5.7 TO H.6/6; CORRIDOR & 4F033 FACE FROM H.2/6.5 TO F.9/6.6 TO H.6/6.8 TO H.9/6.7;
In-wall Inspection Partial 8/23/2012 at 12:00 AM 08/23/2012
Misc
Partial Correction
08/13/2012
OK TO COVER WHEN READY WALL TOP-OUT AT FOLLOWING LOCATIONS: FROM D.1/5.7 TO H.6/5.7 TO H.6/6; H.2/6.5 TO F.9/6.6 TO H.6/6.8 TO H.9/6.7;
Misc
Partial Correction
08/23/2012
OK TO COVER WHEN READY EXTERIOR PERIMETER WALLS FROM BLDG "A" @ D.5/9 TO EE/2 TO O/9 TO K/3 TO G/4 TO E/0; ALONG SE EXTERIOR WALL; ALONG S EXTERIOR WALL TO BLDG "A"
Rated Assembly Inspection Partial 9/25/2012 9/26/2012 at 12:00 AM 09/26/2012
Misc
Resolved
09/26/2012
OK TO TAPE, MUD AND FIRE-SEAL WHEN READY WALL TOP-OUT AT FOLLOWING LOCATIONS: CORRIDOR FACE FROM D.1/5.7 TO H.6/5.7 TO H.6/6; CORRIDOR & 4F033 FACE FROM H.2/6.5 TO F.9/6.6 TO H.6/6.8 TO H.9/6.7;
Misc
Partial Correction
09/26/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD;
In-wall Inspection Partial 9/26/2012 9/26/2012 at 12:00 AM 09/26/2012
Misc
Resolved
09/26/2012
OK TO COVER WHEN READY WALL TOP-OUT AT FOLLOWING LOCATIONS: FROM D.1/5.7 TO H.6/5.7 TO H.6/6; H.2/6.5 TO F.9/6.6 TO H.6/6.8 TO H.9/6.7;
Misc
Resolved
09/26/2012
OK TO COVER WHEN READY EXTERIOR PERIMETER WALLS FROM BLDG "A" @ D.5/9 TO EE/2 TO O/9 TO K/3 TO G/4 TO E/0; ALONG SE EXTERIOR WALL; ALONG S EXTERIOR WALL TO BLDG "A"
Misc
Partial Correction
09/26/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065;
Rated Assembly Inspection Partial 9/26/2012 at 12:00 AM 09/26/2012
Misc
Partial Correction
09/26/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD;
Rated Assembly Inspection Partial 9/28/2012 at 12:00 AM 09/28/2012
Misc
Partial Correction
09/26/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + ONE LAYER 5/8" TYPE X GWB
In-wall Inspection Partial 9/28/2012 09/28/2012
Misc
Partial Correction
09/26/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065;
In-wall Inspection Partial 10/3/2012 10/4/2012 at 12:00 AM 10/04/2012
Misc
Partial Correction
09/28/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076;
In-wall Inspection Partial 10/10/2012 10/10/2012 at 12:00 AM 10/10/2012
Misc
Partial Correction
10/04/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076;
Misc
Partial Correction
10/10/2012
MEP AT MECHANICAL SHAFT: OK TO PLACE SHAFT LINER BOARD AT 3RD & 4TH FLOORS; OK TO PLACE SHAFT LINER BOARD AT 5TH FLOOR AFTER * ITEMS ARE COMPLETED; * AT 5TH FLOOR LEVEL REMOVE ABANDONED STRAP HANGER & FORM TIE; ALSO REPAIR DAMAGED INSULATION TWO LOCATIONS ON VERTICAL PIPE.
Rated Assembly Inspection Partial 10/10/2012 10/10/2012 at 12:00 AM 10/10/2012
Misc
Partial Correction
09/28/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD AND FIRE-SEAL
In-wall Inspection Partial 10/12/2012 10/12/2012 at 12:00 AM 10/12/2012
Misc
Partial Correction
10/10/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041;
Misc
Partial Correction
10/10/2012
MEP AT MECHANICAL SHAFT: OK TO PLACE SHAFT LINER BOARD AT 3RD, 4TH & 5TH FLOORS;
Above Ceiling Inspection Partial 10/12/2012 10/12/2012 at 12:00 AM 10/12/2012
Misc
Partial Correction
10/12/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012;
Rated Assembly Inspection Partial 10/17/2012 10/17/2012 at 12:00 AM 10/17/2012
Misc
Partial Correction
10/10/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD AND FIRE-SEAL
Misc
Partial Correction
10/17/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RE-CONSTRUCTION OF RATED WALL AT MECHANICAL SHAFT @ 4TH FLOOR: FRAMING & SHAFT LINER BOARD;
Above Ceiling Inspection Partial 10/17/2012 at 12:00 AM 10/17/2012
Misc
Partial Correction
10/12/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065 AND NURSE WORK STATIONS IN CORRIDOR 031 AFTER ALL CEILING JOISTS ARE SCREWED BOTH FLANGES;
In-wall Inspection Partial 10/17/2012 10/17/2012 at 12:00 AM 10/17/2012
Misc
Partial Correction
10/12/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033 INCLUDING @ COLUMN AFTER COPPER MED GAS PIPING IS PROTECTED WHERE IT PASSES THROUGH FRAMING OPENINGS;
Misc
Partial Correction
10/12/2012
MEP AT MECHANICAL SHAFT: OK TO PLACE SHAFT LINER BOARD AT 3RD, 4TH & 5TH FLOORS;
Rated Assembly Inspection Partial 10/26/2012 at 12:00 AM 10/26/2012
Misc
Partial Correction
10/17/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD AND FIRE-SEAL
Misc
Partial Correction
10/17/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RE-CONSTRUCTION OF RATED WALL AT MECHANICAL SHAFT @ 4TH FLOOR: FRAMING & SHAFT LINER BOARD; 1 LAYER 5/8" TYPE X GWB;
Misc
Corrective Action Required
10/26/2012
GWB @ SPACES 4F036; 037; 040: EXPOSE ALL SCREW HEADS FOR SCREW PATTERN INSPECTION
Rated Assembly Inspection Partial 10/30/2012 at 12:00 AM 10/30/2012
Misc
Partial Correction
10/26/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD AND FIRE-SEAL
Misc
Partial Correction
10/26/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RE-CONSTRUCTION OF RATED WALL AT MECHANICAL SHAFT @ 4TH FLOOR: FRAMING & SHAFT LINER BOARD; 2 LAYERS 5/8" TYPE X GWB MECHANICAL SHAFT @ 3RD FLOOR: FRAMING + LINER BOARD;
Misc
Partial Correction
10/30/2012
