Permit Application Status

PRCOM20121142


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20121142
Building Permit - Commercial
Certificate of Occupancy
LE GRAND APARTMENTS LLC
ALTERATION COMMERCIAL
REMODEL TO ENLARGE WORSHIP HALL
05/23/2012
07/09/2012
12/02/2012
07/27/2012
Locations
Contacts
KC CONSTRUCTORS INC, Address:14716 S BYNUM RD, Phone:(816) 246-2095  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
KC CONSTRUCTORS INC, Address:14716 S BYNUM RD, Phone:(816) 246-2095  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
LE GRAND APARTMENTS LLC, Address:25706 E SHADYBROOK LN  
EAGLE CREEK CHURCH, Address:1499 SW MARKET ST, Phone:(816) 872-9872  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 06/05/2012 07/26/2012
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
07/26/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for any sprinkler modifications, if needed
Construction documents for fire alarm systems
Corrective Action Required
07/26/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for any alarm system modifications, if needed
Internal Plan Review (Res) Approved 07/13/2012 07/09/2012
Codes Admin
True
Building Plan Review Approved 06/15/2012 06/12/2012
Mike Weisenborn
Business License
Resolved
06/12/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A minimum of a Class B license is required. This needs to be provided for permit appravel.
License contractors
Resolved
06/12/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical and electrical contracts prior to permit approval.
Fire Plan Review Approved 06/15/2012 06/12/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
06/08/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for sprinkler and alarm system alterations.
Posting of occupant load
Corrective Action Required
06/12/2012

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Misc
Resolved
06/12/2012

Door hardware from the building and assembly areas shall be panic hardware. Confirmed at inspection.
Misc
Resolved
06/12/2012

Provide electrical drawings showing exit and emergency lighting.
Portable fire extinguishers - general
Resolved
06/12/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Show the locations of the fire extinguishers to be provided.
Internal Plan Review (Res) Rejected 06/05/2012 06/05/2012
Mike Weisenborn
License Tax Codes Approved 06/05/2012 06/05/2012
Mike Weisenborn
Building Plan Review Rejected 06/05/2012 06/05/2012
Mike Weisenborn
Business License
Corrective Action Required
06/05/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A minimum of a Class B license is required. This needs to be provided for permit appravel.
License contractors
Corrective Action Required
06/05/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical and electrical contracts prior to permit approval.
Fire Plan Review Rejected 06/05/2012 05/31/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
05/31/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for sprinkler and alarm system alterations.
Posting of occupant load
Corrective Action Required
05/31/2012

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Misc
Corrective Action Required
05/31/2012

Door hardware from the building and assembly areas shall be panic hardware. Confirmed at inspection.
Misc
Corrective Action Required
05/31/2012

Provide electrical drawings showing exit and emergency lighting.
Portable fire extinguishers - general
Corrective Action Required
05/31/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Show the locations of the fire extinguishers to be provided.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 07/09/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 7/25/2012 at 12:00 AM 07/25/2012
Above Ceiling Inspection Passed 07/27/2012
Occupancy Inspection - Codes Commercial Full C of O 7/27/2012 7/27/2012 at 12:00 AM 07/27/2012
Misc
Corrective Action Required
07/27/2012
Occupancy Inspection - Fire Passed 7/27/2012 at 12:00 AM 07/27/2012
Misc
Corrective Action Required
07/27/2012
post wording on glass man door exits " this door to remain unlocked when occupied remove curtains hanging in front of exit door in room 121. note : sprinkler system is due for annual inspction in August
Documents & Images
Date Uploaded File Type Document Name
06/05/2012 Letter Plan Review Conditions
07/09/2012 Letter Building Permit
07/09/2012 Letter Plan Review Conditions
07/25/2012 Letter Inspection Summary
07/27/2012 Letter Inspection Summary
07/27/2012 Letter Fire Loss Reduction Form
07/30/2012 Letter Final Certificate of Occupancy
08/20/2012 Letter DOC082012-008.pdf
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home