Review Type |
Outcome |
Est. Completion Date |
Completed |
Alarm Plan Review
|
Released for Construction
|
|
09/24/2012
|
|
Brian Austerman
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action Required: Call (816) 969-1300 to schedule hood and alarm system testing prior to final
|
|
|
Internal Plan Review (Res)
|
Approved
|
06/22/2012
|
06/15/2012
|
|
Mike Weisenborn
|
|
True
|
License Tax Codes
|
Approved
|
06/22/2012
|
06/13/2012
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
06/14/2012
|
06/13/2012
|
|
Mike Weisenborn
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Misc
Zoning approval must be obtained prior to building permit approval.
|
|
Misc
Sheet AD100 shows cutting the existing parking lot for the installation of the grease interceptor but the plumbing plans show it to be located inside the tenant space.
Action required - Make needed corrections.
Mike Weisenborn 06/13/2012 8:53 AM - Corrections have been made.
|
|
Misc
I have discussed the installation of the pipe bollards with Hector Soto in the Planning and Development Department. The City requires a minimum of 5 feet of clear sidewalk between the curb and any structure, fence or similar item. This is to allow for usable sidewalk when cars are pulled upt to the curb.
Action required - Remove the pipe bollards.
Mike Weisenborn 06/13/2012 8:54 AM - Corrections have been made.
|
|
Misc
I don't believe the area of the space provided in the Code Review includes the building addition.
Action required. Make needed corrections.
Mike Weisenborn 06/13/2012 8:54 AM - Corrections have been made.
|
|
Bldg - Occupant load calculations - Areas without fixed seats
2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Action required - The Code Review indicates the number of seats but not the calculated occupant load. Provide the calculated occupant load of the tenant space.
Mike Weisenborn 06/13/2012 8:55 AM - Information has been provided.
|
|
License Tax Application
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required - The general contractor will need to complete a license tax application prior to permit issuance. There is an applicable license tax of $241.41.for this project due to the addition to the building. This can be paid at the time of permit issuance or it can be deferred to prior to receiving andy type of occupancy.
|
|
Misc
I am unable to locate on the plans the location of the condencing unit for the new walkin.
Action required - Provide additional information.
Mike Weisenborn 06/13/2012 9:01 AM - Have been relocated to the roof of the existing structure to meet screening requirements.
|
|
Misc
Structural information has not been provided for the installation of the new equipment that will either be mount on or suspended from the roof.
Action required - Provide documentation from a structural engineer licensed in the State of Missouri which shows that the existing structure is capable of supporting the new loads or what alterations are required. The documentation is required to be signed and sealed.
Mike Weisenborn 06/13/2012 9:02 AM - A letter from an engineer has been provided.
|
|
Misc
Obtain zoning approval from Planning and Development.
|
|
|
Zoning Review
|
Approved
|
06/14/2012
|
06/12/2012
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved
|
|
06/12/2012
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action Required: Provide construction documents for any sprinkler alterations for review. Sprinkler must be extended into the cooler
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action Required: Provide construction documents for any alarm modifications or additions. The hood and manual pull for the hood must be tied in to the building alarm panel
|
|
Misc
1014.2 Egress through intervening spaces.
Egress through intervening spaces shall comply with this section.
1. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high-hazard occupancy and provide a discernible path of egress travel to an exit.
Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group.
2. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes.
Action Required: Corridor 112 cannot be used as an exit egress as it passes through the kitchen, options are to enclose the corridor from the kitchen or remove the exit sign from the corridor door
|
|
Misc
904.11.5.2 Class K portable fire extinguishers for deep fat fryers.
When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows:
1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One Class K portable fire extinguisher of a minimum 1.5 gallon ( 6 L) capacity.
2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One additional Class K portable fire extinguisher of a minimum 1.5 gallon (6 L) capacity shall be provided.
3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations.
Action Required: Provide a Class K extinguisher under the manual pull for the hood
|
|
Portable fire extinguishers - general
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action Required: Provide a minimum size of 2A10B:C extinguishers
|
|
Misc
1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Action Required: marked exits shall have panic hardware or thumb latch only, double keyed deadbolts are not allowed.
|
|
Misc
907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances.
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Action Required: Duct detectoe shall be monitored by the building alarm panel, in an activation they shall intiate a supervisory signal and unit shut down
|
|
Misc
Corrective Action Required
904.11.1 Manual system operation.
A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system.