OK TO TAPE, MUD & FIRE-SEAL RATED GWB BOTH FACES @ SPACES 4F036; 037; 040; 082
Rated Assembly Inspection Partial 10/31/2012 at 12:00 AM 10/31/2012
Misc
Partial Correction
10/30/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD AND FIRE-SEAL
Misc
Partial Correction
10/30/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RE-CONSTRUCTION OF RATED WALL AT MECHANICAL SHAFT @ 4TH FLOOR: FRAMING & SHAFT LINER BOARD; 2 LAYERS 5/8" TYPE X GWB MECHANICAL SHAFT @ 3RD FLOOR: FRAMING + LINER BOARD; 1ST LAYER 5/8" TYPE X GWB
Misc
Partial Correction
10/30/2012
OK TO TAPE, MUD & FIRE-SEAL RATED GWB BOTH FACES @ SPACES 4F036; 037; 040; 082
In-wall Inspection Partial 11/7/2012 at 12:00 AM 11/07/2012
Misc
Partial Correction
10/17/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END;
Misc
Resolved
11/07/2012
MEP AT MECHANICAL SHAFT: OK TO PLACE SHAFT LINER BOARD AT 3RD, 4TH & 5TH FLOORS;
Above Ceiling Inspection Failed 11/7/2012 at 12:00 AM 11/07/2012
Misc
Partial Correction
10/17/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031;
Misc
Corrective Action Required
11/07/2012
SOFFITS @ CORRIDORS 4F016, 031, 034/035, 041: 1) REINFORCE ALL TENSION STUDS WHICH HAVE BEEN COPED TO ALLOW PASSAGE OF M/E/P SYSTEMS 2) HEADER SEVERED TENSION STUDS AND DISTRIBUTE THEIR LOADS TO ADJACENT STUDS; FULLY SCREW CONNECTIONS 3) SCREW BOTH FLANGES OF TENSION STUDS TO TOP TRACK UNLESS OTHERWISE DIRECTED IN WRITING BY A/E
Above Ceiling Inspection Partial 11/9/2012 11/9/2012 at 12:00 AM 11/09/2012
Misc
Partial Correction
11/07/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ CORRIDORS 4F016, 031, 034/035, 041;
Misc
Resolved
11/09/2012
SOFFITS @ CORRIDORS 4F016, 031, 034/035, 041: 1) REINFORCE ALL TENSION STUDS WHICH HAVE BEEN COPED TO ALLOW PASSAGE OF M/E/P SYSTEMS 2) HEADER SEVERED TENSION STUDS AND DISTRIBUTE THEIR LOADS TO ADJACENT STUDS; FULLY SCREW CONNECTIONS 3) SCREW BOTH FLANGES OF TENSION STUDS TO TOP TRACK UNLESS OTHERWISE DIRECTED IN WRITING BY A/E
Above Ceiling Inspection Partial 11/14/2012 11/14/2012 at 12:00 AM 11/14/2012
Misc
Partial Correction
11/09/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041;
In-wall Inspection Partial 11/9/2012 11/14/2012 at 12:00 AM 11/14/2012
Misc
Partial Correction
11/07/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A;
Rated Assembly Inspection Partial 11/14/2012 at 12:00 AM 11/14/2012
Misc
Resolved
11/14/2012
2-HR BUMP-OUTS AT TUBE COLUMNS AT 3RD & 4TH FLOOR FREIGHT ELEVATOR WALLS OK TO COVER: FRAMING AND LINER BOARD; + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD AND FIRE-SEAL
Misc
Resolved
11/14/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RE-CONSTRUCTION OF RATED WALL AT MECHANICAL SHAFT @ 4TH FLOOR: FRAMING & SHAFT LINER BOARD; 2 LAYERS 5/8" TYPE X GWB MECHANICAL SHAFT @ 3RD FLOOR: FRAMING + LINER BOARD; 1ST LAYER 5/8" TYPE X GWB
Misc
Resolved
11/14/2012
OK TO TAPE, MUD & FIRE-SEAL RATED GWB BOTH FACES @ SPACES 4F036; 037; 040; 082
Misc
Partial Correction
11/14/2012
DOGLEGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD;
In-wall Inspection Partial 11/19/2012 at 12:00 AM 11/19/2012
Misc
Partial Correction
11/14/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 072
Rated Assembly Inspection Partial 11/19/2012 11/19/2012 at 12:00 AM 11/19/2012
Misc
Partial Correction
11/14/2012
DOGLEGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + ONE LAYER 5/8" TYPE X GWB
In-wall Inspection Partial 11/21/2012 11/21/2012 at 12:00 AM 11/21/2012
Misc
Partial Correction
11/19/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076
Rated Assembly Inspection Partial 11/21/2012 11/21/2012 at 12:00 AM 11/21/2012
Misc
Partial Correction
11/19/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
11/21/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER FOLLOWING COMPONENTS OK TO COVER WHEN READY: 2ND FLOOR OPENINGS -- FRAMING + LINER BOARD + FIRE-CAULK;
Rated Assembly Inspection Partial 11/28/2012 11/28/2012 at 12:00 AM 11/28/2012
Misc
Partial Correction
11/21/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
11/21/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER FOLLOWING COMPONENTS OK TO COVER WHEN READY: 2ND FLOOR OPENINGS -- FRAMING + LINER BOARD + FIRE-CAULK + 1ST LAYER 5/8" TYPE X GWB; 1ST FLOOR OPENINGS -- FRAMING + LINER BOARD
Rated Assembly Inspection Partial 12/4/2012 12/4/2012 at 12:00 AM 12/04/2012
Misc
Partial Correction
11/28/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
11/28/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Above Ceiling Inspection Partial 12/12/2012 12/12/2012 at 12:00 AM 12/12/2012
Misc
Partial Correction
11/14/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041;
Misc
Partial Correction
12/12/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F017; 018; 023 THRU 030; 061/061A THRU 064/064A; 065B THRU 070/070A;
Occupancy Inspection - Codes Commercial Partial 12/13/2012 at 12:00 AM 12/18/2012
Misc
Partial Correction
12/18/2012
ELEVATORS AT 120 SURGICENTER INSTALLED UNDER THIS PERMIT APPROVED BY STATE OF MISSOURI INSPECTOR 12/13/12.
