Summary
PRCOM20120827
Building Permit - Commercial
Final Completion
LEES SUMMIT SCHOOL DIST R 7
ALTERATION COMMERCIAL
CAFETERIA ALTERATION
04/18/2012
06/07/2012
08/02/2012
Locations
Contacts
HEARTLAND CONSTRUCTION, Address:10647 WIDMER RD  
JAKE'S INDUSTRIAL INC, Address:1101 SW 1ST, Phone:(816) 690-3173  
MAX ELECTRIC INC, Address:705 BLUE RIDGE EXT, Phone:(816) 965-7555  
TAYLOR MECHANICAL INC, Address:23700 E 189th st, Phone:(816) 743-9900  
HOLLIS MILLER ARCHITECTS  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/15/2012 06/07/2012
Codes Admin
True
Fire Plan Review Approved 04/30/2012 05/03/2012
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
05/03/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide construction documents for alarm system modifications
Misc
Corrective Action Required
05/03/2012

1008.3 Turnstiles. Turnstiles or similar devices that restrict travel to one direction shall not be placed so as to obstruct any required means of egress. Exception: Each turnstile or similar device shall be credited with no more than a 50-person capacity where all of the following provisions are met: 1. Each device shall turn free in the direction of egress travel when primary power is lost, and upon the manual release by an employee in the area. 2. Such devices are not given credit for more than 50 percent of the required egress capacity. 3. Each device is not more than 39 inches (991 mm) high. 4. Each device has at least 16.5 inches (419 mm) clear width at and below a height of 39 inches (991 mm) and at least 22 inches (559 mm) clear width at heights above 39 inches (991 mm). Where located as part of an accessible route, turnstiles shall have at least 36 inches (914 mm) clear at and below a height of 34 inches (864 mm), at least 32 inches (813 mm) clear width between 34 inches (864 mm) and 80 inches (2032 mm) and shall consist of a mechanism other than a revolving device. For information only
Building Plan Review Approved 04/30/2012 04/30/2012
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $560.83 $560.83 Paid 06/07/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 6/12/2012 (8:00 to 5:00) 6/12/2012 at 12:00 AM 06/12/2012
Misc
Corrective Action Required
06/12/2012
2" FLOOR DRAIN PIPING ON EXISTING 2" WASTE SYSTEM -- NO ISSUES ON WORKMANSHIP. VENTING NOT INSTALLED PER DRAWING. WRITTEN A/E RESPONSE TO LS CODES REQUIRED BEFORE COVERING.
Underslab Plumbing Inspection - Commercial Partial 6/20/2012 6/20/2012 at 12:00 AM 06/20/2012
Misc
Resolved
06/20/2012
2" FLOOR DRAIN PIPING ON EXISTING 2" WASTE SYSTEM -- NO ISSUES ON WORKMANSHIP. VENTING NOT INSTALLED PER DRAWING. WRITTEN A/E RESPONSE TO LS CODES REQUIRED BEFORE COVERING.
Above Ceiling Inspection Failed 6/27/2012 06/27/2012
Misc
Corrective Action Required
06/27/2012
COMPLETE ALL ELECTRICAL INSTALLATION AND TERMINATIONS; PLUG ALL UNUSED OPENINGS AT J.B.'s; CLOSE ALL BOXES
Misc
Corrective Action Required
06/27/2012
NEC 330.30: SECURE MC ELECTRICAL CABLE WITHIN 12" OF ENTRY TO BOXES EXCEPT FIXTURE WHIPS < 6" LONG
Misc
Corrective Action Required
06/27/2012
REMOVE TEMPORARY ELECTRICAL WIRING
Misc
Corrective Action Required
06/27/2012
AT STUDS ACTING IN TENSION SCREW FLANGE-TO-FLANGE CONNECTIONS AT BOTH FLANGES
Misc
Corrective Action Required
06/27/2012
UNLESS DRAWINGS INDICATE OTHERWISE, MINIMUM 2 SCREWS AT STUD WEB-TO-WEB CONNECTIONS
Above Ceiling Inspection Partial 6/28/2012 6/28/2012 at 12:00 AM 06/28/2012
Misc
Resolved
06/28/2012
COMPLETE ALL ELECTRICAL INSTALLATION AND TERMINATIONS; PLUG ALL UNUSED OPENINGS AT J.B.'s; CLOSE ALL BOXES
Misc
Resolved
06/28/2012
NEC 330.30: SECURE MC ELECTRICAL CABLE WITHIN 12" OF ENTRY TO BOXES EXCEPT FIXTURE WHIPS < 6" LONG
Misc
Resolved
06/28/2012
REMOVE TEMPORARY ELECTRICAL WIRING
Misc
Partial Correction
06/28/2012
AT STUDS ACTING IN TENSION SCREW FLANGE-TO-FLANGE CONNECTIONS AT BOTH FLANGES: OK TO COVER WHEN READY ALL CLOUD SOFFITS EXCEPT SE 4' AT SOUTH SERVERY WHERE FOUR TENSION STUDS ARE NOT SECURED TO STRUCTURE ABOVE