Action Required: For information only, verified at inspection
|
|
|
Fire Plan Review
|
Approved
|
05/23/2012
|
06/12/2012
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action Required: Provide construction documents for any sprinkler alterations for review. Sprinkler must be extended into the cooler
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action Required: Provide construction documents for any alarm modifications or additions. The hood and manual pull for the hood must be tied in to the building alarm panel
|
|
Misc
Corrective Action Required
1014.2 Egress through intervening spaces.
Egress through intervening spaces shall comply with this section.
1. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high-hazard occupancy and provide a discernible path of egress travel to an exit.
Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group.
2. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes.
Action Required: Corridor 112 cannot be used as an exit egress as it passes through the kitchen, options are to enclose the corridor from the kitchen or remove the exit sign from the corridor door
|
|
Misc
Corrective Action Required
904.3.4 Alarms and warning signs.
Where alarms are required to indicate the operation of automatic fire-extinguishing systems, distinctive audible, visible alarms and warning signs shall be provided to warn of pending agent discharge. Where exposure to automatic-extinguishing agents poses a hazard to persons and a delay is required to ensure the evacuation of occupants before agent discharge, a separate warning signal shall be provided to alert occupants once agent discharge has begun. Audible signals shall be in accordance with Section 907.10.2.
904.3.5 Monitoring.
Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72.
The kitchen hood and pull shall be monitored by the building's alarm panel
|
|
Misc
Corrective Action Required
904.11.5.2 Class K portable fire extinguishers for deep fat fryers.
When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows:
1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One Class K portable fire extinguisher of a minimum 1.5 gallon ( 6 L) capacity.
2. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One additional Class K portable fire extinguisher of a minimum 1.5 gallon (6 L) capacity shall be provided.
3. For individual fryers exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire extinguishers shall be installed in accordance with the extinguisher manufacturer’s recommendations.
Action Required: Provide a Class K extinguisher under the manual pull for the hood
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action Required: Provide a minimum size of 2A10B:C extinguishers
|
|
Misc
Corrective Action Required
1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Action Required: marked exits shall have panic hardware or thumb latch only, double keyed deadbolts are not allowed.
|
|
Misc
Corrective Action Required
907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances.
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Action Required: Duct detectore shall be monitored by the building alarm panel, in an activation they shall intiate a supervisory signal and unit shut down
|
|
Misc
Corrective Action Required
904.11.1 Manual system operation.
A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system.
Action Required: For information only, verified at inspection
|
|
|
Internal Plan Review (Res)
|
Rejected
|
05/23/2012
|
05/24/2012
|
|
Mike Weisenborn
|
|
Was waiting on a zoning determination which I have not received. Added a comment.
|
Building Plan Review
|
Rejected
|
05/23/2012
|
05/23/2012
|
|
Mike Weisenborn
|
|
Health Dept Review
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required - Provide documentation of plan approval prior to building permit approval.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Misc
Corrective Action Required
Zoning approval must be obtained prior to building permit approval.
|
|
Misc
Corrective Action Required
Sheet AD100 shows cutting the existing parking lot for the installation of the grease interceptor but the plumbing plans show it to be located inside the tenant space.
Action required - Make needed corrections.
|
|
Misc
Corrective Action Required
I have discussed the installation of the pipte bollards with Hector Soto in the Planning and Development Department. The City requires a minimum of 5 feet of clear sidewalk between the curb and any structure, fence or similar item. This is to allow for usable sidewalk when cars are pulled upt to the curb.
Action required - Remove the pipe bollards.
|
|
Misc
Corrective Action Required
I don't believe the area of the space provided in the Code Review includes the building addition.
Action required. Make needed corrections.
|
|
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Action required - The Code Review indicates the number of seats but not the calculated occupant load. Provide the calculated occupant load of the tenant space.
|
|
License Tax Application
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required - The general contractor will need to complete a license tax application prior to permit issuance. There is an applicable license tax of $241.41.for this project due to the addition to the building. This can be paid at the time of permit issuance or it can be deferred to prior to receiving andy type of occupancy.
|
|
Misc
Corrective Action Required
I am unable to locate on the plans the location of the condencing unit for the new walkin.
Action required - Provide additional information.
|
|
Misc
Corrective Action Required
Structural information has not been provided for the installation of the new equipment that will either be mount on or suspended from the roof.
Action required - Provide documentation from a structural engineer licensed in the State of Missouri which shows that the existing structure is capable of supporting the new loads or what alterations are required. The documentation is required to be signed and sealed.
|
|
Misc
Corrective Action Required
Obtain zoning approval from Planning and Development.
|
|
|