Above Ceiling Inspection Partial 12/19/2012 at 12:00 AM 12/19/2012
Misc
Partial Correction
12/12/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT;
Misc
Partial Correction
12/12/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F017; 018; 023 THRU 030; 061/061A THRU 064/064A; 065B THRU 070/070A; 035; 042; 043; 036; 038; 039; 040; 072; 073/073A; 074; 076;
In-wall Inspection Partial 12/19/2012 at 12:00 AM 12/19/2012
Misc
Partial Correction
11/21/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE;
Rated Assembly Inspection Partial 12/19/2012 12/19/2012 at 12:00 AM 12/19/2012
Misc
Partial Correction
12/04/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
12/04/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED BUMP-OUTS AT 5TH FLOOR ELEVATOR SHAFT WALLS -- ONE @ S WALL + TWO @ N WALL: FRAMING + LINER BOARD FIRE-CAULKED
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF 5TH FLOOR RATED UTILITY SHAFT WALL: FRAMING + LINER BOARD FIRE-CAULKED;
Rated Assembly Inspection Partial 12/21/2012 12/21/2012 at 12:00 AM 12/21/2012
Misc
Partial Correction
12/19/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
12/19/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED BUMP-OUTS AT 5TH FLOOR ELEVATOR SHAFT WALLS -- ONE @ S WALL + TWO @ N WALL: FRAMING + LINER BOARD FIRE-CAULKED; ONE LAYER 5/8" TYPE X GWB
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF 5TH FLOOR RATED UTILITY SHAFT WALL: FRAMING + LINER BOARD FIRE-CAULKED; ONE LAYER 5/8" TYPE X GWB
Above Ceiling Inspection Partial 12/28/2012 12/28/2012 at 12:00 AM 12/28/2012
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT;
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F017; 018; 023 THRU 030; 035; 036; 038; 039; 040; 042; 043; 061/061A THRU 064/064A; 065B THRU 070/070A; 072; 073/073A; 074; 076; [*015; 016; 022; 031; 034; 037; 041; 071A; 072A; 074A; 075A; 076A*]; *LUMINAIRES ON ORDER TO BE INSTALLED WHEN RECEIVED
Rated Assembly Inspection Partial 12/28/2012 at 12:00 AM 12/28/2012
Misc
Partial Correction
12/21/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
12/21/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Misc
Partial Correction
12/21/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED BUMP-OUTS AT 5TH FLOOR ELEVATOR SHAFT WALLS -- ONE @ S WALL + TWO @ N WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Partial Correction
12/21/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF 5TH FLOOR RATED UTILITY SHAFT WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Rated Assembly Inspection Partial 1/3/2013 1/3/2013 at 12:00 AM 01/03/2013
Misc
Partial Correction
12/28/2012
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
12/28/2012
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Misc
Partial Correction
12/28/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED BUMP-OUTS AT 5TH FLOOR ELEVATOR SHAFT WALLS -- ONE @ S WALL + TWO @ N WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Partial Correction
12/28/2012
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF 5TH FLOOR RATED UTILITY SHAFT WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Partial Correction
01/03/2013
2ND, 3RD AND 4TH CORE BOARD AROUND ELEVATOR DOORS APPROVED 1ST LAYER.
Sprinkler - Hydrostatic Test Failed 1/4/2013 at 12:00 AM 01/04/2013
Sprinkler - Hydrostatic Test Passed 1/7/2013 at 8:00 AM 01/07/2013
Rated Assembly Inspection Not Ready 1/9/2013 1/9/2013 at 12:00 AM 01/09/2013
Misc
Partial Correction
01/03/2013
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Partial Correction
01/03/2013
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Misc
Partial Correction
01/03/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED BUMP-OUTS AT 5TH FLOOR ELEVATOR SHAFT WALLS -- ONE @ S WALL + TWO @ N WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Partial Correction
01/03/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF 5TH FLOOR RATED UTILITY SHAFT WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Partial Correction
01/03/2013
2ND, 3RD AND 4TH CORE BOARD AROUND ELEVATOR DOORS APPROVED 1ST LAYER.
