Permit Application Status

PRCOM20120798


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20120798
Building Permit - Commercial
Certificate of Occupancy
CP DEER BROOK PLAZA LLC
CHANGE OF TENANT
TENANT FINISH
04/12/2012
05/03/2012
10/21/2012
07/06/2012
Locations
Contacts
CMG CONSTRUCTION , Address:8336 NIEMAN RD, Phone:(913) 384-2284  
SECO INC, Address:7007 COLLEGE BLVD STE 265, Phone:(913) 428-3550  
LONON PLUMBING, Address:507 W 4TH ST, Phone:(816) 916-1003  
CP DEER BROOK PLAZA LLC, Address:3400 COLLEGE BLVD STE 195  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/02/2012
Mike Weisenborn
True
Building Plan Review Approved 05/09/2012 05/02/2012
Mike Weisenborn
License contractors
Resolved
05/02/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the licensed plumbing contractor prior to permit approval.
NEC - Receptacles - Grounding
Resolved
05/02/2012

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Indicate on the plans which rooms will be used for patient exam rooms and provide information on how this requirement will be met.
Fire Plan Review Approved 05/09/2012 05/02/2012
Mike Weisenborn
License Tax Codes Approved 04/24/2012 04/24/2012
Mike Weisenborn
Zoning Review Approved 04/24/2012 04/24/2012
Mike Weisenborn
Internal Plan Review (Res) Rejected 04/24/2012 04/24/2012
Mike Weisenborn
Building Plan Review Rejected 04/24/2012 04/24/2012
Mike Weisenborn
License contractors
Corrective Action Required
05/02/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the licensed plumbing contractor prior to permit approval.
NEC - Receptacles - Grounding
Corrective Action Required
04/23/2012

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Indicate on the plans which rooms will be used for patient exam rooms and provide information on how this requirement will be met.
Fire Plan Review Approved 04/24/2012 04/18/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/18/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler alteration plans for review and approval.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
04/18/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing sprinkler system shall have documentation of a current annual inspection. Verified at inspection.
Misc
Corrective Action Required
04/18/2012

The correct occupancy group for this tenant is a B. Correct the drawings and the occupant load
Misc
Corrective Action Required
04/18/2012

Existing exit signage and emerrgency lighting subject to site inspection.
Portable fire extinguishers - general
Corrective Action Required
04/18/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one, 2A:10B:C fire extinguisher at a conspicuous location.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $39.63 $39.63 Paid 05/03/2012
8331507-Sewer Connection Fee $30.00 $30.00 Paid 05/03/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 5/11/2012 (8:00 to 5:00) 5/11/2012 at 12:00 AM 05/11/2012
Rough Plumbing Inspection - Commercial Passed 5/25/2012 (8:00 to 5:00) 5/29/2012 at 12:00 AM 05/29/2012
Occupancy Inspection - Codes Commercial Temporary C of O 6/20/2012 6/20/2012 at 12:00 AM 06/20/2012
Misc
Corrective Action Required
06/20/2012
-INSTALL UL LISTED SIGN -OBTAIN APPROVAL FROM FIRE DEPARTMENT
Occupancy Inspection - Fire Temporary C of O 6/20/2012 at 12:00 AM 06/20/2012
Misc
Corrective Action Required
06/20/2012
sprinkler system for complex is due for annual inspection - last was 6/13/12 (Jayhawk) remove slide latch bolt locks from rear exir door remove the wording "this door block from the exterior of the rear door and post the numeric address of 1121
Occupancy Inspection - Fire Passed 7/3/2012 at 12:00 AM 07/03/2012
Misc
Corrective Action Required
06/20/2012
sprinkler system for complex is due for annual inspection - last was 6/13/12 (Jayhawk) remove slide latch bolt locks from rear exir door remove the wording "this door block from the exterior of the rear door and post the numeric address of 1121
Misc
Corrective Action Required
07/03/2012
ALL PREVIOUS VIOLATIONS HAVE BEEN RESOLVED OK TO OCCUPY ONCE CLEARED THROUGH CODES ADMINISTRATION
Occupancy Inspection - Codes Commercial Full C of O 7/9/2012 7/9/2012 at 12:00 AM 07/06/2012
Misc
Resolved
07/06/2012
-INSTALL UL LISTED SIGN -OBTAIN APPROVAL FROM FIRE DEPARTMENT
Documents & Images
Date Uploaded File Type Document Name
04/24/2012 Letter Plan Review Conditions
05/03/2012 Letter Building Permit
05/11/2012 Letter Inspection Summary
05/29/2012 Letter Inspection Summary
06/20/2012 Letter Temporary Certificate of Occupancy
06/20/2012 Letter Fire Loss Reduction Form
07/03/2012 Letter Fire Loss Reduction Form
07/06/2012 Letter Field Certificate of Occupancy
07/09/2012 Letter Envelope
07/09/2012 Letter Final Certificate of Occupancy
06/26/2013 Letter Fire Building Plan Review
07/02/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home