Misc
Resolved
06/28/2012
UNLESS DRAWINGS INDICATE OTHERWISE, MINIMUM 2 SCREWS AT STUD WEB-TO-WEB CONNECTIONS
Above Ceiling Inspection Partial 7/20/2012 7/20/2012 at 12:00 AM 07/20/2012
Misc
Partial Correction
06/28/2012
AT STUDS ACTING IN TENSION SCREW FLANGE-TO-FLANGE CONNECTIONS AT BOTH FLANGES: OK TO COVER WHEN READY ALL CLOUD SOFFITS EXCEPT SE 4' AT SOUTH SERVERY WHERE FOUR TENSION STUDS ARE NOT SECURED TO STRUCTURE ABOVE
Misc
Corrective Action Required
07/20/2012
ACT TILE AREAS OK TO COVER EXCEPT - AT NORTH SERVERY: 1) TWO LARGE CAN LIGHTS REQUIRE SLACK WIRES 2) FOUR LOCATIONS WITH OPEN BOXES WITH TRANSFORMERS YET TO BE INSTALLED 3) ONE OPEN BOX WHERE POWER POLE TO BE INSTALLED 4) ONE EXISTING ELECT RECEPT AT E WALL TO BE REMOVED OR PROPERLY CLOSED - AT SOUTH SERVERY: 1) TWO LARGE CAN LIGHTS REQUIRE SLACK WIRES 2) THREE LOCATIONS WITH OPEN BOXES WITH TRANSFORMERS YET TO BE INSTALLED
Final Inspection - Commercial Not Ready 8/6/2012 at 12:00 AM 08/06/2012
Misc
Corrective Action Required
08/06/2012
ELECTRICAL WORK IN PROGRESS. CALL FOR INSPECTION WHEN READY. NOTE NEC 210.63 REQUIRES ELECTRICAL RECEPTACLE OUTLET WITHIN 25' OF HACR EQUIPMENT AT SAME LEVEL AS EQUIPMENT FOR SERVICING OF EQUIPMENT
Above Ceiling Inspection Not Ready 8/6/2012 at 12:00 AM 08/06/2012
Misc
Resolved
08/06/2012
AT STUDS ACTING IN TENSION SCREW FLANGE-TO-FLANGE CONNECTIONS AT BOTH FLANGES: OK TO COVER WHEN READY ALL CLOUD SOFFITS EXCEPT SE 4' AT SOUTH SERVERY WHERE FOUR TENSION STUDS ARE NOT SECURED TO STRUCTURE ABOVE
Misc
Corrective Action Required
07/20/2012
ACT TILE AREAS OK TO COVER EXCEPT - AT NORTH SERVERY: 1) TWO LARGE CAN LIGHTS REQUIRE SLACK WIRES 2) FOUR LOCATIONS WITH OPEN BOXES WITH TRANSFORMERS YET TO BE INSTALLED 3) ONE OPEN BOX WHERE POWER POLE TO BE INSTALLED 4) ONE EXISTING ELECT RECEPT AT E WALL TO BE REMOVED OR PROPERLY CLOSED - AT SOUTH SERVERY: 1) TWO LARGE CAN LIGHTS REQUIRE SLACK WIRES 2) THREE LOCATIONS WITH OPEN BOXES WITH TRANSFORMERS YET TO BE INSTALLED
Underslab Plumbing Inspection - Commercial Passed 8/6/2012 at 12:00 AM 08/06/2012
Occupancy Inspection - Fire Temporary C of O 8/6/2012 at 12:00 AM 08/15/2012
Occupancy Inspection - Fire Passed 8/15/2012 at 12:00 AM 08/15/2012
Above Ceiling Inspection Passed 8/15/2012 at 12:00 AM 08/15/2012
Misc
Resolved
08/15/2012
ACT TILE AREAS OK TO COVER EXCEPT - AT NORTH SERVERY: 1) TWO LARGE CAN LIGHTS REQUIRE SLACK WIRES 2) FOUR LOCATIONS WITH OPEN BOXES WITH TRANSFORMERS YET TO BE INSTALLED 3) ONE OPEN BOX WHERE POWER POLE TO BE INSTALLED 4) ONE EXISTING ELECT RECEPT AT E WALL TO BE REMOVED OR PROPERLY CLOSED - AT SOUTH SERVERY: 1) TWO LARGE CAN LIGHTS REQUIRE SLACK WIRES 2) THREE LOCATIONS WITH OPEN BOXES WITH TRANSFORMERS YET TO BE INSTALLED
Final Inspection - Commercial Not Ready 8/6/2012 at 12:00 AM 08/15/2012
Misc
Corrective Action Required
08/06/2012
ELECTRICAL WORK IN PROGRESS. CALL FOR INSPECTION WHEN READY. NOTE NEC 210.63 REQUIRES ELECTRICAL RECEPTACLE OUTLET FOR SERVICING OF EQUIPMENT WITHIN 25' OF HACR EQUIPMENT AT SAME LEVEL AS EQUIPMENT
Final Inspection - Commercial Passed 8/17/2012 at 12:00 AM 08/17/2012
Misc
Resolved
08/16/2012
ELECTRICAL WORK IN PROGRESS. CALL FOR INSPECTION WHEN READY. NOTE NEC 210.63 REQUIRES ELECTRICAL RECEPTACLE OUTLET FOR SERVICING OF EQUIPMENT WITHIN 25' OF HACR EQUIPMENT AT SAME LEVEL AS EQUIPMENT
Documents & Images
Date Uploaded File Type Document Name
06/07/2012 Letter Building Permit
06/07/2012 Letter Plan Review Conditions
06/12/2012 Letter Inspection Summary
06/20/2012 Letter Inspection Summary
06/20/2012 Letter Inspection Summary
06/27/2012 Letter Inspection Summary
06/28/2012 Letter Inspection Summary
07/20/2012 Letter Inspection Summary
08/06/2012 Letter Inspection Summary
08/17/2012 Letter Inspection Summary
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home