In-wall Inspection Partial 1/9/2013 1/9/2013 at 12:00 AM 01/09/2013
Misc
Partial Correction
12/19/2012
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS;
Above Ceiling Inspection Partial 1/10/2013 1/10/2013 at 12:00 AM 01/10/2013
Misc
Partial Correction
12/28/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT;
Misc
Partial Correction
12/28/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F011; 015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065B THRU 070/070A; 071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A;
Above Ceiling Inspection Partial 1/10/2013 at 12:00 AM 01/10/2013
Misc
Partial Correction
01/10/2013
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT;
Misc
Partial Correction
01/10/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A;
Rated Assembly Inspection Partial 1/15/2013 (8:00 to 5:00) 1/15/2013 at 12:00 AM 01/15/2013
Misc
Resolved
01/15/2013
DOGLEGGED RATED WALL ASSEMBLY ABOVE CEILING @ 4F032 SOUTH END - OK TO COVER WHEN READY: FRAMING + LINER BOARD + TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-SEAL
Misc
Resolved
01/15/2013
RATED CLOSURES FROM CONCRETE WALLS TO ELEVATOR DOOR FRAMES AT SURGICENTER 1ST & 2ND FLOOR OPENINGS COMPLETE
Misc
Resolved
01/15/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED BUMP-OUTS AT 5TH FLOOR ELEVATOR SHAFT WALLS -- ONE @ S WALL + TWO @ N WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Resolved
01/15/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF 5TH FLOOR RATED UTILITY SHAFT WALL: FRAMING + LINER BOARD FIRE-CAULKED; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, & FIRE-SEAL
Misc
Partial Correction
01/09/2013
FOLLOWING COMPONENTS OF PASSENGER ELEVATOR FRONTS OK TO COVER WHEN READY : 1ST FLOOR: FRAMING, LINER BOARD + FIRE CAULK; 3RD, 5TH FLOORS: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED;
Misc
Partial Correction
01/15/2013
FOLLOWING COMPONENTS OF 1ST FLOOR FREIGHT ELEVATOR SHAFT OK TO COVER WHEN READY: FRAMING, LINER BOARD + FIRE CAULK;
Misc
Partial Correction
01/15/2013
FOLLOWING COMPONENTS OF FREIGHT ELEVATOR FRONTS OK TO COVER WHEN READY: 2ND FLOOR THROUGH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK;
Underslab Plumbing Inspection - Commercial Partial 1/15/2013 (8:00 to 5:00) 1/15/2013 at 12:00 AM 01/15/2013
Misc
Partial Correction
01/15/2013
OK TO COVER WHEN READY UNDER-SLAB C.I. DWV PIPING @ SPACE 1A092
In-wall Inspection Partial 1/18/2013 (8:00 to 5:00) 1/18/2013 at 12:00 AM 01/18/2013
Misc
Partial Correction
01/09/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW;
Rated Assembly Inspection Partial 1/18/2013 (8:00 to 5:00) 1/18/2013 at 12:00 AM 01/18/2013
Misc
Partial Correction
01/15/2013
FOLLOWING COMPONENTS OF PASSENGER ELEVATOR FRONTS OK TO COVER WHEN READY : 1ST FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED; 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 3RD FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED; 4TH FLOOR: 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED
Misc
Partial Correction
01/15/2013
FOLLOWING COMPONENTS OF 1ST FLOOR FREIGHT ELEVATOR SHAFT OK TO COVER WHEN READY: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB
Misc
Partial Correction
01/15/2013
FOLLOWING COMPONENTS OF FREIGHT ELEVATOR FRONTS OK TO COVER WHEN READY: 2ND FLOOR THROUGH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB
Rated Assembly Inspection Partial 1/18/2013 at 12:00 AM 01/18/2013
Misc
Partial Correction
01/18/2013
FOLLOWING COMPONENTS OF PASSENGER ELEVATOR FRONTS OK TO COVER WHEN READY : 1ST FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED; 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 3RD FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED; 4TH FLOOR: 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB FIRE-CAULKED
Misc
Partial Correction
01/18/2013
FOLLOWING COMPONENTS OF 1ST FLOOR FREIGHT ELEVATOR SHAFT OK TO COVER WHEN READY: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB
Misc
Partial Correction
01/18/2013
FOLLOWING COMPONENTS OF FREIGHT ELEVATOR FRONTS OK TO COVER WHEN READY: 2ND FLOOR THROUGH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; ONE LAYER 5/8" TYPE X GWB
Misc
Partial Correction
01/18/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALL @ 4F021 SW: ONE LAYER OF 5/8" TYPE X GWB
Rated Assembly Inspection Partial 1/22/2013 1/22/2013 at 12:00 AM 01/22/2013
Misc
Partial Correction
01/18/2013
FOLLOWING COMPONENTS OF PASSENGER ELEVATOR FRONTS OK TO COVER WHEN READY : 1ST FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 3RD FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 4TH FLOOR: 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/18/2013
FOLLOWING COMPONENTS OF 1ST FLOOR FREIGHT ELEVATOR SHAFT OK TO COVER WHEN READY: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/18/2013
FOLLOWING COMPONENTS OF FREIGHT ELEVATOR FRONTS OK TO COVER WHEN READY: 2ND FLOOR THROUGH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/18/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALL @ 4F021 SW: TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Alarm Test Passed 1/23/2013 at 12:00 AM 01/23/2013
Sprinkler - Flow Test Passed 1/23/2013 at 12:00 AM 01/23/2013
In-wall Inspection Partial 1/23/2013 1/23/2013 at 12:00 AM 01/23/2013
Misc
Partial Correction
01/18/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL;
In-wall Inspection Partial 1/24/2013 1/24/2013 at 12:00 AM 01/24/2013
Misc
Partial Correction
01/23/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; BOTH FACES OF CORRIDOR CROSSWALL @ DOOR #3F007;
In-wall Inspection Not Ready 1/28/2013 1/28/2013 at 12:00 AM 01/28/2013
Misc
Partial Correction
01/24/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; BOTH FACES OF CORRIDOR CROSSWALL @ DOOR #3F007;
Rated Assembly Inspection Partial 1/28/2013 1/28/2013 at 12:00 AM 01/28/2013
Misc
Resolved
01/28/2013
FOLLOWING COMPONENTS OF PASSENGER ELEVATOR FRONTS OK TO COVER WHEN READY : 1ST FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 3RD FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 4TH FLOOR: 2ND FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Resolved
01/28/2013
FOLLOWING COMPONENTS OF 1ST FLOOR FREIGHT ELEVATOR SHAFT OK TO COVER WHEN READY: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Resolved
01/28/2013
FOLLOWING COMPONENTS OF FREIGHT ELEVATOR FRONTS OK TO COVER WHEN READY: 2ND FLOOR THROUGH 5TH FLOOR: FRAMING, LINER BOARD + FIRE CAULK; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/22/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALL @ 4F021 SW: TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/28/2013
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT FOLLOWING LOCATIONS: S/E WALL @ 1F001 ONE LAYER 5/8" TYPE X GWB; BOTH FACES CORRIDOR CROSSWALL @ DOOR #3F007 ONE LAYER 5/8" TYPE X GWB;
Miscellaneous Inspection Partial 1/28/2013 at 12:00 AM 01/28/2013
In-wall Inspection Partial 1/29/2013 1/29/2013 at 12:00 AM 01/29/2013
Misc
Partial Correction
01/28/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING AT EXISTING SURGERY WAITING ROOM
Rated Assembly Inspection Partial 1/29/2013 1/29/2013 at 12:00 AM 01/29/2013
Misc
Partial Correction
01/28/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALL @ 4F021 SW: TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/28/2013
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT FOLLOWING LOCATIONS: S/E WALL @ 1F001 TWO LAYERS 5/8" TYPE X GWB; BOTH FACES CORRIDOR CROSSWALL @ DOOR #3F007;
Miscellaneous Inspection Partial 1/29/2013 at 12:00 AM 01/29/2013
Miscellaneous Inspection Partial 1/30/2013 at 12:00 AM 01/30/2013
Rated Assembly Inspection Partial 1/31/2013 1/31/2013 at 12:00 AM 01/31/2013
Misc
Partial Correction
01/29/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALL @ 4F021 SW: TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Partial Correction
01/29/2013
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT FOLLOWING LOCATIONS: S/E WALL @ 1F001 TWO LAYERS 5/8" TYPE X GWB; BOTH FACES CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM OK TO TAPE, MUD & FIRE-SEAL AFTER TWO LAYERS OF 5/8" TYPE X GWB ARE IN PLACE
In-wall Inspection Partial 1/31/2013 at 12:00 AM 01/31/2013
Misc
Partial Correction
01/29/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090
Miscellaneous Inspection Passed 1/31/2013 at 12:00 AM 01/31/2013
Occupancy Inspection - Codes Commercial Partial 2/1/2013 2/1/2013 at 12:00 AM 02/01/2013
Misc
Partial Correction
12/18/2012
ELEVATORS AT 120 SURGICENTER INSTALLED UNDER THIS PERMIT APPROVED BY STATE OF MISSOURI INSPECTOR 12/13/12.
Misc
Partial Correction
02/01/2013
4TH FLOOR FINAL: OK TO SET UP FOR OPERATION REQUIRED FOR FULL OCCUPANCY: - STATE ELEVATOR INSPECTION APPROVAL - INSTALLATION OF BACKFLOW PREVENTION DEVICES AT EQUIPMENT PIPED WITH POTABLE WATER - FINAL WORK IN PROGRESS AT NEW-TO-EXISTING INTERFACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO
Occupancy Inspection - Fire Passed 02/01/2013
Occupancy Inspection - Codes Commercial Partial 2/5/2013 at 12:00 AM 02/05/2013
Misc
Partial Correction
02/01/2013
ELEVATORS AT 120 SURGICENTER INSTALLED UNDER THIS PERMIT APPROVED BY STATE OF MISSOURI INSPECTOR 12/13/12.
Misc
Partial Correction
02/01/2013
4TH FLOOR FINAL: OK TO SET UP FOR OPERATION REQUIRED FOR FULL OCCUPANCY: - STATE ELEVATOR INSPECTION APPROVAL - INSTALLATION OF BACKFLOW PREVENTION DEVICES AT EQUIPMENT PIPED WITH POTABLE WATER - FINAL WORK IN PROGRESS AT NEW-TO-EXISTING INTERFACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO
Above Ceiling Inspection Partial 2/8/2013 2/8/2013 at 12:00 AM 02/08/2013
Misc
Partial Correction
01/10/2013
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT; ELEVATOR CORRIDOR 001 EXCEPT WHERE STRUCTURAL EXPANSION JOINT REQUIRES FIRE PROTECTION AND ELECT CABLE TRAY REQUIRES "PILLOWS".
Misc
Partial Correction
01/10/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A;
Occupancy Inspection - Codes Commercial Temporary C of O 2/8/2013 at 12:00 AM 02/08/2013
Misc
Resolved
02/08/2013
ELEVATORS AT 120 SURGICENTER INSTALLED UNDER THIS PERMIT APPROVED BY STATE OF MISSOURI INSPECTOR 12/13/12.
Misc
Partial Correction
02/05/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY REQUIRED FOR FULL OCCUPANCY: - INSTALLATION OF BACKFLOW PREVENTION DEVICES AT EQUIPMENT PIPED WITH POTABLE WATER - FINAL WORK IN PROGRESS AT NEW-TO-EXISTING INTERFACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO
In-wall Inspection Partial 2/19/2013 2/19/2013 at 12:00 AM 02/19/2013
Misc
Partial Correction
01/31/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 001 E WALL 1F090 W WALL FROM B/6 TO SOUTH;
In-wall Inspection Partial 2/19/2013 at 12:00 AM 02/19/2013
Misc
Partial Correction
02/19/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH;
Rated Assembly Inspection Partial 2/21/2013 2/21/2013 at 12:00 AM 02/21/2013
Misc
Resolved
02/21/2013
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED WALL @ 4F021 SW: TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD & FINISH
Misc
Resolved
02/21/2013
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT FOLLOWING LOCATIONS: S/E WALL @ 1F001 TWO LAYERS 5/8" TYPE X GWB; BOTH FACES CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM OK TO TAPE, MUD & FIRE-SEAL AFTER TWO LAYERS OF 5/8" TYPE X GWB ARE IN PLACE
Misc
Corrective Action Required
02/21/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 1ST LAYER 5/8" TYPE X GWB;
In-wall Inspection Partial 2/22/2013 2/22/2013 at 12:00 AM 02/22/2013
Misc
Partial Correction
02/19/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED
In-wall Inspection Partial 2/27/2013 2/27/2013 at 12:00 AM 02/27/2013
Misc
Partial Correction
02/22/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED,
Rated Assembly Inspection Partial 2/27/2013 2/27/2013 at 12:00 AM 02/27/2013
Misc
Corrective Action Required
02/21/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 1ST LAYER 5/8" TYPE X GWB;
Rated Assembly Inspection Partial 2/28/2013 2/28/2013 at 12:00 AM 02/28/2013
Misc
Partial Correction
02/28/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 2 LAYERS 5/8" TYPE X GWB; NE WALL 2 LAYERS 5/8" TYPE X GWB; IN-FILL @ E WALL 1ST LAYER 5/8" TYPE X GWB
Misc
Resolved
02/28/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 1ST LAYER 5/8" TYPE X GWB;
In-wall Inspection Partial 2/28/2013 at 12:00 AM 02/28/2013
Misc
Partial Correction
02/27/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL;
Rated Assembly Inspection Partial 3/1/2013 3/1/2013 at 12:00 AM 03/01/2013
Misc
Partial Correction
02/28/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 2 LAYERS 5/8" TYPE X GWB; NE WALL 2 LAYERS 5/8" TYPE X GWB; IN-FILL @ E WALL 2 LAYERS 5/8" TYPE X GWB NOTE: CHECK BUMP-OUT AT INTERSECTION OF NE WALL & IN-FILL @ E WALL TO ENSURE 2-LAYER FIRE INTEGRITY.
In-wall Inspection Partial 3/5/2013 3/5/2013 at 12:00 AM 03/05/2013
Misc
Partial Correction
02/28/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL; JAN CLO 1A092; 1A090 9'Hx14'W SECTION OF W WALL;
In-wall Inspection Partial 3/6/2013 3/6/2013 at 12:00 AM 03/06/2013
Misc
Partial Correction
03/05/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL; JAN CLO 1A092; 1A090 9'Hx14'W SECTION OF W WALL; 1A090 S WALL + S 20' OF E WALL
In-wall Inspection Partial 3/13/2013 3/13/2013 at 12:00 AM 03/13/2013
Misc
Partial Correction
03/06/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL; JAN CLO 1A092; 1A090 9'Hx14'W SECTION OF W WALL; 1A090 S WALL + S 20' OF E WALL; 12' OF TYPE "P" WALL @ 1A090 W; 1F151A;
Rated Assembly Inspection Partial 3/15/2013 3/15/2013 at 12:00 AM 03/15/2013
Misc
Partial Correction
03/01/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 2 LAYERS 5/8" TYPE X GWB; NE WALL 2 LAYERS 5/8" TYPE X GWB; IN-FILL @ E WALL 2 LAYERS 5/8" TYPE X GWB; N,W,S WALLS BOTH FACES SPACE 1F151A -- NOTE: SPACE COMMUNICATES WITH OTHER SPACES VIA OVERHEAD CONCRETE STRUCTURE EXPANSION JOINT -- APPROVABLE CLOSURE REQUIRED;
Above Ceiling Inspection Partial 3/15/2013 3/15/2013 at 12:00 AM 03/15/2013
Misc
Partial Correction
02/08/2013
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT; ELEVATOR CORRIDOR 001 EXCEPT WHERE STRUCTURAL EXPANSION JOINT REQUIRES FIRE PROTECTION AND ELECT CABLE TRAY REQUIRES "PILLOWS".
Misc
Partial Correction
02/08/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007
Above Ceiling Inspection Failed 3/20/2013 3/20/2013 at 12:00 AM 03/20/2013
Misc
Partial Correction
03/15/2013
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT; ELEVATOR CORRIDOR 001 EXCEPT WHERE STRUCTURAL EXPANSION JOINT REQUIRES FIRE PROTECTION AND ELECT CABLE TRAY REQUIRES "PILLOWS".
Misc
Partial Correction
03/15/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007; 1ST FLOOR WAITING ROOM
Misc
Corrective Action Required
03/20/2013
WAITING ROOM 1A090 NOT READY FOR INSPECTION: MULTIPLE ISSUES POINTED OUT TO TURNER, SHAW, AND P1 FOR COMPLETION BEFORE NEXT INSPECTION
Occupancy Inspection - Codes Commercial Partial 3/21/2013 at 12:00 AM 03/21/2013
Misc
Partial Correction
02/08/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING NEW-TO-EXISTING INTERFACE SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021;
Above Ceiling Inspection Partial 3/21/2013 3/21/2013 at 12:00 AM 03/21/2013
Misc
Resolved
03/21/2013
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 3F012; SHOWERS AT 061-065; NURSE WORK STATIONS IN CORRIDOR 031; SOFFITS @ INNER ARC OF CORRIDORS 4F016, 031, 034/035, 041; ARC SOFFITS @ ENDS OF CORRIDORS 4F031/034 & 041; TRIANGULAR SEGMENT IN CORR 021 S OF SE CORNER OF FREIGHT ELEVATOR SHAFT; ELEVATOR CORRIDOR 001 EXCEPT WHERE STRUCTURAL EXPANSION JOINT REQUIRES FIRE PROTECTION AND ELECT CABLE TRAY REQUIRES "PILLOWS".
Misc
Partial Correction
03/20/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007; WAITING ROOM 1A090 NEW NORTH END;
Misc
Resolved
03/21/2013
WAITING ROOM 1A090 NOT READY FOR INSPECTION: MULTIPLE ISSUES POINTED OUT TO TURNER, SHAW, AND P1 FOR COMPLETION BEFORE NEXT INSPECTION
Occupancy Inspection - Codes Commercial Partial 3/22/2013 3/22/2013 at 12:00 AM 03/22/2013
Misc
Partial Correction
03/21/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING NEW-TO-EXISTING INTERFACE SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021; 1F090 NEW NORTH 1/2
Occupancy Inspection - Fire Temporary C of O 3/22/2013 at 12:00 AM 03/22/2013
Underslab Plumbing Inspection - Commercial Partial 3/29/2013 3/29/2013 at 12:00 AM 03/29/2013
Misc
Partial Correction
01/15/2013
OK TO COVER WHEN READY UNDER-SLAB C.I. DWV PIPING @ SPACES: 1A092; 1A090; 1A090B;
In-wall Inspection Partial 4/2/2013 4/2/2013 at 12:00 AM 04/02/2013
Misc
Partial Correction
03/13/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL; JAN CLO 1A092; 1A090 9'Hx14'W SECTION OF W WALL; 1A090 S WALL + S 20' OF E WALL; 12' OF TYPE "P" WALL @ 1A090 W; 1F151A; 1A090 SOUTH WALL; 090C NORTH & EAST WALLS; 090B EAST WALL;
In-wall Inspection Partial 4/4/2013 4/5/2013 at 12:00 AM 04/05/2013
Misc
Partial Correction
04/02/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL; JAN CLO 1A092; 1A090 9'Hx14'W SECTION OF W WALL; 1A090 S WALL + S 20' OF E WALL; 12' OF TYPE "P" WALL @ 1A090 W; 1F151A; 1A090 SOUTH WALL; 090C NORTH & EAST WALLS; 090B EAST WALL; REMAINDER OF AFFECTED WALLS IN 1A090 SE CORNER, O90A & 090B
Above Ceiling Inspection Not Ready 4/15/2013 4/15/2013 at 12:00 AM 04/15/2013
Misc
Partial Correction
03/21/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007; WAITING ROOM 1A090 NEW NORTH END;
Occupancy Inspection - Codes Commercial Temporary C of O 4/16/2013 at 12:00 AM 04/16/2013
Misc
Partial Correction
03/22/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING NEW-TO-EXISTING INTERFACE SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021; 1F090 NEW NORTH 1/2
Above Ceiling Inspection Partial 4/16/2013 4/16/2013 at 12:00 AM 04/16/2013
Misc
Partial Correction
04/15/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007; WAITING ROOM 1A090 NEW NORTH END; 090A; 090B;
Occupancy Inspection - Codes Commercial Temporary C of O 4/18/2013 at 12:00 AM 04/18/2013
Misc
Partial Correction
04/16/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING NEW-TO-EXISTING INTERFACE SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021; 1F090 NEW NORTH 1/2
Occupancy Inspection - Codes Commercial Partial 4/22/2013 4/22/2013 at 12:00 AM 04/22/2013
Misc
Partial Correction
04/18/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING NEW-TO-EXISTING INTERFACE SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021; 1F090 NEW NORTH 1/2; 1A091; 1A090A AND 090B CONTINGENT ON INSTALLATION OF VERTICAL GRAB BARS AND H/C ACCESSIBLE SIGNS NLT 5/6/13;
Above Ceiling Inspection Partial 5/1/2013 5/1/2013 at 12:00 AM 05/01/2013
Misc
Partial Correction
04/16/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007; WAITING ROOM 1A090 NEW NORTH END; 090A; 090B; WAITING ROOM 1A090 SOUTH END; 1A090C
Occupancy Inspection - Codes Commercial Temporary C of O 5/6/2013 5/6/2013 at 12:00 AM 05/06/2013
Misc
Partial Correction
04/22/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING INTERFACE SPACES AND MODIFIED EXISTING SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021; 1F090 COMPLETE; 1A091; 1A090A 090B AND 090C CONTINGENT ON INSTALLATION OF H/C ACCESSIBLE SIGNS;
Misc
Corrective Action Required
05/06/2013
ONLY SPACE 1F151A REMAINS TO BE APPROVED WHEN READY FOR FINAL INSPECTION. MED GAS EXHAUST IS REQUIRED IN THIS SPACE FOR INTENDED USE & OCCUPANCY.
Occupancy Inspection - Fire Temporary C of O 5/6/2013 at 12:00 AM 05/06/2013
Misc
Corrective Action Required
05/06/2013
PRCOM20121257: Rooms 1A900B, 1A909A, 1A091, 1A090C, 1A090 southend are completed, only remaining room on this pwermit is Emerg.O2 room 1F151A which will be completed along with another permit held by JEDunn.
Occupancy Inspection - Codes Commercial Temporary C of O 6/13/2013 at 12:00 AM 06/13/2013
Misc
Resolved
06/13/2013
4TH FLOOR FINAL: OK FOR OCCUPANCY - OK TO USE AND OCCUPY THE FOLLOWING INTERFACE SPACES AND MODIFIED EXISTING SPACES AS DESCRIBED IN ADAM WIEDERHOLT 1/30/2013 E-MAIL MEMO: 1F001; 2F020; 2F021; 4F020; 4F021; 1F090 COMPLETE; 1A091; 1A090A 090B AND 090C CONTINGENT ON INSTALLATION OF H/C ACCESSIBLE SIGNS;
Misc
Corrective Action Required
05/06/2013
ONLY SPACE 1F151A REMAINS TO BE APPROVED WHEN READY FOR FINAL INSPECTION. MED GAS EXHAUST IS REQUIRED IN THIS SPACE FOR INTENDED USE & OCCUPANCY.
Occupancy Inspection - Codes Commercial Temporary C of O 7/26/2013 at 12:00 AM 07/26/2013
Misc
Corrective Action Required
06/13/2013
ONLY SPACE 1F151A REMAINS TO BE APPROVED WHEN READY FOR FINAL INSPECTION. MED GAS EXHAUST IS REQUIRED IN THIS SPACE FOR INTENDED USE & OCCUPANCY.
Occupancy Inspection - Fire Temporary C of O 8/29/2013 at 12:00 AM 08/29/2013
Misc
Corrective Action Required
08/29/2013
Oxygen back-up room (1F151A) for 4th floor ICU -exhaust for the room needs to enclosed in 1-hour protection from the room until it exits the building - property owner to verify that all the red outlets and switches supply power during a generator test.
Occupancy Inspection - Codes Commercial Temporary C of O 8/29/2013 8/29/2013 at 12:00 AM 08/29/2013
Misc
Partial Correction
08/29/2013
ONLY SPACE 1F151A REMAINS TO BE APPROVED WHEN READY FOR FINAL INSPECTION. MED GAS EXHAUST IS REQUIRED IN THIS SPACE FOR INTENDED USE & OCCUPANCY. 8/29/13: PER FD, DUCT MUST BE PROTECTED BEFORE APPROVAL.
Miscellaneous Inspection Passed 8/29/2013 at 12:00 AM 08/29/2013
Above Ceiling Inspection Passed 5/1/2013 at 12:00 AM 08/29/2013
Misc
Resolved
08/29/2013
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4F015; 016; 017; 018; 022; 023 THRU 030; 031; 034; 035; 036; 037; 038; 039; 040; 041; 042; 043; 061/061A THRU 064/064A; 065/065A; 065B THRU 070/070A; 071/071A; 072/072A; 073/073A; 074/074A; 075/075A; 076/076A; 1F007; WAITING ROOM 1A090 NEW NORTH END; 090A; 090B; WAITING ROOM 1A090 SOUTH END; 1A090C
In-wall Inspection Passed 4/5/2013 at 12:00 AM 08/29/2013
Misc
Resolved
08/29/2013
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: 3F012; 4F017 THRU 020; 024 THRU 019; 061; 061A THRU 065; 066 thru 070; 072; 045; 075; 042; 074; 075; 076; 016; 034 THRU 041; 031; 032; 033; 016 N END; 4F020 BOTH FACES EXCEPT SE WHERE LATER TO INTERFACE W/ BLDG 100; 022 OUTSIDE FACE WHERE REMOVED FOR MODIFICATIONS AND REPLACED ; 071A; DUPLEX EMERGENCY CIRCUIT ELECT RECEPT ADDED TO HEADWALL @ IC UNITS 4F061 THROUGH 076; 071 SE; PASSENGER ELEVATOR ENTRANCES AT 2ND & 4TH FLOORS; WALL + DOOR FRAME @ 4F021 SW; 4F020 SE & SW WALLS; 4F021 NW WALL; CORRIDOR 1F001; CORRIDOR CROSSWALL @ DOOR #3F007; AT NEW DOOR OPENING 1F007C AT EXISTING SURGERY WAITING ROOM; WALL & DOOR MODIFICATIONS AT DOOR OPENING 1A090; 1F090 W WALL FROM B/6 TO SOUTH; ROOM 1A010 THREE WALLS APPROVED; IN-FILL FRAMING & ELECT @ 1A090 E WALL; JAN CLO 1A092; 1A090 9'Hx14'W SECTION OF W WALL; 1A090 S WALL + S 20' OF E WALL; 12' OF TYPE "P" WALL @ 1A090 W; 1F151A; 1A090 SOUTH WALL; 090C NORTH & EAST WALLS; 090B EAST WALL; REMAINDER OF AFFECTED WALLS IN 1A090 SE CORNER, O90A & 090B
Rated Assembly Inspection Passed 3/15/2013 at 12:00 AM 08/29/2013
Misc
Resolved
08/29/2013
OK TO COVER WHEN READY GWB AT UL-RATED WALLS AT 1F090: W WALL FROM B/6 TO SOUTH 2 LAYERS 5/8" TYPE X GWB; NE WALL 2 LAYERS 5/8" TYPE X GWB; IN-FILL @ E WALL 2 LAYERS 5/8" TYPE X GWB; WALLS BOTH FACES SPACE 1F007 -- NOTE: SPACE COMMUNICATES WITH OTHER SPACES VIA OVERHEAD CONCRETE STRUCTURE EXPANSION JOINT -- APPROVABLE CLOSURE REQUIRED;
Underslab Plumbing Inspection - Commercial Passed 3/29/2013 at 12:00 AM 08/29/2013
Misc
Resolved
08/29/2013
OK TO COVER WHEN READY UNDER-SLAB C.I. DWV PIPING @ SPACES: 1A092; 1A090; 1A090B;
Occupancy Inspection - Fire Passed 9/6/2013 at 12:00 AM 09/06/2013
Misc
Corrective Action Required
09/06/2013
PRCOM20121257: Rooms 1A900B, 1A909A, 1A091, 1A090C, 1A090 southend are completed, only remaining room on this pwermit is Emerg.O2 room 1F151A which will be completed along with another permit held by JEDunn.
Occupancy Inspection - Codes Commercial Full C of O 9/6/2013 9/6/2013 at 12:00 AM 09/06/2013
Misc
Resolved
09/06/2013
ONLY SPACE 1F151A REMAINS TO BE APPROVED WHEN READY FOR FINAL INSPECTION. MED GAS EXHAUST IS REQUIRED IN THIS SPACE FOR INTENDED USE & OCCUPANCY. 8/29/13: PER FD, DUCT MUST BE PROTECTED BEFORE APPROVAL.
Documents & Images
Date Uploaded File Type Document Name
06/20/2012 Letter Plan Review Conditions
07/09/2012 Letter Fire (Sprinkler) Plan Review
07/23/2012 Letter Fire (Sprinkler) Plan Review
08/06/2012 Letter Plan Review Conditions
08/06/2012 Letter Building Permit
08/13/2012 Letter Inspection Summary
08/23/2012 Letter Inspection Summary
09/13/2012 Letter Plan Review Conditions
09/26/2012 Letter Inspection Summary
09/28/2012 Letter Inspection Summary
10/04/2012 Letter Inspection Summary
10/10/2012 Letter Inspection Summary
10/10/2012 Letter Inspection Summary
10/12/2012 Letter Inspection Summary
10/17/2012 Letter Inspection Summary
10/26/2012 Letter Inspection Summary
10/30/2012 Letter Inspection Summary
10/31/2012 Letter Inspection Summary
11/07/2012 Letter Inspection Summary
11/09/2012 Letter Inspection Summary
11/14/2012 Letter Inspection Summary
11/19/2012 Letter Inspection Summary
11/19/2012 Letter Inspection Summary
11/21/2012 Letter Inspection Summary
11/28/2012 Letter Inspection Summary
12/12/2012 Letter Inspection Summary
12/19/2012 Activity Document DOC121912-003.pdf
12/19/2012 Letter Inspection Summary
12/21/2012 Letter Inspection Summary
12/28/2012 Letter Inspection Summary
01/03/2013 Letter Inspection Summary
01/09/2013 Letter Inspection Summary
01/10/2013 Letter Inspection Summary
01/15/2013 Letter Inspection Summary
01/18/2013 Letter Inspection Summary
01/18/2013 Letter Inspection Summary
01/22/2013 Letter Inspection Summary
01/23/2013 Letter Inspection Summary
01/24/2013 Letter Inspection Summary
01/28/2013 Letter Inspection Summary
01/29/2013 Letter Inspection Summary
01/31/2013 Letter Inspection Summary
02/01/2013 Letter Inspection Summary
02/08/2013 Letter Temporary Certificate of Occupancy
02/19/2013 Letter Inspection Summary
02/19/2013 Letter Inspection Summary
02/21/2013 Letter Inspection Summary
02/22/2013 Letter Inspection Summary
02/28/2013 Letter Inspection Summary
03/01/2013 Letter Inspection Summary
03/05/2013 Letter Inspection Summary
03/06/2013 Letter Inspection Summary
03/13/2013 Letter Inspection Summary
03/15/2013 Letter Inspection Summary
03/21/2013 Letter Inspection Summary
03/22/2013 Letter Inspection Summary
03/29/2013 Letter Inspection Summary
04/02/2013 Letter Inspection Summary
04/05/2013 Letter Inspection Summary
04/16/2013 Letter Temporary Certificate of Occupancy
04/16/2013 Letter Inspection Summary
04/18/2013 Letter Temporary Certificate of Occupancy
04/22/2013 Letter Inspection Summary
05/01/2013 Letter Inspection Summary
05/06/2013 Letter Fire Loss Reduction Form
05/06/2013 Letter Temporary Certificate of Occupancy
06/13/2013 Letter Temporary Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/26/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Fire (Sprinkler) Plan Review
07/26/2013 Letter Codes Temporary Certificate of Occupancy
08/27/2013 Letter Inspection Summary
08/27/2013 Letter Inspection Summary
08/29/2013 Letter Fire Loss Reduction Form
08/29/2013 Letter Codes Temporary Certificate of Occupancy
09/06/2013 Letter Field Certificate of Occupancy
09/09/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home